2016-07-11 12:30:38 | INITIAL ELECTRICAL PLAN REVIEW |
| |
| APPLICABLE CODES IN EFFECT: |
| FLORIDA BUILDING CODE 2014 5TH EDITION |
| FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| EDITION |
| NFPA 70- 2011 NEC |
| COMMENTS: |
| |
| 1. PLANS PROVIDED ARE INSUFFICIENT. PLANS ARE TO |
| REFLECT PER SCOPE LISTED ON APPLICATION ALL |
| REQUIREMENTS PER FBC 107.3.5- MINIMUM PLAN REVIEW. |
| 2. PLANS ARE TO BE SIGNED AND SEALED BY AOR OR EOR, IF |
| QUALIFIER IS DESIGNING DRAWINGS MUST SIGN AND NOTARIZED |
| ELECTRICAL SHEETS. FBC 107.3.5- MINIMUM PLAN REVIEW |
| 3. PROVIDE A GENERAL NOTE TO INDICATE LOW VOLTAGE TO BE |
| UNDER SEPARATE PERMIT. |
| 4. PROVIDE FIXTURE SPECS AND DETAILS OF INSTALLATIONS. |
| 5. PROVIDE CUT SHEET FOR ALL LIGHTING CONTROLS PANEL |
| AND ACCESSORIES AND SHOW SEQUENCE OF OPERATION AS PER |
| FBC ENERGY CONSERVATION C405.7 |
| 6. LABEL ON DRAWING WHAT IS EXISTING TO REMAIN, NEW, |
| RELOCATED ETC. |
| 7. LABEL CIRCUIT ID FOR ALL NEW POWER AND LIGHTING |
| OUTLETS. |
| 8. PROVIDE A FIXTURE LEGEND. |
| 9. PROVIDE A REVISED PANEL SCHEDULE REFLECTING ALL |
| CIRCUITS AND NEW LOADS BEING ADDED INCLUDING |
| MECHANICAL. |
| 10. SHOW PANEL LOCATIONS FOR ALL SCOPE REFLECTING |
| PROPER CLEARANCE PER NEC 110.26 |
| 11. A COMPLETE REVIEW IN ACCORDANCE WITH FBC CANNOT BE |
| COMPLETE DUE TO PENDING INFORMATION. |
| 12. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL |
| FREE TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS |
| REGARDING THIS PROJECT. |
| |
| |