Plan Review Notes
Plan Review Notes For Permit 16070269
Permit Number 16070269
Review Stop B
Sequence Number 1
Notes
Date Text
2016-07-18 11:52:30BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16070269
 ADD: 2427 PRESIDENTIAL WAY SUITE # 301
 CONT: FINE LINE CONSTRUCTION
 TEL: 561-427-5664
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JULY 18/2016
 ACTION: DENIED
  
 1) THE DEMOLITION PLAN INDICATES THE REMOVAL OF ALL
 FLOOR FINISHES THROUGH OUT THE UNIT. PLEASE PROVIDE
 COMPLIANCE WITH THE 2014 FBC-B.
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B
 2014)
 FOR TILE, STONE, MARBLE AND WOOD FLOORING ALL NEED TO
 HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES
 TO THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS
 LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH
 CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
 1A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 1B) FBC-B 2014 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 1C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 2A) SHEET A.02 SHOWS A LIVING ROOM CEILING HEIGHT OF 8
 FT. 1 IN. AND A BREAKFAST AREA WITH THE SAME FINISH
 CEILING AT 8 FT. 1 INCH. PLEASE NOTE THERE IS A NOTE OF
 A NEW 7 INCH DEEP SOFFIT ( DROPPED CEILING OVER THE
 KITCHEN AREA) BUT THERE IS NO INFORMATION AS TO WHERE
 IT ENDS? THIS ALSO HOLDS TRU WITH THE NEW MASTER BATH
 LAYOUT AND MASTER BATH ENTRY HALLWAY. PLEASE NOTE WITH
 ONLY A 7 INCH DROPPED CEILING WHERE WILL THE A/C DUCTS
 BE RUN SINCE THE FRAMING MEMBERS WILL TAKE
 APPROXIMATELY 3 1/2 INCHES OF THIS SPACE? 107.2.1.3
 ADDITIONAL INFORMATION REQUIRED.
  
 2B) THERE IS ALSO NO FRAMING INFORMATIONFOR THE DROPPED
 SOFFIT/ CEILING, AS TO MATERIAL, SIZE OF, GAUGE,
 SPACING, ANCHORING TO THE CONCRETE DECK ABOVE, TYPE OF
 ANCHOR, FREQUENCY OF ATTACHMENT TO THE CONRETE DECK,IF
 STIFF BACKS ARE REQUIRED NOR THE TYPE OF FINISH
 MATERIAL TO BE USED FOR THE SOFFIT/ KITCHEN CEILING NOR
 THE ALLOWABLE CEILING SPANS AND DEFLECTION LIMITATIONS.
 2014 FBC-B TABLE 2507.2 STEEL STUDS NON-LOAD BEARING
 ASTM C645. ASTM C754. TABLE 1604.3 DEFLECTION.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  