Plan Review Notes
Plan Review Notes For Permit 16070609
Permit Number 16070609
Review Stop R
Sequence Number 2
Notes
Date Text
2016-09-29 13:58:591- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR;
 A) ROOF TILE AS SPECIFIED ON PLANS. NOA 07-0919.05
 SUBMITTED EXPIRED ON 12/16/12. NEED CURRENT NOA.
  
 2- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1
 CITY AMENDMENTS.
  
 3- CLARIFY WHY SUBMITTING NOA 13-1217.01 FOR FLAT ROOF
 DECKS. PLANS DON'T PROVIDE ANY SPECIFICATION FOR THIS
 TYPE OF ROOFING. AND, CLEARLY IDENTIFY APPROVED
 ASSEMBLY TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. NOTE:
 IF SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES
 FOR ALL ROOF ZONES, THEN SIGNED AND SEALED RAS 117
 CALCULATIONS WILL BE REQUIRED. SEE GENERAL LIMITATION
 #7 ON LAST PAGE OF NOA SUBMITTED.
  
  