Plan Review Notes For Permit 16070370
Permit Number 16070370
Review Stop M
Sequence Number 1
Notes
Date Text
2016-07-19 15:59:531ST REVIEW MECHANICAL
 PERMIT #16070370
 7/19/16
  
 1) THE EXHAUST SYSTEMS FOR THE NEW GAS DRYERS SHALL BE
 DONE IN ACCORDANCE WITH THE MANUFACTURER'S
 SPECIFICATIONS. PLEASE PROVIDE PRODUCT SUBMITTALS
 APPROVED WITH SIGNATURE BY THE EOR. REFER TO SECTION
 504.7 AND PROVIDE COMPLETE DETAILS INCLUDING EXHAUST
 DUCT SIZES AND GAGE OF STEEL, LENGTH OF DUCT RUNS,
 LOCATIONS OF CLEANOUTS, SEQUENCE OF OPERATION FOR
 MULTIPLE INSTALLATIONS (IF APPLICABLE), CLEARANCE TO
 COMBUSTIBLES, PLEASE NOTE THAT REUSE OF EXISTING
 EXHAUST DUCTS OR REPLACEMENT WITH THE SAME TYPE MAY NOT
 BE COMPLIANT WITH MANUFACTURER'S SPECIFICATIONS.
  
 2) INDICATE HOW COMBUSTION AIR IS BEING PROVIDED FOR
 THE GAS DRYERS AND PROVIDE CALCULATIONS- SECTION 304
 FBC-14 FUEL GAS. PLEASE NOTE THAT REUSE OF EXISTING
 DUCTS, WHERE NOTED ON THE PLAN, MAY NOT BE COMPLIANT
 WITH MANUFACTURER'S SPECS.
  
 3) SUBMIT TWO COPIES OF THE MIAMI-DADE NOA #13-1017.09
 FOR THE AC STAND.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER