2016-12-08 15:00:57 | RESIDENTIAL (R3) ALTERATIONS THIRD BUILDING REVIEW |
| CHECKLIST. |
| CODE: FBC-5TH EDITION (2014). |
| |
| |
| NOTE: |
| ENGINEER OF RECORD MAY BE CHARGED FOUR TIMES THE PLAN |
| REVIEW FEE IF PLANS ARE DENIED THREE OR MORE TIMES AS |
| REQUIRED BY FLORIDA STATUTE 553.80(2)(B). |
| |
| |
| 1- SURVEY SUBMITTED SHOWS 2.7' SETBACK FROM THE |
| PROPERTY LINE ON THE WEST SIDE. ACCORDING TO TABLE |
| R302.1(1) FBC-RESIDENTIAL, 5TH EDITION (2014) NEED THE |
| FOLLOWING: |
| A) OPENINGS ARE NOT ALLOWED. |
| RESPONSE: LAUNDRY WINDOW ON THE WEST WALL WAS REMOVED |
| BUT A NEW OPENING WAS CREATED FOR THE NEW A/C. NO |
| OPENINGS ARE ALLOWED. NEED TO KEEP ONE HOUR FIRE RATING |
| ON THE WALL. A/C UNIT WILL BRAKE THE FIRE RATING OF THE |
| ASSEMBLY. REVISE AS REQUIRED. |
| |
| B) NEED 1 HOUR FIRE RESISTANCE WALL WITH EXPOSURE ON |
| BOTH SIDES OF THE WEST SIDE WALL. REVISE PLANS AS |
| REQUIRED. PROVIDE FIRE RATED WALL DETAIL AND |
| SPECIFICATIONS. |
| RESPONSE: REPEAT COMMENT. ENGINEER OF RECORD NEEDS TO |
| PROVIDE WALL ASSEMBLY DETAIL AND SPECIFICATIONS. |
| INFORMATION WAS NOT PROVIDED. NOTE: NEED TO SPECIFY |
| ASSEMBLY TESTED IN ACCORDANCE WITH ASTM E119 OR UL 263 |
| WITH EXPOSURE FROM BOTH SIDES. |
| |
| 2- PROVIDE COMPLETE INFORMATION SHOWING COMPLIANCE WITH |
| THE REQUIRED HEATING FOR HABITABLE SPACES. SEC. R303.9 |
| FBC-RESIDENTIAL. |
| RESPONSE: WALL A/C UNIT WITH HEAT LOCATED ON THE WEST |
| WALL IS NOT ALLOWED. SEE ITEM #1(A) ABOVE. REVISE AS |
| REQUIRED. |
| |
| 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS, |
| CONTRACTOR OVERHEAD AND PROFIT AND ALL DESIGN |
| PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY |
| AMENDMENTS. |
| RESPONSE: REPEAT COMMENT. NOT ADDRESSED AT ALL. PROVIDE |
| COPY OF SIGNED CONTRACT FOR THE CONSTRUCTION AND COPY |
| OF CONTRACT FOR THE DESIGN PROFESSIONAL. |
| |
| 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| FAC 61G20-3.002(33) FOR: |
| A) BARN DOORS AS SHOWN ON PLANS. |
| RESPONSE: REPEAT COMMENT. REVIEW IS NOT ONLY FOR |
| HISTORIC. BUILDING REVIEW IS REQUIRED AS WELL. IF THERE |
| IS NOT PRODUCT APPROVAL, THEN PROVIDE COMPLETE SITE |
| SPECIFIC ENGINEERING ANALYSIS FOR BUILDING OFFICIAL |
| REVIEW AND APPROVAL. |
| |
| 5- ENGINEER OF RECORD TO REVIEW/APPROVE ABOVE PRODUCT |
| APPROVAL AS REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| |
| ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| |