Notes |
Date |
Text |
2017-02-21 11:30:38 | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | ELECTRICAL REVIEW COMMENTS. | | | | THE ELECTRIC PLAN SHOWS TWO KITCHENS. PLEASE CLARIFY. | | | | PROVIDE A 20 AMPERE KITCHEN COUNTER TOP RECEPTACLES AS | | REQUIRED FOR ALL COUNTER SPACES. FBC E3901.4 | | | | PROVIDE A 20 AMPERE RECEPTACLE CIRCUIT FOR THE DINING | | AREA/ KITCHEN WALL SPACE. FBC E3901.3 | | | | REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO | | INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND | | OUTSIDE EACH SLEEPING AREA INCLUDING THE SECOND FLOOR. | | IF THE BUILDING HAS GAS APPLIANCES, AN ATTACHED GARAGE | | OR A FIREPLACE, A CARBON MONOXIDE DETECTOR IS REQUIRED | | WITHIN TEN FEET OF EACH ROOM USED FOR SLEEPING. FBC | | R314, 315 | | | | A DEDICATED LAUNDRY BRANCH CIRCUIT AND RECEPTACLE IS | | REQUIRED. FBC E3703.3 | | | | PROVIDE WALL SWITCHED CONTROLLED LIGHTING AT ALL | | ENTRANCES. FBC E3903, | | | | SHOW THE LOCATION OF THE ELECTRICAL PANEL AND MAIN | | DISCONNECTS. FBC E3405, E3603 | | | | ROBERT LECKY | | ELECTRICAL PLANS EXAMINER | | 561-805-6654(OFFICE) | | 561-373-3701(CELL) | | | | | | | | |
|