2016-08-13 11:05:33 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 16070269 |
| ADD: 2427 PRESIDENTIAL WAY SUITE # 301 |
| CONT: FINE LINE CONSTRUCTION |
| TEL: 561-427-5664 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 3RD REVIEW |
| DATE: SAT. AUGUST 13/2016 |
| ACTION: DENIED |
| |
| 1) 3RD REQUEST. SEMI-COMPLIED.THE DEMOLITION PLAN |
| INDICATES THE REMOVAL OF ALL FLOOR FINISHES THROUGH OUT |
| THE UNIT. SHEET A.02 THIS REVIEW MAKES REFERENCE TO |
| WHICH ROOMS WILL RECEIVE WOOD FLOOR FINISHES AND WHICH |
| WILL RECEIVE MARBLE FINISHES. |
| _______________________________________________________ |
| _______________________________________________________ |
| ___ |
| E-MIAL SENT SAT. AUG. 13/16 11:24 AM |
| |
| GOOD MORNING MR. STEINBORG, |
| I'VE BEEN REVIEWING THE PLANS FOR 2427 PRESIDENTIAL WAY |
| THE PLANS INDICATE THE USE OF WOOD FLOORING THROUGH THE |
| UNIT WITH THE EXCEPTION OF THE RESTROOMS AND LAUNDRY |
| ROOM THE INSTALLATION OF MARBLE IN THESE ROOMS. WE ONLY |
| HAVE TESTING FOR THE PROFLEX RCU-500 FOR MARBLE/ TILE. |
| NO ONE TO DATE HAS BROUGHT IN THE TEST REPORTS TO USE |
| THIS PRODUCT ON WOOD. WE WILL NEED THE ACTUAL TEST |
| DOCUMENTS FOR THE FLOOR INSULATION TESTED WITH A WOOD |
| FINISH FLOOR ABOVE. PLEASE ALSO NOTE THE SUBMITTED |
| DOCUMENTS SUBMITTED ONCE OPENED ARE NOLONGER ATTACHED |
| TO THIS E-MAIL. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION |
| DEVELOPMENT SERVICES DEPARTMENT |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| DEVELOPMENT SERVICES HOME PAGE |
| HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| _______________________________________________________ |
| _______________________________________________________ |
| PLAN REVIEW NOTES |
| |
| THE PLANS REFER BACK TO THE REQUIRED TESTING REPORTS. I |
| SPOKE LAST WEEK WITH A DESIGNER ON THIS PROJECT. DO NOT |
| SEND IN SPEC SHEETS, WE NEED THE ACTUAL TEST. SUBMITTED |
| IS PROFLEX MSC 90, THIS DOES NOT MEET THE REQUIREMENT |
| WHEN YOU ACTUALLY SEE THE DOCUMENTED TEST. NEITHER DID |
| THE DESIGNER NOR CONTRACTOR SUBMIT THE FLAME SPREAD |
| TEST REPORT REQUESTED BELOW. |
| CURRENTLY THE ONLY PRODUCT THAT HAS MET ALL OF THE |
| REQUIREMENTS FOR TILE ON A 6 INCH SLAB IS THE PRODUCT |
| PROFLEX RCU-500 WHICH IS 1/2 INCH THICK. STC 53 & IIC |
| 50, |
| FOR THE USE OF TILE/ MARBLE, 6 INCH CONCRETE SLAB/ NO |
| DROPPED CEILING. |
| |
| |
| PLEASE PROVIDE COMPLIANCE WITH THE 2014 FBC-B. |
| BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B |
| 2014) |
| FOR TILE, STONE, MARBLE AND WOOD FLOORING ALL NEED TO |
| HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES |
| TO THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS |
| LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH |
| CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: |
| PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH: |
| |
| 1A)2ND REQUEST. FBC-B 2014 1207.3 STRUCTURE-BORNE |
| SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS |
| OR BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| |
| 1B) 2ND REQUEST. FBC-B 2014 1207.2 AIR-BORNE SOUND. |
| WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| E 90. |
| |
| 1C) 2ND REQUEST. FLAME SPREAD- FBC-B 2014 603.1. |
| EXCEPTION 2. INSULATION INSTALLED BETWEEN A FINISHED |
| FLOOR AND SOLID DECKING WITHOUT INTERVENING AIRSPACE |
| SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT |
| MORE THAN 200. |
| |
| FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION |
| DEVELOPMENT SERVICES DEPARTMENT |
| TEL: 561-805-6715 |