Plan Review Notes
Plan Review Notes For Permit 16070384
Permit Number 16070384
Review Stop E
Sequence Number 1
Notes
Date Text
2016-07-25 09:28:03REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
 - SERVICE EQUIPMENT SEEMS TO BE OVER THE STEPS OF THE
 STAIRWAY ? NEC 240.24(F)
  
 - E3405.1 WORKING SPACE AND CLEARANCES. SUFFICIENT
 ACCESS AND WORKING SPACE SHALL BE PROVIDED AND
 MAINTAINED AROUND ALL ELECTRICAL EQUIPMENT TO PERMIT
 READY AND SAFE OPERATION AND MAINTENANCE OF SUCH
 EQUIPMENT.
  
 - E3405.4 LOCATION OF WORKING SPACES AND
 EQUIPMENT.REQUIRED WORKING SPACE SHALL NOT BE
 DESIGNATED FOR STORAGE. PANELBOARDS AND OVERCURRENT
 PROTECTION DEVICES SHALL NOT BE LOCATED IN CLOTHES
 CLOSETS, IN BATHROOMS, OR OVER THE STEPS OF A STAIRWAY.
  