2016-08-04 12:21:59 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 16070269 |
| ADD: 2427 PRESIDENTIAL WAY SUITE # 301 |
| CONT: FINE LINE CONSTRUCTION |
| TEL: 561-427-5664 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: MON. JULY 18/2016 |
| ACTION: DENIED |
| |
| NOTICE TO CONTRACTOR, REMOVE OLD SHEETS AND INSERT NEW |
| SHEETS< SEE COMMENT # 3!!!!!!! |
| |
| |
| |
| 1) 2ND REQUEST. THE DEMOLITION PLAN INDICATES THE |
| REMOVAL OF ALL FLOOR FINISHES THROUGH OUT THE UNIT. |
| SHEET A.02 MAKES REFERENCE TWICE TO THE REQUIRED FLOOR |
| SOUND INSULATION REQUIREMENTS. THE SHEET A.02 INTERIOR |
| NOTE # 6 INDICATES THE FLOOR FINISHES ARE TO BE |
| SPECIFIED BY THE OWNER. THE PLANS DO NOT STATE WHICH |
| ROOMS WILL RECIEVE WHAT FLOOR FINISHES!!!!!! WE NEED TO |
| KNOW THAT TO BE ABLE TO MATCH UP THE TYPEOF MATERIAL TO |
| BE INSTALLED TO THE SUBMITTED REPORT. |
| |
| THE PLANS REFER BACK TO THE REQUIRED TESTING REPORTS. I |
| SPOKE LAST WEEK WITH A DESIGNER ON THIS PROJECT. DO NOT |
| SEND IN SPEC SHEETS, WE NEED THE ACTUAL TEST. SUBMITTED |
| IS PROFLEX MSC 90, THIS DOES NOT MEET THE REQUIREMENT |
| WHEN YOU ACTUALLY SEE THE DOCUMENTED TEST. NEITHER DID |
| THE DESIGNER NOR CONTRACTOR SUBMIT THE FLAME SPREAD |
| TEST REPORT REQUESTED BELOW. |
| CURRENTLY THE ONLY PRODUCT THAT HAS MET ALL OF THE |
| REQUIREMENTS FOR TILE ON A 6 INCH SLAB IS THE PRODUCT |
| PROFLEX RCU-500 WHICH IS 1/2 INCH THICK. STC 53 & IIC |
| 50, 6 INCH CONCRETE SLAB/ NO DROPPED CEILING. |
| |
| |
| PLEASE PROVIDE COMPLIANCE WITH THE 2014 FBC-B. |
| BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B |
| 2014) |
| FOR TILE, STONE, MARBLE AND WOOD FLOORING ALL NEED TO |
| HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES |
| TO THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS |
| LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH |
| CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: |
| PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH: |
| |
| 1A)2ND REQUEST. FBC-B 2014 1207.3 STRUCTURE-BORNE |
| SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS |
| OR BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| |
| 1B) 2ND REQUEST. FBC-B 2014 1207.2 AIR-BORNE SOUND. |
| WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| E 90. |
| |
| 1C) 2ND REQUEST. FLAME SPREAD- FBC-B 2014 603.1. |
| EXCEPTION 2. INSULATION INSTALLED BETWEEN A FINISHED |
| FLOOR AND SOLID DECKING WITHOUT INTERVENING AIRSPACE |
| SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT |
| MORE THAN 200. |
| |
| FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| |
| 2) COMPLIED. |
| |
| 3) 2ND REQUEST!!!!! WHEN RESUBMITTING PLANS PLEASE |
| INDICATE THE REVISION & REMOVE ANY VOIDED SHEETS & |
| REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH A |
| DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE SHEET |
| OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| ANTICIPATED COOPERATION. |
| |