2016-08-04 07:22:01 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 16070370 |
| ADD: 6021 S. DIXIE HWY. |
| CONT: SISCA CONSTRUCTION |
| TEL: 561-228-7503 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: THURS. AUGUST 04/ 2016 |
| ACTION: DENIED |
| |
| 1) SHEET A210 NOTES INDICATE THE INSTALLATION OF NEW |
| GRAB BARS IN THE RESTROOM. THE GRAB BAR DETAIL |
| INDICATES THE INSTALLATION FROM FINISH FLOOR TO CENTER |
| LINE OF GRAB BAR 33-36 INCHES. PLEASE NOTE UNDER THE |
| 2014 FBC-ACCESS. CODE THE MEASUREMENTS ARE TAKEN FROM |
| FINISH FLOOR TO THE TOP (GRASPING SURFACE) OF THE GRAB |
| BAR. 2014 FBC- ACCESS. CODE 609.4 POSITION OF GRAB |
| BARS. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL |
| POSITION, 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 |
| MM) MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP |
| OF THE GRIPPING SURFACE, EXCEPT THAT AT WATER CLOSETS. |
| |
| 2) SHEET M1.2 INDICATES THE INSTALLATION OF NEW ROOFTOP |
| A/C CONDENSER STANDS. 2014 FBC-B 1609.1.2 PROTECTION OF |
| OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA |
| DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 |
| (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS |
| THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31)(G) PRE-ENGINEERED A/C STANDS |
| |
| 3) ADMINISTRATION 107.3.4 DESIGN PROFESSIONAL IN |
| RESPONSIBLE CHARGE. THE REGISTERED DESIGN |
| PROFESSIONAL IN RESPONSIBLE CHARGE SHALL BE RESPONSIBLE |
| FOR REVIEWING AND COORDINATING SUBMITTAL DOCUMENTS |
| PREPARED BY OTHERS, INCLUDING PHASED AND DEFERRED |
| SUBMITTAL ITEMS, FOR COMPATIBILITY WITH THE DESIGN OF |
| THE BUILDING. THOSE PRODUCTS WHICH ARE REGULATED BY DCA |
| RULE 9N-3SHALL BE REVIEWED AND APPROVED IN WRITING BY |
| THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. |
| |
| 4) PLEASE PROVIDE THE WIND DESIGN CRITERIA FOR ROOF |
| STANDS PRESSURES ALSO FOR ROOF ZONES. 2014 FBC-B |
| 1603.1.4 WIND DESIGN DATA. THE FOLLOWING INFORMATION |
| RELATED TO WIND LOADS SHALL BE SHOWN, REGARDLESS OF |
| WHETHER WIND LOADS GOVERN THE DESIGN OF THE LATERAL |
| FORCE-RESISTING SYSTEM OF THE STRUCTURE: |
| |
| 4.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED, |
| VASD, AS DETERMINED IN ACCORDANCE WITH SECTION |
| 1609.3.1. |
| |
| 4.2. RISK CATEGORY. |
| |
| 4.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| THAN ONE WIND EXPOSURE IS UTILIZED. |
| |
| 4.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| |
| 4.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY |
| DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL |
| RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/ |
| M2). |
| TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| BUILDING. |
| 1609.3.1 WIND SPEED CONVERSION VULT TO VASD. |
| |
| 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |