2017-02-09 15:19:19 | RESIDENTIAL (R3) ALTERATIONS FOURTH BUILDING REVIEW |
| CHECKLIST. |
| CODE: FBC-5TH EDITION (2014). |
| |
| 1- A) ENGINEER TO PAY FOUR TIMES THE PLAN REVIEW FEES |
| AS REQUIRED BY FLORIDA STATUTE 553.80(2)(B) FOR |
| MULTIPLE FAILURES TO PROVIDE A COMPLETE ONE HOUR FIRE |
| RATED WALL ASSEMBLY. |
| |
| ORIGINAL COMMENT: |
| B) NEED 1 HOUR FIRE RESISTANCE WALL WITH EXPOSURE ON |
| BOTH SIDES OF THE WEST SIDE WALL. REVISE PLANS AS |
| REQUIRED. PROVIDE FIRE RATED WALL DETAIL AND |
| SPECIFICATIONS. |
| RESPONSE: |
| REPEAT COMMENT. ENGINEER OF RECORD NEEDS TO PROVIDE A |
| COMPLETE WALL ASSEMBLY DETAIL AND SPECIFICATIONS. |
| INFORMATION SUBMITTED IS INSUFFICIENT. IT DOESN'T |
| SPECIFY A COMPLETE ASSEMBLY ON BOTH SIDES OF THE WALL. |
| NEED TO PROVIDE COMPLETE SPECIFICATIONS (TYPE, |
| THICKNESS OF MATERIALS, ETC) ON EACH SIDE OF THE WALL. |
| NOTE: UL 263 IS AN STANDARD TEST METHOD NOT FIRE RATED |
| ASSEMBLY. |
| |
| 2- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS, |
| CONTRACTOR OVERHEAD AND PROFIT AND ALL L DESIGN |
| PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY |
| AMENDMENTS. |
| RESPONSE: REPEAT COMMENT. NOT ADDRESSED AT ALL. SINCE |
| THERE WAS NO RESPONSE AFTER SEVERAL REQUESTS, THE |
| VALUATION WAS ESTIMATED TO BE $30,000 +/-. THE PERMIT |
| FEE IS $858.56. |
| |
| 3- THE ATTACHMENT OF THE BARN DOORS SHOWN NORTH |
| ELEVATION IS NOT CLEAR AND NEEDS MORE INFORMATION: A) |
| THERE ARE NO SPECIFICATIONS FOR THE NUMBER AND LOCATION |
| OF FASTENERS. B) THE SCREW SIZE #8 X 1-5/8" SPECIFIED |
| MAY NOT BE ADEQUATE. THE LENGTH OF THIS SCREW MAY JUST |
| BE ENOUGH TO FASTEN TO THE STUCCO INSTEAD OF THE |
| FRAMING MEMBERS. C) CLEARLY SPECIFY HOW ARE THESE DOORS |
| ATTACHED TO THE STRUCTURE FRAMING MEMBERS. D) SPECIFY |
| HOW ARE THE BARN DOORS SCREWED TOGETHER. SEC. R301.1 |
| FBC-RESIDENTIAL. |
| |
| 4- SITE PLAN ON SHEET S1 SPECIFIES 3'-0" SETBACK ON THE |
| WEST SIDE. THIS IS INCORRECT. SEE SURVEY AND REVISE AS |
| REQUIRED. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 5- WINDOW SHOWN ON THE EAST ELEVATION IS LOCATED IN THE |
| END ZONE, NOT INTERIOR ZONE. IT SHOULD BE NOTED AS "B" |
| NOT "A". REVISE AS REQUIRED. SEC. R301.1 |
| FBC-RESIDENTIAL. |
| |
| ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| |