Plan Review Notes
Plan Review Notes For Permit 16070342
Permit Number 16070342
Review Stop B
Sequence Number 2
Notes
Date Text
2016-10-05 10:41:17 
 RESIDENTIAL (R3) ALTERATION SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 5TH EDITION (2014)
  
 ORIGINAL COMMENT:
 1- PROVIDE SURVEY SHOWING SETBACKS FROM PROPERTY LINE
 TO VERIFY COMPLIANCE WITH THE FIRE RESISTANCE
 CONSTRUCTION OF SEC. R302.1 FBC-RESIDENTIAL.
  
 RESPONSE:
 SURVEY SUBMITTED SHOWS 2.7' SETBACK FROM THE PROPERTY
 LINE ON THE WEST SIDE. ACCORDING TO TABLE R302.1(1)
 FBC-RESIDENTIAL, 5TH EDITION (2014) NEED THE FOLLOWING:
 A) OPENINGS ARE NOT ALLOWED. REVISE PLANS AS REQUIRED.
  
 B) NEED 1 HOUR FIRE RESISTANCE WALL WITH EXPOSURE ON
 BOTH SIDES OF THE WEST SIDE WALL. REVISE PLANS AS
 REQUIRED. PROVIDE FIRE RATED WALL SPECIFICATIONS.
  
 2- PROVIDE COMPLETE INFORMATION SHOWING COMPLIANCE WITH
 THE REQUIRED HEATING FOR HABITABLE SPACES. SEC. R303.9
 FBC-RESIDENTIAL.
  
 RESPONSE:
 COMMENT NOT ADDRESSED AT ALL.
  
 NEW COMMENT BASED ON NEW INFORMATION PROVIDED:
 3- TYPICAL WALL SECTION A/S2 SHOWS ONLY ONE 2X4 TOP
 PLATE. EXTERIOR DOOR AND WINDOWS FRAMING DETAILS ON
 SAME SHEET SHOW DOUBLE TOP PLATES. REVISE AS REQUIRED
 TO MATCH. TYPICALLY 2 TOP PLATES ARE REQUIRED. ENGINEER
 OF RECORD TO PROVIDE STRUCTURAL ANALYSIS IF ONLY USING
 ONE TOP PLATE FOR BEARING WALLS. SEC. R301.1
 FBC-RESIDENTIAL.
  
 ORIGINAL COMMENT:
 4- WINDOW SCHEDULE SPECIFIES IMPACT WINDOWS. PRODUCT
 APPROVALS SUBMITTED ARE FOR NON-IMPACT WINDOWS. REVISE
 AS REQUIRED TO MATCH. SEC. 107.2.1 CITY AMENDMENTS.
  
 RESPONSE:
 NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 5- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR OVERHEAD AND PROFIT AND ALL DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. REVISE VALUATION AS REQUIRED.
  
 RESPONSE:
 NOT ADDRESSED. PROVIDE COPY OF FULLY SIGNED CONTRACT
 FOR THE CONSTRUCTION AND FOR COPY OF CONTRACT FOR THE
 DESIGN PROFESSIONAL.
  
 6- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 ORIGINAL COMMENT:
 A) SINGLE HUNG WINDOWS. DRAWINGS SUBMITTED WITH NOA
 15-0511.05 ARE INCOMPLETE. PROVIDE COMPLETE DRAWINGS.
 AND, CLEARLY MARK WHICH MODEL IS GOING TO BE INSTALLED
 TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES.
  
 RESPONSE:
 NOT ADDRESSED. PROVIDE UNCUT DRAWINGS AND MARK WHICH
 MODEL IS GOING TO BE USED.
  
 ORIGINAL COMMENT:
 B) FRENCH DOORS. DRAWINGS SUBMITTED WITH NOA 14-0908.06
 ARE INCOMPLETE. PROVIDE COMPLETE DRAWINGS.
  
 RESPONSE:
 DRAWINGS SUBMITTED WITH NEW NOA 13-0328.11 ARE
 INCOMPLETE ALSO. PROVIDE COMPLETE UNCUT DRAWINGS.
  
 ORIGINAL COMMENT:
 C) BARN DOORS AS SHOWN ON PLANS.
  
 RESPONSE:
 NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 D) HURRICANE SHUTTERS. AND PROVIDE COMPLETE
 INSTALLATION SCHEDULE. SEE CITY SAMPLE OR PROVIDE
 COMPLETE INFORMATION IN ANY OTHER FORMAT.
  
 RESPONSE:
 NOT ADDRESSED.
  
 NEW COMMENT:
 7- CLARIFY WHY SUBMITTING NOA FOR SLIDING GLASS DOORS.
 PLANS DON'T SHOW ANY. SEC. 107.2.1 CITY AMENDMENTS.
  
 8- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRE3D BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT