Plan Review Notes
Plan Review Notes For Permit 16070628
Permit Number 16070628
Review Stop E
Sequence Number 1
Notes
Date Text
2016-07-21 13:03:01INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PLEASE PROVIDE A NOTE TO INDICATE REQUIRED SEPARATE
 PERMITS FOR ALL LOW VOLTAGE SYSTEMS AND SIGNAGE SHOWN
 ON PLANS. FBC 107.3
 2. PROVIDE A SHOW COMPLIANCE WITH FBC EC 405.7.3,
 405.7.4 SEE VERBIAGE IN THE CODE REGARDING AUTOMATIC
 MEANS OF LIGHTING CONTROLS, BRANCH VOLTAGE DROP AND
 COMPLETIONS DOCUMENTS.
 3. LABEL ALL RECEPTACLES IN LOCKERS AREAS TO BE GFCI
 PROTECTED NEC 210.8B
 4. PROVIDE A SYMBOLS LEGEND FOR ALL DEVICES SHOWN. FBC
 107.3.5
 5. PROVIDE EQUIPMENT SCHEDULE FOR DRYERS, WATER HEATERS
 TO VERIFY 3 PHASE VOLTAGE LOADS
 6. CLARIFY IF ABOVE MOUNTED W/H ARE IN A DROP CEILING,
 JUST NEED CLARIFICATION.
 7. FEEL FREE TO CONTACT ME DIRECTLY SHOULD YOU HAVE ANY
 QUESTIONS OR CONCERNS.
  
  
  