Plan Review Notes
Plan Review Notes For Permit 16070342
Permit Number 16070342
Review Stop B
Sequence Number 1
Notes
Date Text
2016-08-19 19:29:18RESIDENTIAL (R3) ALTERATION BUILDING REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014)
  
 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
  
 2- THIS IS NOT ALTERATION LEVEL 2. THIS IS A CHANGE OF
 OCCUPANCY (CHANGE OF USE FROM GARAGE TO LIVABLE AREA).
 REVISE AS REQUIRED. SEC. 506 FBC-EXISTING BUILDING, 5TH
 EDITION (2014).
  
 3- PROVIDE COMPLETE DOORS AND WINDOWS FRAMING DETAILS
 AND SPECIFICATIONS. SPECIFY ALL FRAMING MEMBERS AND
 CONNECTORS. SEC. R301.1 FBC-RESIDENTIAL, 5TH EDITION
 (2014).
  
 4- PROVIDE SURVEY SHOWING SETBACKS FROM PROPERTY LINE
 TO VERIFY COMPLIANCE WITH THE FIRE RESISTANCE
 CONSTRUCTION OF SEC. R302.1 FBC-RESIDENTIAL.
  
 5- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 REPLACEMENT OF 2X4 STUDS AS SPECIFIED ON THE DEMOLITION
 PLAN. SPECIFY ALL CONNECTORS. SEC. R302.1
 FBC-RESIDENTIAL.
  
 6-PROVIDE COMPLETE INFORMATION SHOWING COMPLIANCE WITH
 THE REQUIRED HEATING FOR HABITABLE SPACES. SEC. R303.9
 FBC-RESIDENTIAL.
  
 7- MISSING SECTION 5/S2 SPECIFIED ON THE FLOOR PLAN.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 8- LOCATION OF BATHROOM WINDOW SHOWN ON THE EAST
 ELEVATION DOESN'T MATCH FLOOR PLAN. REVISE AS REQUIRED
 TO MATCH. SEC. 107.2.1 CITY AMENDMENTS.
  
 9- SPECIFY SAFETY GLASS FOR BATHROOM WINDOW AS REQUIRED
 BY SEC. R308.4.2 FBC-RESIDENTIAL.
  
 10- CLARIFY WHY THERE IS NOT FRAMING FOR THE BATHROOM
 CORNER BY THE LAVATORY. SEC. R301.1 FBC-RESIDENTIAL.
  
 11- CHANGING THE USE FROM GARAGE TO HABITABLE SPACE.
 THE RISK CATEGORY CHANGED FROM RISK CATEGORY I TO RISK
 CATEGORY II WHERE THERE IS A HIGHER HAZARD FOR HUMAN
 LIFE. PROVIDE COMPLETE DETAILS AND SPECIFICATIONS
 SHOWING HOW THE STRUCTURE IS REINFORCED TO RESIST ALL
 THE WIND LOADS AS REQUIRED BY SEC. R301.1
 FBC-RESIDENTIAL. SPECIFY ALL CONNECTORS FROM ROOF TO
 WALL AND WALL TO FOUNDATION.
  
 12- WEST AND SOUTH ELEVATION SPECIFY STUCCO OVER CMU
 BLOCK WALLS. PLANS DON'T SHOW CMU WALLS. REVISE AS
 REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 13- WINDOW SCHEDULE SPECIFIES IMPACT WINDOWS. PRODUCT
 APPROVALS SUBMITTED ARE FOR NON-IMPACT WINDOWS. REVISE
 AS REQUIRED TO MATCH. SEC. 107.2.1 CITY AMENDMENTS.
  
 14- INTERIOR PARTITION DETAIL: CLARIFY FASTENING OF 2 X
 4 WOOD STUDS TO THE TRUSS. AND, SPECIFY FASTENING OF 2
 X 4 TO THE BOTTOM PLATE. SEC. R301.1 FBC-RESIDENTIAL.
  
 15- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR OVERHEAD AND PROFIT AND ALL DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. REVISE VALUATION AS REQUIRED.
  
 16- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) SINGLE HUNG WINDOWS. DRAWINGS SUBMITTED WITH NOA
 15-0511.05 ARE INCOMPLETE. PROVIDE COMPLETE DRAWINGS.
 AND, CLEARLY MARK WHICH MODEL IS GOING TO BE INSTALLED
 TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES.
  
 B) FRENCH DOORS. DRAWINGS SUBMITTED WITH NOA 14-0908.06
 ARE INCOMPLETE. PROVIDE COMPLETE DRAWINGS.
  
 C) BARN DOORS AS SHOWN ON PLANS.
  
 D) ALL SIMPSON OR USP STRUCTURAL CONNECTORS SPECIFIED
 ON DETAILS. PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL
 COVER PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR OR
 LIST THE FLORIDA PRODUCT APPROVAL NEXT TO EACH
 SPECIFIED CONNECTOR.
  
 E) HURRICANE SHUTTERS. AND PROVIDE COMPLETE
 INSTALLATION SCHEDULE. SEE CITY SAMPLE OR PROVIDE
 COMPLETE INFORMATION IN ANY OTHER FORMAT.
  
 17- CLARIFY IF SUBMITTING ENERGY CALCULATIONS OR NOT.
 INFORMATION SUBMITTED IS INCOMPLETE. FORM R405-2014
 INFORMATION SUBMITTED IS MISSING THE REST OF THE
 PACKAGE. THIS IS A CONTRIBUTING HISTORIC BUILDING. IT'S
 EXEMPT FROM THE ENERGY CODE. BUT IF SUBMITTING ENERGY
 CALCULATIONS, THEN PROVIDE COMPLETE INFORMATION. SEC.
 R101.4.2 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]
  