2016-10-26 10:18:282ND ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 JOB ADDRESS: 814 CLAREMORE DR.
 DESCRIPTION: CONVERT EXISTING GARAGE INTO LIVING SPACES
 MASTER PERMIT: 16070342
  
 BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS.
 ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF
 SUBMITTED CORRECTIONS.
  
 NOW THAT THE PROPOSED WORK HAS BEEN APPROVED BY ZONING
 WE CAN PRECEDE WITH THE ELECTRICAL REQUIREMENTS FOR A
 SUCCESSFUL ELECTRICAL PLAN REVIEW.
 1. YOU WERE ASKED TO MARK ON A SITE PLAN THE LOCATION
 OF THE ELECTRICAL SERVICE POLE SERVICE THE PREMISES.
 YOU WERE TO ALSO INDICATE THE LOCATION OF THE
 ELECTRICAL METER/S AND MAIN DISCONNECT/S. FURTHERMORE
 YOU WERE TOLD TO SHOW HOW THE GARAGE IS SERVED
 ELECTRICALLY.
 2. THE ELECTRICAL FLOOR PLAN IS MISSING THE REQUIRED
 LIGHTING ABOUT THE ELECTRICAL PANEL (NEC 110.26(D)).
 THERE IS A MISSING OUTLET BELOW THE ELECTRICAL PANEL
 (NEC 210.52(A)(2)). YOU SHALL MARK THE LOCATION OF THE
 WATER HEATER AND THE A/C.
 3. YOU WERE PREVIOUSLY INFORMED THAT WITH THIS
 CONVERSION YOU WILL HAVE TO PROVIDE HEAT TO THESE
 PREMISES. THIS CAN?T BE WITH PORTABLE UNITS. YOU WILL
 HAVE TO INDICATE IF THE PROPOSED A/C UNIT IS REVERSE
 CYCLE AND PLACE IT STRATEGICALLY TO HEAT THE ENTIRE
 AREA OR PROVIDE ADDITIONAL PERMANENT HEATING. THIS
 ADDITIONAL LOAD SHALL BE INCLUDED IN THE RISER DIAGRAM
 AND LOAD CALCS.
 4. THE ELECTRICAL RISER DIAGRAM AS PRESENTED DOES NOT
 ANSWER THE QUESTION. YOU SHALL PROVIDE A RISER DIAGRAM
 THAT INCLUDES THE MAIN PANEL W/ITS RESPECTIVE LOAD AS
 WELL AS THE SUB PANEL AND ITS LOAD. YOU SHALL INDICATE
 IF THE PANELS ARE MAIN BREAKER TYPE OR MAIN LUG ONLY
 AND THERE IS A SEPARATE MAIN DISCONNECT.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,