2016-08-01 12:55:08 | 1) A DRINKING FOUNTAIN IS REQD. PER TABLE 403.1 OF 2014 | | FPC & 2014 FBC-ACCESS. SECS.202.4.2, 211.2. | | 2) A SERVICE SINK IS REQD. PER 2014 FPC TABLE 403.1. | | 3) THE BREAKROOM SINK SHALL COMPLY WITH THE FL. | | ACCESSIBILITY CODE SECS. 212.1, 606. | | 4) SHOW THE WIDTH OF TOILET ROOM #17. THE WIDTH SHALL | | BE A MINIMUM OF 85 INCHES WIDE IF BUILT PERFECT. 86 | | INCHES ALLOWS FOR TOLERANCE. | | 5) TOILET ROOM #14 SHALL BE HANDICAPPED ACCESSIBLE.FAC | | SEC. 213.2. | | 6) SHT. A-5.01 - SHOW ALL MOUNTING HEIGHTS FOR GRAB | | BARS, MIRROR, SOAP & TOILET PAPER DISPENSER, ETC.ALL | | MOUNTING HEIGHTS SHALL COMPLY WITH 2014 FAC. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | |
|