2016-07-20 10:35:21 | 1ST REVIEW | | | | | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER LL | | CITY OF WEST PALM BEACH | | DEVELOPMENT SERVICES | | BUILDING DIVISION | | 561-805-6711 | | [email protected] | | | | | | GAS COMMENTS: A SEPARATE GAS PERMIT IS REQUIRED | | | | 1. ORIGINAL GAS PLAN SHOWS 3/4 PE PIPE THIS PLAN SHOWS | | EXISTING AS 1IN. PLEASE CLARIFY. PER WPB AMEND. TP FBC | | 107.2.1 | | | | 2. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL | | CUT SECTIONS OF NEW PIPE AND CORRESPONDING LENGTHS PER | | FBC-2014 FUEL GAS, SECS. 402.4.1, 402.4.2. | | | | | | 3. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL | | PIPE SIZES, AND THE EHD NUMBER OF CORRUGATED STAINLESS | | STEEL TUBING FOR EACH PIPE SIZE IF BEING USED. WPB | | AMENDMENTS TO FBC SEC. 107 | | | | 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON | | THE SYSTEM. REFER TO THE FBC-2014 FUEL GAS SECS. 401.8 | | THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(37). | | | | 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, | | (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING | | AND/OR SYSTEM PER THE FBC-2014 FUEL GAS APPENDIX A ? | | USE OF CAPACITY SECTION A.3.1(4) & 2014 FUEL GAS CODE | | SEC. 402.4.1. | | | | 6. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL | | GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA | | 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2 | | |
|