Plan Review Notes
Plan Review Notes For Permit 16070516
Permit Number 16070516
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2016-07-22 15:26:05THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) SHEET A2 - PER NFPA 101, CHAPTER 43 BUILDING
 REHABILITATION
  
  
 43.4 RENOVATIONS.
 43.4.1 GENERAL REQUIREMENTS.
 43.4.1.3 ALL NEW WORK SHALL COMPLY WITH THE
 REQUIREMENTS OF THIS CODE APPLICABLE TO EXISTING
 BUILDINGS.
 43.4.1.4 THE WORK SHALL NOT MAKE THE BUILDING LESS
 CONFORMING WITH OTHER SECTIONS OF THIS CODE, OR WITH
 ANY PREVIOUS APPROVED ALTERNATIVE ARRANGEMENTS, THAN IT
 WAS BEFORE THE RENOVATION WAS UNDERTAKEN, UNLESS
 OTHERWISE SPECIFIED IN 43.4.1.5.
  
 ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR
 CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND
 SPRINKLER SYSTEM FOR CODE COVERAGE AND COMPLIANCE BY
 CERTIFIED LIFE SAFETY CONTRACTORS.
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  
 2) THE FIRE INSPECTOR WILL REVIEW AND VERIFY COMPLAINCE
 NOTED ABOVE. PLEASE ENSURE REVIEW AND COMPLAINCE PRIOR
 TO INSPECTION.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  