2016-09-29 08:47:56 | 10/31/16 |
| BUILDING REVIEW MAY BE APPROVED WITH PROVISO AFTER |
| CONTRACTOR'S INFORMATION IS UPDATED. PRODUCT APPROVALS |
| MAY BE SUBMITTED LATER. CONTRACTOR TO ADVICE IF PROVISO |
| OPTION IS PREFERRED AT THIS TIME. |
| |
| |
| RESIDENTIAL (R3) ADDITION/ALTERATION SECOND BUILDING |
| REVIEW CHECKLIST. |
| CODE: FBC 5TH EDITION (2014). |
| |
| ORIGINAL COMMENT: |
| 1- CONTRACTOR LICENSE NUMBER SHOWN ON THE PERMIT |
| APPLICATION (CPC057027) IS FOR A POOL CONTRACTOR. NEED |
| TO PROVIDE LICENSE OF GENERAL, BUILDING OR RESIDENTIAL |
| CONTRACTOR. SEC. 489.113 FLORIDA STATUTES. |
| |
| RESPONSE: |
| NOT ADDRESSED. NEED TO REVISE INFORMATION ON THE PERMIT |
| APPLICATION TO UPDATE INFORMATION THE CITY SYSTEM. |
| |
| 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| FAC 61G20-3.002(33) FOR; |
| A) ROOF TILE AS SPECIFIED ON PLANS. NOA 07-0919.05 |
| SUBMITTED EXPIRED ON 12/16/12. NEED CURRENT NOA. |
| |
| B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON |
| DETAILS AND PLANS. PROVIDE ONLY THE FLORIDA PRODUCT |
| APPROVAL COVER PAGE AND PAGE SHOWING THE SPECIFIED |
| CONNECTOR OR ARCHITECT TO LIST THE CURRENT FLORIDA |
| PRODUCT APPROVAL NUMBER NEXT TO EACH SPECIFIED |
| CONNECTOR. |
| NOTE: NOA 03-0123.05 SUBMITTED EXPIRED ON FEBRUARY 16, |
| 2008. NEED CURRENT NOA OR FLORIDA PRODUCT APPROVAL. |
| |
| 3- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| ALL PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1 |
| CITY AMENDMENTS. |
| NOTE: NEED TO APPROVE ALL THE PRODUCT APPROVALS, |
| INCLUDING THE ONES THAT WERE SUBMITTED EARLIER. |
| |
| 4- CLARIFY WHY SUBMITTING NOA 13-1217.01 FOR FLAT ROOF |
| DECKS. PLANS DON'T PROVIDE ANY SPECIFICATION FOR THIS |
| TYPE OF ROOFING. AND, CLEARLY IDENTIFY APPROVED |
| ASSEMBLY TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE |
| DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. NOTE: |
| IF SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES |
| FOR ALL ROOF ZONES, THEN SIGNED AND SEALED RAS 117 |
| CALCULATIONS WILL BE REQUIRED. SEE GENERAL LIMITATION |
| #7 ON LAST PAGE OF NOA SUBMITTED. |
| |
| |
| ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| DRAWING. PLEASE DON"T STAPLE OLD DRAWING. SUBMITT OLD |
| DRAWINGS FOR REFERENCE. |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| DEVELOPMENT SERVICES DEPARTMENT |
| (561)805-6712 |
| [email protected] |