 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 THE ELECTRIC PLAN SHOWS TWO KITCHENS. PLEASE CLARIFY.
  
 PROVIDE A 20 AMPERE KITCHEN COUNTER TOP RECEPTACLES AS
 REQUIRED FOR ALL COUNTER SPACES. FBC E3901.4
  
 PROVIDE A 20 AMPERE RECEPTACLE CIRCUIT FOR THE DINING
 AREA/ KITCHEN WALL SPACE. FBC E3901.3
  
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND
 OUTSIDE EACH SLEEPING AREA INCLUDING THE SECOND FLOOR.
 IF THE BUILDING HAS GAS APPLIANCES, AN ATTACHED GARAGE
 OR A FIREPLACE, A CARBON MONOXIDE DETECTOR IS REQUIRED
 WITHIN TEN FEET OF EACH ROOM USED FOR SLEEPING. FBC
 R314, 315
  
 A DEDICATED LAUNDRY BRANCH CIRCUIT AND RECEPTACLE IS
 REQUIRED. FBC E3703.3
  
 PROVIDE WALL SWITCHED CONTROLLED LIGHTING AT ALL
 ENTRANCES. FBC E3903,
  
 SHOW THE LOCATION OF THE ELECTRICAL PANEL AND MAIN
 DISCONNECTS. FBC E3405, E3603
  