2016-08-09 14:35:54 | BUILDING PLAN REVIEW |
| 2014 FLORIDA BUILDING CODE |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| BUILDING PLANS EXAMINER ? PX3169 |
| CONSTRUCTION SERVICES DIVISION |
| DEVELOPMENT SERVICES DEPARTMENT |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| DATE: 8/9/16 |
| |
| 1. PROVIDE SITE PLAN. |
| 2. SCOPE OF WORK EXCEEDS DESCRIPTION ON APPLICATION. |
| STRUCTURAL CONCRETE, WALLS AND ROOFING SHOWN ON PLANS. |
| 3. STATED VALUE MAY BE LOW. |
| 4. ROOFING PERMIT REQUIRED. |
| 5. PROVIDE RE-INFORCING DTAIL FOR NEW BOND BEAMS. |
| 6. DETAIL 1, PG A-4 INDICATES NEW ROOF RAFTERS. DEMO |
| PLANS SHOWS NO WORK IN THIS AREA.. PLEASE CLARIFY. TO |
| WHAT EXTENT IS ROOFING BEING REMOVED? |
| 7. PROVIDE LANDINGS AT EXTERIOR DOORS. |
| |
| FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| CONSTRUCTION DOCUMENTS SHALL BE |
| DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL. |
| CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL |
| CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, |
| AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS |
| ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH |
| INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES |
| SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE |
| TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE |
| FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS, |
| SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE |
| NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE |
| DESIGN. (SEE ALSO SECTION 107.3.5). |
| |
| [A] 109.3 BUILDING PERMIT VALUATIONS. |
| THE APPLICANT FOR A PERMIT SHALL PROVIDE AN ESTIMATED |
| PERMIT VALUE AT TIME OF APPLICATION. PERMIT VALUATIONS |
| SHALL INCLUDE TOTAL VALUE OF WORK, INCLUDING MATERIALS |
| AND LABOR, FOR WHICH THE PERMIT IS BEING ISSUED, SUCH |
| AS ELECTRICAL, GAS, MECHANICAL, PLUMBING EQUIPMENT AND |
| PERMANENT SYSTEMS. IF, IN THE OPINION OF THE BUILDING |
| OFFICIAL, THE VALUATION IS UNDERESTIMATED ON THE |
| APPLICATION, THE PERMIT SHALL BE DENIED, UNLESS THE |
| APPLICANT CAN SHOW DETAILED ESTIMATES TO MEET THE |
| APPROVAL OF THE BUILDING OFFICIAL. FINAL BUILDING |
| PERMIT VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. |
| |
| R311.3 FLOORS AND LANDINGS AT EXTERIOR DOORS. |
| THERE SHALL BE A LANDING OR FLOOR ON EACH SIDE OF EACH |
| EXTERIOR DOOR. THE WIDTH OF EACH LANDING SHALL NOT BE |
| LESS THAN THE DOOR SERVED. EVERY LANDING SHALL HAVE A |
| MINIMUM DIMENSION OF 36 INCHES (914 MM) MEASURED IN THE |
| DIRECTION OF TRAVEL. EXTERIOR LANDINGS SHALL BE |
| PERMITTED TO HAVE A SLOPE NOT TO EXCEED 1/4 UNIT |
| VERTICAL IN 12 UNITS HORIZONTAL (2-PERCENT). |
| |
| |
| |