Plan Review Notes
Plan Review Notes For Permit 16070290
Permit Number 16070290
Review Stop M
Sequence Number 1
Notes
Date Text
2016-08-11 18:43:11PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PLANS SHOW AN EXISTING HVAC SYSTEM IN THE MAIN
 HOUSE. THE INTERIOR OF THE HOUSE IS BEING CHANGED SUCH
 THAT THE LOCATION OF THE DUCT SYSTEM WOULD BE AFFECTED.
 FBC - 107.3.5.3 PROVIDE TWO SETS OF A MECHANICAL PLAN
 TO SHOW EQUIPMENT AND LOCATION AND DUCT SYSTEMS PER
 FBC-R M16 & BATH EXHAUST PER FBC-R M15.
  
 2) THE NEW GUEST HOUSE THAT WAS A DETACHED GARAGE IS
 REQUIRED TO HAVE SOME HVAC WORK (HEAT AND BATHROOM
 EXHAUST). FBC - 107.3.5.3 PROVIDE TWO SETS OF A
 MECHANICAL PLAN TO SHOW EQUIPMENT AND LOCATION AND DUCT
 SYSTEMS PER FBC-R M16 & BATH EXHAUST PER FBC-R M15.
  
 3) FBC ENERGY CONSERVATION SECTIONS R101.5.1.1.1 OR
 R101.5.1.1.2. SUBMIT TWO SETS OF ENERGY COMPLIANCE
 FORMS AS REQUIRED.
  
 4) FBC-R - M1401.3 SIZING. HEATING AND COOLING
 EQUIPMENT SHALL BE SIZED BASED ON BUILDING LOADS
 CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR OTHER
 APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES.
 PROVIDE EQUIPMENT SIZING CALCULATIONS FOR THE GUEST
 HOUSE.
  
  
  
  