2016-07-13 17:18:07 | 1ST ELECTRICAL REVIEW NOTES |
| REVIEWED FOR COMPLIANCE WITH: |
| 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| |
| ELECTRICAL REVIEW APPROVED WITH THE FOLLOWING |
| EXCEPTIONS:. |
| 1. NEC 110.16 ARC-FLASH HAZARD WARNING LABELS REQUIRED. |
| NEC 110.24 THE MAXIMUM AVAILABLE FAULT CURRENT SHALL BE |
| DURABLY MARKED AND DATED ON ALL ELECTRICAL APPARATUS. |
| 2. PER FBC-B 714.3.2 EXCEPTIONS: 1.1 UNLESS YOU HAVE |
| SOLID NONCOMMUNICATING PARTITIONS, ALL ELECTRICAL BOXES |
| IN 2 HR. RATED WALLS SHALL BE PROTECTED WITH LISTED |
| FIRE STOPPING MATERIAL. |
| 3. PER FBC-EC405.7, A MINIMUM OF 50% OF ALL 125V, 15 & |
| 20 AMP RECEPTACLES SHALL BE AUTOMATICALLY CONTROLLED |
| WHERE INSTALLED IN PRIVATE OR OPEN OFFICES AND COMPUTER |
| CLASSROOMS. THIS INCLUDES MODULAR PARTITIONS. |
| |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| GREATLY APPRECIATED. |
| |