Plan Review Notes For Permit 16070258 |
Permit Number |
16070258 |
|
Review Stop |
M |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2016-10-24 17:06:54 | 3RD REVIEW FBC-2014 MECHANICAL | | PERMIT #16070258 | | 10/24/16 | | | | 1) M-1: MANUAL DAMPERS FOR O/A ARE NOT IN COMPLIANCE | | WITH SECTION C403.2.4.4 FBC-14 ENEREGY CONSERVATION AS | | PREVIOUSLY NOTED IN THE 2ND REVIEW. PLEASE PROVIDE | | EITHER A GRAVITY OR MOTORIZED DAMPER. | | | | 2) THE REQUESTED AC STAND NOA HAS NOT BEEN SUBMITTED: | | PLEASE COMPLY. | | | | 3) SIGNATURE OF OWNER/AGENT REQUIRED ON PAGE 3 OF THE | | ENERGYGAUGE COMPLIANCE SUBMITTAL. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|