Plan Review Notes For Permit 16070433 |
Permit Number |
16070433 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-07-15 11:29:35 | 1ST REVIEW MECHANICAL | | PERMIT #16070433 | | 7/15/16 | | | | 1) SHEET 200-ME-300A: | | | | A) PROVIDE AN AC EQUIPMENT SCHEDULE ON THE PLAN. | | B) PROVIDE INSTALLATION DETAILS FOR THE AIR HANDLER TO | | BE HUNG IN THE CORRIDOR. | | C) INDICATE HOW ACCESS FOR MAINTENANCE AND REPLACEMENT | | OF THE AIR HANDLER WILL BE ACCOMPLISHED- SECTION 306.1 | | D) PROVIDE A CONDENSATE DISPOSAL PLAN- SECTION 307. | | E) PROVIDE WIND LOAD ENGINEERING FOR TIE-DOWN OF THE AC | | CONDENSER AND CONSTRUCTION DETAILS FOR THE MOUNTING | | PAD- SECTION 301.15. | | F) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR THE | | STORAGE/LIBRARY 309 AND SUPER 308 ROOMS PER TABLE | | 403.3. | | G) PROVIDE O/A DUCT DETAILS- TYPE OF DUCT AND GAGE OF | | STEEL, INTAKE LOCATION AND REQUIRED CLEARANCES PER | | SECTION 401.4, AND INTAKE OPENING PROTECTION- 401.5. | | H) PROVIDE A MOTORIZED OR GRAVITY DAMPER FOR THE O/A | | INTAKE WITH AUTOMATIC SHUTOFF CONTROL PER SECTION | | C403.2.4.4 FBC-14 ENERGY CONSERVATION. | | I) AIR DEVICE SCHEDULE. | | | | 2) THE MECHANICAL PLAN SHEET AND THE AC CALCULATIONS | | EACH HAVE COPIED ENGINEER'S SIGNATURES AND SEALS. REFER | | TO SECTION 61G15-23.002 FAC AND PROVIDE PLANS AND | | DOCUMENTS WITH ORIGINAL SEALS AND SIGNATURES. | | | | 3) THERE ARE SEVERAL AHU'S NOTED ON THE ELECTRICAL | | PLANS- PLEASE CLARIFY IF THEY ARE INCLUDED IN THE SCOPE | | OF THIS PROJECT OR FOR REFERENCE ONLY. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|