2016-07-19 11:41:18 | ELECTRICAL REVIEW NOTES |
| REVIEWED FOR COMPLIANCE WITH: 5TH EDITION FBC 2014 & |
| NFPA 70 2011 (NEC) |
| |
| JOB NAME: INTERIOR RENOVATION W/WINDOW & DOOR |
| REPLACEMENT |
| JOB ADDRESS: 729 PENN ST. |
| DESCRIPTION: MOVE INTERIOR WALLS; ADD ? BATH; NEW |
| KITCHEN CABINETS, INSULATION, FLOOR & WALL COVERING. |
| MAST. PERMIT: 16070290 |
| REVISION: N/A |
| |
| 1. YOUR NOTES REFER TO A NON-EXISTENT EDITION OF THE |
| NEC; THE APPLICABLE NEC EDITION IS THE 2011. |
| 2. FBC-ER3609.3/NEC 250.94 BONDING FOR OTHER SYSTEMS. |
| THE INTER-SYSTEM BONDING TERMINAL PRESCRIBED SHALL BE |
| INSTALLED. |
| 3. FBC-RE3901.7/NEC 210.52(E)(1) REQUIRES THAT THERE BE |
| A GFCI PROTECTED OUTLET IN THE FRONT AND REAR OF EVERY |
| DWELLING UNIT WITH GRADE LEVEL ACCESS. |
| 4. FBC-RE3901.7/NEC 210.52(E)(3) BALCONIES. BALCONIES, |
| DECKS, AND PORCHES THAT ARE ACCESSIBLE FROM INSIDE THE |
| DWELLING UNIT SHALL HAVE AT LEAST ONE RECEPTACLE OUTLET |
| INSTALLED WITHIN THE PERIMETER OF THE BALCONY, DECK, OR |
| PORCH. THE RECEPTACLE SHALL NOT BE LOCATED MORE THAN |
| 2.0 M (61?2 FT.) ABOVE THE BALCONY, DECK, OR PORCH |
| SURFACE. |
| 5. FBC-R4001.15/NEC 404.2(C). WHERE SWITCHES |
| CONTROLLING LIGHTING LOADS SUPPLIED BY A GROUNDED |
| BRANCH CIRCUIT, THE GROUNDED BRANCH CIRCUIT CONDUCTOR |
| FOR THE CONTROLLED LIGHTING CIRCUIT SHALL BE PROVIDED |
| AT THE SWITCH. THIS APPLIES TO ALL OF THE NEW |
| ELECTRICAL WORK AND AS INSTRUCTED BY FBC-EX. FOR |
| ALTERATIONS LEVEL 2. |
| 6. FBC-RE3905.8/NEC 314.27(D) PADDLE FANS. BOXES USED |
| FOR THE SOLE SUPPORT OF CEILING FANS SHALL BE MARKED BY |
| THE MANUFACTURER AS SUITABLE FOR THE PURPOSE, AND |
| INDICATE THE WEIGHT LIMITATIONS BUT SHALL NOT BE USED |
| TO SUPPORT PADDLE FANS HEAVIER THAN 70 LBS. |
| 7. FBC-RE3903.4/NEC 210.70(A)(3) STORAGE OR EQUIPMENT |
| SPACES. AT LEAST ONE LIGHTING OUTLET CONTAINING A |
| SWITCH OR CONTROLLED BY A WALL SWITCH SHALL BE |
| INSTALLED WHERE THESE SPACES ARE USED FOR STORAGE OR |
| CONTAIN EQUIPMENT REQUIRING SERVICING. THE LIGHTING |
| OUTLET SHALL BE PROVIDED AT OR NEAR THE EQUIPMENT |
| REQUIRING SERVICING. UNLESS THE EQUIPMENT INSIDE THE |
| ATTIC IS WITHIN 6 FT. FROM THE ENTRANCE, A PULL CHAIN |
| FIXTURE WILL NOT COMPLY. |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| GREATLY APPRECIATED. |
| |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME DIRECTLY. |
| |
| THANK YOU, |
| MIKE ALBARRAN |
| ELECTRICAL PLANS EXAMINER |