Plan Review Notes For Permit 16070476 |
Permit Number |
16070476 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-08-11 10:26:37 | REVIEW 2014 5TH FBC ED. NEC 2011 | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 561-805-6713 | | [email protected] | | | | | | 1) SHEET E-1, SHOW PROPER GFCI RECEPTACLE SPACING IN | | THE KITCHEN COUNTERTOP PER NEC 210.52(3)(C) | | | | 2) SHEET E-1, THE A/C DISCONNECT IS SHOWN BEHIN THE CU | | PLEASE RELOCATE TO BE IN COMPLIANCE WITH WORKING | | CLEARANCE. NEC 110.26(A)(1) | | | | 3) SHEET E-1, THE RECEPTACLE BY THE CU SHALL HAVE DUAL | | RATING "WP/WR" LISTING IN ACCORDANCE WITH NEC 406.9(B). | | PLEASE ADD SYMBOL TO OUTLET. | | | | 4) SHEET E-1, SMOKE ALAMS NEED TO BE REFLECTED IN BOTH | | "EXISTING & AREA OF REMODEL" TO COMPLY WITH FBC-R 314 & | | 315. | | | | 5) SHEET E-1, AT LEAST ONE WALL SWITCH SHALL CONTROL A | | LIGHTING OUTLET ON THE EXTERIOR SIDE OF OUTDOOR DOORS. | | NEC 210.70(2)(B) | | | | 6) SHEET E-1, PROVIDE A RISER-DIAGRAM TO VERIFY | | ELECTRICAL DISTRUBUTION SYSTEM AND REFLECT PANEL AND | | SERVICE LOCATION ON THE FLOOR PLAN. FBC-107 |
|