Plan Review Notes
Plan Review Notes For Permit 16070609
Permit Number 16070609
Review Stop B
Sequence Number 1
Notes
Date Text
2016-08-25 10:09:15RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- CONTRACTOR LICENSE NUMBER SHOWN ON THE PERMIT
 APPLICATION (CPC057027) IS FOR A POOL CONTRACTOR. NEED
 TO PROVIDE LICENSE OF GENERAL, BUILDING OR RESIDENTIAL
 CONTRACTOR. SEC. 489.113 FLORIDA STATUTES.
  
 2- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE. NOTE: THIS MAY BE
 DONE LATER WHEN THE PERMIT IS READY TO BE ISSUED
  
 3- SHEET A3:
 A) FOUNDATION PLAN IS NOT CLEAR. FOUNDATION PLAN AND
 FOOTING SCHEDULE DON'T MATCH. THE THICKENED EDGE IS NOT
 SHOWN ON THE FOUNDATION PLAN. REVISE AS REQUIRED. SEC.
 107.2.1 CITY AMENDMENTS.
  
 B) FOOTING SCHEDULE IS NOT CLEAR. THE DEPTH DIMENSION
 SHOWN FOR FOOTING F1 DOESN'T MATCH THE FOOTING DEPTH
 SPECIFIED UNDER DESCRIPTION. REVISE AS REQUIRED. SEC.
 107.2.1 CITY AMENDMENTS.
  
 C) SPECIFY THE SIZE OF THE TREADS ON THE TYP. STONE
 STAIR DETAIL. SEC. R311.7.5.2 FBC-RESIDENTIAL, 5TH
 EDITION (2014).
  
 4- PROVIDE COMPLETE FRAMING DETAILS FOR THE NEW FRENCH
 DOORS WITH SIDELITES AS SHOWN ON PLANS. SPECIFY ALL
 FRAMING MEMBERS AND CONNECTORS. SEC. R301.1
 FBC-RESIDENTIAL.
  
 5- SHEET A5:
 A) SPECIFY Y CONNECTORS AT TOP AND BOTTOM OF CORNER AND
 MIDDLE COLUMNS TO SHOW THE COMPLETE LOAD PATH AS
 REQUIRED BY SEC. R301.1 FBC-RESIDENTIAL.
 NOTE: SPECIFYING SIMPSON POST CAP AND BASE IS NOT
 ENOUGH INFORMATION. THERE ARE MANY TYPES OF CONNECTORS.
 CORNER CONNECTORS ARE DIFFERENT. ALSO, TAKE INTO
 CONSIDERATION HOW THE POST BASE IS ATTACHED TO THE
 SPECIFIED CONCRETE BLOCK COLUMN.
  
 B) CONNECTOR DETAIL "B". SPECIFY WHAT IS THIS CONNECTOR
 ATTACHED TO IN ORDER TO GET 4" MIN. EMBEDMENT. ALSO,
 SPECIFIED BOLT SEEMS TO BE FOR MASONRY APPLICATION.
 REVISE AS REQUIRED. NOTE: CONNECTION AT THE SOUTH END
 MAY NEED SPECIAL ATTENTION. THERE IS NO PARAPET WALL
 BEHIND. SEE RIGHT ELEVATION ON SHEET A4. SEC. R301.1
 FBC-RESIDENTIAL.
  
 C) THE LATERAL LOADS F1 AND F2 SHOWN ON THE SIMPSON
 CONNECTION SCHEDULE ARE INCORRECT. FROM WHERE ARE THESE
 VALUES TAKEN FROM?. REVISE AS REQUIRED. SEC. R301.1
 FBC-RESIDENTIAL.
  
 D) INFORMATION SHOWN ON PORCH SECTION IS NOT CLEAR. (1)
 THE 2 X 12 LEDGER SPECIFIED ON THE ROOF FRAMING PLAN IS
 NOT SHOWN. (2) IT DOESN'T MATCH INFORMATION SHOWN ON
 PORCH SECTION ON SHEET A4. THE ROOF PITCH IS DIFFERENT.
 THE PARAPET AND 2X12 LEDGER INFORMATION IS DIFFERENT.
 (3) THE CONCRETE SLAB DOESN'T SHOW THE THICKENED EDGE
 OF FOOTING F2 SHOWN ON THE FOUNDATION PLAN. REVISE AS
 REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 E) ATTACHMENT OF THE 2 X 12 LEDGER SHOWN ON THE ROOF
 FRAMING PLAN IS NOT CLEAR. WHAT IS THE FASTENER
 ATTACHED TO IN ORDER TO BE 16" ON CENTER AND HAVE 4"
 EMBEDMENT. SEC. R301.1 FBC-RESIDENTIAL.
  
 F) BEAM TO COLUMN DETAIL IS NOT CLEAR. (1) WOOD BEAM
 DOESN'T MATCH SIZE SPECIFIED ON ROOF FRAMING PLAN.
 (2)WHAT IS CONNECTOR "F". (3) COORDINATE WITH SPECIFIED
 POST CAP. (4) THIS IS A CORNER DETAIL. HOW ARE THE TWO
 BEAMS SEATED ON THE 6" POST. SEC. R301.1
 FBC-RESIDENTIAL.
  
 G) ROOF DESIGN CRITERIA DOESN'T MATCH DESIGN CRITERIA
 SHOWN ON PAGE A. REVISE AS REQUIRED TO MATCH. SEC.
 R301.1 FBC-RESIDENTIAL.
  
 6- SHEET A:
 A) THE TOTAL MIN. ROOF LOAD SHOWN ON THE DESIGN
 CRITERIA IS INCORRECT. REVISE AS REQUIRED. SEC. R301.1
 FBC-RESIDENTIAL.
  
 B) THIS IS ALTERATION LEVEL 3 NOT 2. REVISE AS
 REQUIRED. SEC. 505 FBC-EXISTING BUILDING, 5TH EDITION
 (2014).
  
 C) UPDATE WOOD NOTES #2 AND #3. THE CURRENT CODE IS THE
 FBC 5TH EDITION (2014) NOT 2010 OR 2004. SEC. 553
 FLORIDA STATUTES.
  
 7- SHEET SP1:
 A) SITE PLAN SHOWS AN EXISTING GUEST HOUSE IN THE BACK
 OF THE LOT. THIS STRUCTURE IS SUPPOSED TO BE A GARAGE.
 ACCORDING TO CITY RECORDS AND PBC PROPERTY APPRAISER
 THIS STRUCTURE IS A GARAGE NOT GUEST HOUSE. REVISE AS
 REQUIRED, INCLUDING THE AREA CALCULATIONS. IF PROPOSING
 GUEST HOUSE, THEN REVISE PLANS AS REQUIRED. PLANS WILL
 NEED TO BE REVIEWED BY PALM BEACH COUNTY FOR IMPACT
 FEES ASSESSMENT. CONTACT ZONING TO VERIFY IF GUEST
 HOUSE IS ALLOWED. INSPECTION WILL BE REQUIRED TO VERIFY
 USE OF EXISTING STRUCTURE. SEC. 102.2 CITY AMENDMENTS.
  
 B) FOR YOUR INFORMATION: DRIVEWAYS AND FENCES REQUIRE
 SEPARATE PERMITS. PROVIDE COMPLETE INFORMATION
 SEPARATELY TO AVOID CONFLICTS/DELAYS.
  
 8- OUTLOOKERS ON RIGHT ELEVATION ON SHEET A4 ARE NOT
 CLEAR: SPACING OF THE OUTLOOKERS SHOWN DON'T MATCH
 SPACING SHOWN ON THE ROOF FRAMING PLAN. REVISE AS
 REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 9- DESIGNER OF RECORD TO SPECIFY ROOF TILE FASTENING AS
 REQUIRED BY SEC. 107.2.1.2 CITY AMENDMENTS. IF USING
 SCREWS, THEN SPECIFY NUMBER AND SIZE OF SCREWS. IF
 USING ADHESIVE, THEN PRODUCT APPROVAL IS REQUIRED.
  
 10- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR;
 A) ROOF TILE AS SPECIFIED ON PLANS.
  
 B) ROOF TILE ADHESIVE IF SPECIFIED BY THE ARCHITECT OF
 RECORD. SEE ROOF TILE PRODUCT APPROVAL FOR LISTED
 ADHESIVES.
  
 C) ALL SIMPSON AND USP STRUCTURAL CONNECTORS SPECIFIED
 ON DETAILS AND PLANS. PROVIDE ONLY THE FLORIDA PRODUCT
 APPROVAL COVER PAGE AND PAGE SHOWING THE SPECIFIED
 CONNECTOR OR ARCHITECT TO LIST THE CURRENT FLORIDA
 PRODUCT APPROVAL NUMBER NEXT TO EACH SPECIFIED
 CONNECTOR.
  
 D) INSWING ENTRY DOOR AS SHOWN ON PLANS.
  
 11- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. PLEASE DON"T STAPLE OLD DRAWING. SUBMITT OLD
 DRAWINGS FOR REFERENCE.
  