Plan Review Notes For Permit 16070628 |
Permit Number |
16070628 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-08-06 08:11:31 | 1) THE PLANS LIST THIS AS A "B" OCCUPANCY. THIS IS AN | | A-3 OCCUPANCY PER CHAPTER 3 OF 2014 FBC. | | 2) A SERVICE SINK IS REQD. PER TABLE 403.1 OF 2014 FBC. | | 3) SUBMIT EXPANDED SANITARY AND WATER RISERS FOR | | REVIEW. IT IS DIFFICULT TO REVIEW THE RISERS AS DRAWN. | | WPB AMEND. TO FBC SEC. 107.2.1. | | 4) IDENTIFY ON THE PLANS THE USE OF THE PREP SINK.WPB | | AMEND. TO FBC SEC. 107.2.1. | | 5) THE SINK LOCATED AT THE FRONT DESK SHALL COMPLY WITH | | THE FBC - ACCESS. SEC. 212 7 606. | | 6) IF THIS IS A CHANGE OF OCCUPANCY THE LAVATORIES | | SHALL BE SUPPLIED WITH HOT OR TEMPERED WATER PER 2014 | | FBC PLUMBING SEC. 607.1. | | 7) SUBMIT ENLARGED FLOOR PLANS FOR THE TOILET ROOMS AND | | SHOWERS.THE SHOWERS, SEATS, CONTROLS, GRAB BARS SHALL | | COMPLY WITH 2014 FBC-ACCESS. SECS.608, 610 & 612. | | 8) THE SAUNA SHALL COMPLY WITH 2014 FBC-ACCESS. | | SEC.612. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | | | | | |
|