2016-07-15 11:29:351ST REVIEW MECHANICAL
 PERMIT #16070433
 7/15/16
  
 1) SHEET 200-ME-300A:
  
 A) PROVIDE AN AC EQUIPMENT SCHEDULE ON THE PLAN.
 B) PROVIDE INSTALLATION DETAILS FOR THE AIR HANDLER TO
 BE HUNG IN THE CORRIDOR.
 C) INDICATE HOW ACCESS FOR MAINTENANCE AND REPLACEMENT
 OF THE AIR HANDLER WILL BE ACCOMPLISHED- SECTION 306.1
 D) PROVIDE A CONDENSATE DISPOSAL PLAN- SECTION 307.
 E) PROVIDE WIND LOAD ENGINEERING FOR TIE-DOWN OF THE AC
 CONDENSER AND CONSTRUCTION DETAILS FOR THE MOUNTING
 PAD- SECTION 301.15.
 F) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR THE
 STORAGE/LIBRARY 309 AND SUPER 308 ROOMS PER TABLE
 403.3.
 G) PROVIDE O/A DUCT DETAILS- TYPE OF DUCT AND GAGE OF
 STEEL, INTAKE LOCATION AND REQUIRED CLEARANCES PER
 SECTION 401.4, AND INTAKE OPENING PROTECTION- 401.5.
 H) PROVIDE A MOTORIZED OR GRAVITY DAMPER FOR THE O/A
 INTAKE WITH AUTOMATIC SHUTOFF CONTROL PER SECTION
 C403.2.4.4 FBC-14 ENERGY CONSERVATION.
 I) AIR DEVICE SCHEDULE.
  
 2) THE MECHANICAL PLAN SHEET AND THE AC CALCULATIONS
 EACH HAVE COPIED ENGINEER'S SIGNATURES AND SEALS. REFER
 TO SECTION 61G15-23.002 FAC AND PROVIDE PLANS AND
 DOCUMENTS WITH ORIGINAL SEALS AND SIGNATURES.
  
 3) THERE ARE SEVERAL AHU'S NOTED ON THE ELECTRICAL
 PLANS- PLEASE CLARIFY IF THEY ARE INCLUDED IN THE SCOPE
 OF THIS PROJECT OR FOR REFERENCE ONLY.
  