Plan Review Notes For Permit 16070628 |
Permit Number |
16070628 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-07-21 13:03:01 | INITIAL ELECTRICAL PLAN REVIEW | | | | APPLICABLE CODES IN EFFECT: | | FLORIDA BUILDING CODE 2014 5TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | EDITION | | NFPA 70- 2011 NEC | | COMMENTS: | | | | 1. PLEASE PROVIDE A NOTE TO INDICATE REQUIRED SEPARATE | | PERMITS FOR ALL LOW VOLTAGE SYSTEMS AND SIGNAGE SHOWN | | ON PLANS. FBC 107.3 | | 2. PROVIDE A SHOW COMPLIANCE WITH FBC EC 405.7.3, | | 405.7.4 SEE VERBIAGE IN THE CODE REGARDING AUTOMATIC | | MEANS OF LIGHTING CONTROLS, BRANCH VOLTAGE DROP AND | | COMPLETIONS DOCUMENTS. | | 3. LABEL ALL RECEPTACLES IN LOCKERS AREAS TO BE GFCI | | PROTECTED NEC 210.8B | | 4. PROVIDE A SYMBOLS LEGEND FOR ALL DEVICES SHOWN. FBC | | 107.3.5 | | 5. PROVIDE EQUIPMENT SCHEDULE FOR DRYERS, WATER HEATERS | | TO VERIFY 3 PHASE VOLTAGE LOADS | | 6. CLARIFY IF ABOVE MOUNTED W/H ARE IN A DROP CEILING, | | JUST NEED CLARIFICATION. | | 7. FEEL FREE TO CONTACT ME DIRECTLY SHOULD YOU HAVE ANY | | QUESTIONS OR CONCERNS. | | | | | | | | VALENTINO PEREZ | | ELECTRICAL PLANS EXAMINER II | | 561-805-6717 | | [email protected] | | | | | | | | | | |
|