Plan Review Notes For Permit 16070290 |
Permit Number |
16070290 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-08-11 18:43:11 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY MECHANICAL | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE PLANS SHOW AN EXISTING HVAC SYSTEM IN THE MAIN | | HOUSE. THE INTERIOR OF THE HOUSE IS BEING CHANGED SUCH | | THAT THE LOCATION OF THE DUCT SYSTEM WOULD BE AFFECTED. | | FBC - 107.3.5.3 PROVIDE TWO SETS OF A MECHANICAL PLAN | | TO SHOW EQUIPMENT AND LOCATION AND DUCT SYSTEMS PER | | FBC-R M16 & BATH EXHAUST PER FBC-R M15. | | | | 2) THE NEW GUEST HOUSE THAT WAS A DETACHED GARAGE IS | | REQUIRED TO HAVE SOME HVAC WORK (HEAT AND BATHROOM | | EXHAUST). FBC - 107.3.5.3 PROVIDE TWO SETS OF A | | MECHANICAL PLAN TO SHOW EQUIPMENT AND LOCATION AND DUCT | | SYSTEMS PER FBC-R M16 & BATH EXHAUST PER FBC-R M15. | | | | 3) FBC ENERGY CONSERVATION SECTIONS R101.5.1.1.1 OR | | R101.5.1.1.2. SUBMIT TWO SETS OF ENERGY COMPLIANCE | | FORMS AS REQUIRED. | | | | 4) FBC-R - M1401.3 SIZING. HEATING AND COOLING | | EQUIPMENT SHALL BE SIZED BASED ON BUILDING LOADS | | CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR OTHER | | APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES. | | PROVIDE EQUIPMENT SIZING CALCULATIONS FOR THE GUEST | | HOUSE. | | | | | | | | |
|