2016-08-24 18:31:08 | ELECTRICAL REVIEW NOTES |
| REVIEWED FOR COMPLIANCE WITH: |
| 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| |
| PROJECT NAME: GARAGE REMODEL |
| JOB ADDRESS: 314 ARDMORE DR. |
| DESCRIPTION: INTERIOR RENOVATIONS OF REAR BLDG. |
| MASTER PERMIT: 16070342 |
| |
| BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS. |
| ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF |
| SUBMITTED CORRECTIONS. |
| |
| PER THE NEC AND THE FBC-R YOU SHALL PROVIDE THE |
| FOLLOWING FOR A SUCCESSFUL ELECTRICAL PLAN REVIEW: |
| |
| 1. A SITE PLAN SHOWING THE LOCATION OF THE FPL UTILITY |
| POLE SERVING THE PROPERTY; THE ELECTRICAL SERVICE DROP |
| TO THE METER. YOU SHALL ALSO INDICATE HOW THE ELECTRIC |
| SERVICE GETS TO THE REAR STRUCTURE. |
| 2. YOU SHALL SUBMIT AN ELECTRICAL PAGE SHOWING THE |
| REQUIRED ELECTRICAL RECEPTACLES AND LIGHTING OUTLETS. |
| SHOW ALL EXISTING OUTLETS AS WELL AS THE PROPOSED AND |
| ARK THEM ACCORDINGLY. |
| 3. YOU SHALL INCLUDE ON THE DRAWINGS AT A MINIMUM A |
| BLOCK NOTE ADDRESSING THE GFI, ARC-FAULT, |
| TAMPER-RESISTANT OUTLETS AND SMOKE DETECTORS. |
| 4. NO THAT THE GARAGE IS BEING CONVERTED INTO HABITABLE |
| SPACE, THE FBC-R REQUIRES THAT HEAT BE PROVIDED. |
| 5. YOU SHALL INCLUDE AN ELECTRICAL SERVICE RISER |
| DIAGRAM TO SHOW THAT THE EXISTING SERVICE IS CAPABLE OF |
| ABSORBING THE ADDED LOADS. |
| 6. ADDITIONAL COMMENTS MAY ARISE DUE TO DEFICIENT |
| SUBMITTAL DOCUMENTS. |
| |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| GREATLY APPRECIATED. |
| |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME DIRECTLY. |
| THANK YOU, |
| MIKE ALBARRAN |
| ELECTRICAL PLANS EXAMINER |
| PH: 561-805-6746 |
| EMAIL: [email protected] |
| |
2016-07-13 17:52:38 | 7/13/16 THE PROPOSED SCOPE OF WORK HAS TO GO BEFORE |
| ZONING BEFORE ANY TRADE REVIEW. |