Date |
Text |
2016-10-26 10:18:28 | 2ND ELECTRICAL REVIEW NOTES |
| REVIEWED FOR COMPLIANCE WITH: |
| 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| |
| JOB ADDRESS: 814 CLAREMORE DR. |
| DESCRIPTION: CONVERT EXISTING GARAGE INTO LIVING SPACES |
| MASTER PERMIT: 16070342 |
| |
| BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS. |
| ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF |
| SUBMITTED CORRECTIONS. |
| |
| NOW THAT THE PROPOSED WORK HAS BEEN APPROVED BY ZONING |
| WE CAN PRECEDE WITH THE ELECTRICAL REQUIREMENTS FOR A |
| SUCCESSFUL ELECTRICAL PLAN REVIEW. |
| 1. YOU WERE ASKED TO MARK ON A SITE PLAN THE LOCATION |
| OF THE ELECTRICAL SERVICE POLE SERVICE THE PREMISES. |
| YOU WERE TO ALSO INDICATE THE LOCATION OF THE |
| ELECTRICAL METER/S AND MAIN DISCONNECT/S. FURTHERMORE |
| YOU WERE TOLD TO SHOW HOW THE GARAGE IS SERVED |
| ELECTRICALLY. |
| 2. THE ELECTRICAL FLOOR PLAN IS MISSING THE REQUIRED |
| LIGHTING ABOUT THE ELECTRICAL PANEL (NEC 110.26(D)). |
| THERE IS A MISSING OUTLET BELOW THE ELECTRICAL PANEL |
| (NEC 210.52(A)(2)). YOU SHALL MARK THE LOCATION OF THE |
| WATER HEATER AND THE A/C. |
| 3. YOU WERE PREVIOUSLY INFORMED THAT WITH THIS |
| CONVERSION YOU WILL HAVE TO PROVIDE HEAT TO THESE |
| PREMISES. THIS CAN?T BE WITH PORTABLE UNITS. YOU WILL |
| HAVE TO INDICATE IF THE PROPOSED A/C UNIT IS REVERSE |
| CYCLE AND PLACE IT STRATEGICALLY TO HEAT THE ENTIRE |
| AREA OR PROVIDE ADDITIONAL PERMANENT HEATING. THIS |
| ADDITIONAL LOAD SHALL BE INCLUDED IN THE RISER DIAGRAM |
| AND LOAD CALCS. |
| 4. THE ELECTRICAL RISER DIAGRAM AS PRESENTED DOES NOT |
| ANSWER THE QUESTION. YOU SHALL PROVIDE A RISER DIAGRAM |
| THAT INCLUDES THE MAIN PANEL W/ITS RESPECTIVE LOAD AS |
| WELL AS THE SUB PANEL AND ITS LOAD. YOU SHALL INDICATE |
| IF THE PANELS ARE MAIN BREAKER TYPE OR MAIN LUG ONLY |
| AND THERE IS A SEPARATE MAIN DISCONNECT. |
| |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| GREATLY APPRECIATED. |
| |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME DIRECTLY. |
| |
| THANK YOU, |
| MIKE ALBARRAN |
| ELECTRICAL PLANS EXAMINER |
| PH: 561-805-6746 |
| EMAIL: [email protected] |
| |