2016-08-25 10:09:15 | RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW |
| COMMENTS. |
| CODE: FBC 5TH EDITION (2014). |
| |
| 1- CONTRACTOR LICENSE NUMBER SHOWN ON THE PERMIT |
| APPLICATION (CPC057027) IS FOR A POOL CONTRACTOR. NEED |
| TO PROVIDE LICENSE OF GENERAL, BUILDING OR RESIDENTIAL |
| CONTRACTOR. SEC. 489.113 FLORIDA STATUTES. |
| |
| 2- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH |
| COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT. |
| BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID |
| RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF |
| THE UNIFIED LAND DEVELOPMENT CODE. NOTE: THIS MAY BE |
| DONE LATER WHEN THE PERMIT IS READY TO BE ISSUED |
| |
| 3- SHEET A3: |
| A) FOUNDATION PLAN IS NOT CLEAR. FOUNDATION PLAN AND |
| FOOTING SCHEDULE DON'T MATCH. THE THICKENED EDGE IS NOT |
| SHOWN ON THE FOUNDATION PLAN. REVISE AS REQUIRED. SEC. |
| 107.2.1 CITY AMENDMENTS. |
| |
| B) FOOTING SCHEDULE IS NOT CLEAR. THE DEPTH DIMENSION |
| SHOWN FOR FOOTING F1 DOESN'T MATCH THE FOOTING DEPTH |
| SPECIFIED UNDER DESCRIPTION. REVISE AS REQUIRED. SEC. |
| 107.2.1 CITY AMENDMENTS. |
| |
| C) SPECIFY THE SIZE OF THE TREADS ON THE TYP. STONE |
| STAIR DETAIL. SEC. R311.7.5.2 FBC-RESIDENTIAL, 5TH |
| EDITION (2014). |
| |
| 4- PROVIDE COMPLETE FRAMING DETAILS FOR THE NEW FRENCH |
| DOORS WITH SIDELITES AS SHOWN ON PLANS. SPECIFY ALL |
| FRAMING MEMBERS AND CONNECTORS. SEC. R301.1 |
| FBC-RESIDENTIAL. |
| |
| 5- SHEET A5: |
| A) SPECIFY Y CONNECTORS AT TOP AND BOTTOM OF CORNER AND |
| MIDDLE COLUMNS TO SHOW THE COMPLETE LOAD PATH AS |
| REQUIRED BY SEC. R301.1 FBC-RESIDENTIAL. |
| NOTE: SPECIFYING SIMPSON POST CAP AND BASE IS NOT |
| ENOUGH INFORMATION. THERE ARE MANY TYPES OF CONNECTORS. |
| CORNER CONNECTORS ARE DIFFERENT. ALSO, TAKE INTO |
| CONSIDERATION HOW THE POST BASE IS ATTACHED TO THE |
| SPECIFIED CONCRETE BLOCK COLUMN. |
| |
| B) CONNECTOR DETAIL "B". SPECIFY WHAT IS THIS CONNECTOR |
| ATTACHED TO IN ORDER TO GET 4" MIN. EMBEDMENT. ALSO, |
| SPECIFIED BOLT SEEMS TO BE FOR MASONRY APPLICATION. |
| REVISE AS REQUIRED. NOTE: CONNECTION AT THE SOUTH END |
| MAY NEED SPECIAL ATTENTION. THERE IS NO PARAPET WALL |
| BEHIND. SEE RIGHT ELEVATION ON SHEET A4. SEC. R301.1 |
| FBC-RESIDENTIAL. |
| |
| C) THE LATERAL LOADS F1 AND F2 SHOWN ON THE SIMPSON |
| CONNECTION SCHEDULE ARE INCORRECT. FROM WHERE ARE THESE |
| VALUES TAKEN FROM?. REVISE AS REQUIRED. SEC. R301.1 |
| FBC-RESIDENTIAL. |
| |
| D) INFORMATION SHOWN ON PORCH SECTION IS NOT CLEAR. (1) |
| THE 2 X 12 LEDGER SPECIFIED ON THE ROOF FRAMING PLAN IS |
| NOT SHOWN. (2) IT DOESN'T MATCH INFORMATION SHOWN ON |
| PORCH SECTION ON SHEET A4. THE ROOF PITCH IS DIFFERENT. |
| THE PARAPET AND 2X12 LEDGER INFORMATION IS DIFFERENT. |
| (3) THE CONCRETE SLAB DOESN'T SHOW THE THICKENED EDGE |
| OF FOOTING F2 SHOWN ON THE FOUNDATION PLAN. REVISE AS |
| REQUIRED. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| E) ATTACHMENT OF THE 2 X 12 LEDGER SHOWN ON THE ROOF |
| FRAMING PLAN IS NOT CLEAR. WHAT IS THE FASTENER |
| ATTACHED TO IN ORDER TO BE 16" ON CENTER AND HAVE 4" |
| EMBEDMENT. SEC. R301.1 FBC-RESIDENTIAL. |
| |
| F) BEAM TO COLUMN DETAIL IS NOT CLEAR. (1) WOOD BEAM |
| DOESN'T MATCH SIZE SPECIFIED ON ROOF FRAMING PLAN. |
| (2)WHAT IS CONNECTOR "F". (3) COORDINATE WITH SPECIFIED |
| POST CAP. (4) THIS IS A CORNER DETAIL. HOW ARE THE TWO |
| BEAMS SEATED ON THE 6" POST. SEC. R301.1 |
| FBC-RESIDENTIAL. |
| |
| G) ROOF DESIGN CRITERIA DOESN'T MATCH DESIGN CRITERIA |
| SHOWN ON PAGE A. REVISE AS REQUIRED TO MATCH. SEC. |
| R301.1 FBC-RESIDENTIAL. |
| |
| 6- SHEET A: |
| A) THE TOTAL MIN. ROOF LOAD SHOWN ON THE DESIGN |
| CRITERIA IS INCORRECT. REVISE AS REQUIRED. SEC. R301.1 |
| FBC-RESIDENTIAL. |
| |
| B) THIS IS ALTERATION LEVEL 3 NOT 2. REVISE AS |
| REQUIRED. SEC. 505 FBC-EXISTING BUILDING, 5TH EDITION |
| (2014). |
| |
| C) UPDATE WOOD NOTES #2 AND #3. THE CURRENT CODE IS THE |
| FBC 5TH EDITION (2014) NOT 2010 OR 2004. SEC. 553 |
| FLORIDA STATUTES. |
| |
| 7- SHEET SP1: |
| A) SITE PLAN SHOWS AN EXISTING GUEST HOUSE IN THE BACK |
| OF THE LOT. THIS STRUCTURE IS SUPPOSED TO BE A GARAGE. |
| ACCORDING TO CITY RECORDS AND PBC PROPERTY APPRAISER |
| THIS STRUCTURE IS A GARAGE NOT GUEST HOUSE. REVISE AS |
| REQUIRED, INCLUDING THE AREA CALCULATIONS. IF PROPOSING |
| GUEST HOUSE, THEN REVISE PLANS AS REQUIRED. PLANS WILL |
| NEED TO BE REVIEWED BY PALM BEACH COUNTY FOR IMPACT |
| FEES ASSESSMENT. CONTACT ZONING TO VERIFY IF GUEST |
| HOUSE IS ALLOWED. INSPECTION WILL BE REQUIRED TO VERIFY |
| USE OF EXISTING STRUCTURE. SEC. 102.2 CITY AMENDMENTS. |
| |
| B) FOR YOUR INFORMATION: DRIVEWAYS AND FENCES REQUIRE |
| SEPARATE PERMITS. PROVIDE COMPLETE INFORMATION |
| SEPARATELY TO AVOID CONFLICTS/DELAYS. |
| |
| 8- OUTLOOKERS ON RIGHT ELEVATION ON SHEET A4 ARE NOT |
| CLEAR: SPACING OF THE OUTLOOKERS SHOWN DON'T MATCH |
| SPACING SHOWN ON THE ROOF FRAMING PLAN. REVISE AS |
| REQUIRED. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 9- DESIGNER OF RECORD TO SPECIFY ROOF TILE FASTENING AS |
| REQUIRED BY SEC. 107.2.1.2 CITY AMENDMENTS. IF USING |
| SCREWS, THEN SPECIFY NUMBER AND SIZE OF SCREWS. IF |
| USING ADHESIVE, THEN PRODUCT APPROVAL IS REQUIRED. |
| |
| 10- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| FAC 61G20-3.002(33) FOR; |
| A) ROOF TILE AS SPECIFIED ON PLANS. |
| |
| B) ROOF TILE ADHESIVE IF SPECIFIED BY THE ARCHITECT OF |
| RECORD. SEE ROOF TILE PRODUCT APPROVAL FOR LISTED |
| ADHESIVES. |
| |
| C) ALL SIMPSON AND USP STRUCTURAL CONNECTORS SPECIFIED |
| ON DETAILS AND PLANS. PROVIDE ONLY THE FLORIDA PRODUCT |
| APPROVAL COVER PAGE AND PAGE SHOWING THE SPECIFIED |
| CONNECTOR OR ARCHITECT TO LIST THE CURRENT FLORIDA |
| PRODUCT APPROVAL NUMBER NEXT TO EACH SPECIFIED |
| CONNECTOR. |
| |
| D) INSWING ENTRY DOOR AS SHOWN ON PLANS. |
| |
| 11- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| |
| ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| DRAWING. PLEASE DON"T STAPLE OLD DRAWING. SUBMITT OLD |
| DRAWINGS FOR REFERENCE. |
| |