Plan Review Notes For Permit 16070599 |
Permit Number |
16070599 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-07-18 15:01:22 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | 1) SHEET FA - THE SUBMITTED SPEC SHEET FOR THE DUCT | | DETECTORDOES NOT APPEAR TO MATCH THE PRODUCT NUMBER IN | | THE FIRE ALARM LEGEND. | | | | PLEASE CORRECT, VERIFY OR JUSTIFY. | | | | 2) SHEET FA - THE DUCT SMOKE DETECTORS ARE CLOUDED ON | | THE FLOOR PLAN BUT NOT ON THE FIRE ALARM LEGEND. | | | | PLEASE CLOUD BOTH AS APPLICABLE. | | | | 3) SHEET FA - THERE ARE NO CLOUDS INDICATED ON THE FIRE | | ALARM CALCULATION TABLES FOR THE ADDED DEVICES. | | | | PLEASE CLOUD AS APPLICABLE. | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|