2016-07-19 11:41:18ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH: 5TH EDITION FBC 2014 &
 NFPA 70 2011 (NEC)
  
 JOB NAME: INTERIOR RENOVATION W/WINDOW & DOOR
 REPLACEMENT
 JOB ADDRESS: 729 PENN ST.
 DESCRIPTION: MOVE INTERIOR WALLS; ADD ? BATH; NEW
 KITCHEN CABINETS, INSULATION, FLOOR & WALL COVERING.
 MAST. PERMIT: 16070290
 REVISION: N/A
  
 1. YOUR NOTES REFER TO A NON-EXISTENT EDITION OF THE
 NEC; THE APPLICABLE NEC EDITION IS THE 2011.
 2. FBC-ER3609.3/NEC 250.94 BONDING FOR OTHER SYSTEMS.
 THE INTER-SYSTEM BONDING TERMINAL PRESCRIBED SHALL BE
 INSTALLED.
 3. FBC-RE3901.7/NEC 210.52(E)(1) REQUIRES THAT THERE BE
 A GFCI PROTECTED OUTLET IN THE FRONT AND REAR OF EVERY
 DWELLING UNIT WITH GRADE LEVEL ACCESS.
 4. FBC-RE3901.7/NEC 210.52(E)(3) BALCONIES. BALCONIES,
 DECKS, AND PORCHES THAT ARE ACCESSIBLE FROM INSIDE THE
 DWELLING UNIT SHALL HAVE AT LEAST ONE RECEPTACLE OUTLET
 INSTALLED WITHIN THE PERIMETER OF THE BALCONY, DECK, OR
 PORCH. THE RECEPTACLE SHALL NOT BE LOCATED MORE THAN
 2.0 M (61?2 FT.) ABOVE THE BALCONY, DECK, OR PORCH
 SURFACE.
 5. FBC-R4001.15/NEC 404.2(C). WHERE SWITCHES
 CONTROLLING LIGHTING LOADS SUPPLIED BY A GROUNDED
 BRANCH CIRCUIT, THE GROUNDED BRANCH CIRCUIT CONDUCTOR
 FOR THE CONTROLLED LIGHTING CIRCUIT SHALL BE PROVIDED
 AT THE SWITCH. THIS APPLIES TO ALL OF THE NEW
 ELECTRICAL WORK AND AS INSTRUCTED BY FBC-EX. FOR
 ALTERATIONS LEVEL 2.
 6. FBC-RE3905.8/NEC 314.27(D) PADDLE FANS. BOXES USED
 FOR THE SOLE SUPPORT OF CEILING FANS SHALL BE MARKED BY
 THE MANUFACTURER AS SUITABLE FOR THE PURPOSE, AND
 INDICATE THE WEIGHT LIMITATIONS BUT SHALL NOT BE USED
 TO SUPPORT PADDLE FANS HEAVIER THAN 70 LBS.
 7. FBC-RE3903.4/NEC 210.70(A)(3) STORAGE OR EQUIPMENT
 SPACES. AT LEAST ONE LIGHTING OUTLET CONTAINING A
 SWITCH OR CONTROLLED BY A WALL SWITCH SHALL BE
 INSTALLED WHERE THESE SPACES ARE USED FOR STORAGE OR
 CONTAIN EQUIPMENT REQUIRING SERVICING. THE LIGHTING
 OUTLET SHALL BE PROVIDED AT OR NEAR THE EQUIPMENT
 REQUIRING SERVICING. UNLESS THE EQUIPMENT INSIDE THE
 ATTIC IS WITHIN 6 FT. FROM THE ENTRANCE, A PULL CHAIN
 FIXTURE WILL NOT COMPLY.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  