2016-10-24 06:49:04 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 16070258 |
| ADD: 1817 S DIXIE HWY |
| CONT: TBD |
| TEL: 215-380-8580 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 3RD REVIEW |
| DATE: MON. 24/ 2016 |
| ACTION: BUILDING PROVISO |
| |
| 1)BUILDING PROVISO: SHOP DRAWINGS TO BE A DEFERRED |
| SUBMITTAL. STRUCTURAL SHEETS NOR THE MECHANICAL SHEETS |
| SHOW ROOF FRAMING DETAILS FOR THE NEW ROOF TOP |
| PENETRATIONS WILL BE FRAMED FOR THE HOOD INTAKE AND |
| EXHAUST FANS, FRAMING DETAILS FOR THE ROOF TOP UNITS |
| NOR DETAILS FOR ROOF TOP CURBS TO THE MWFRS (MAIN WIND |
| FORCE RESISTING SYSTEM). DETAILS ARE LACKING ALSO HOW |
| THE ROOFTOP FANS WILL BE ANCHORED TO THE CURBS NOR THE |
| RTU UNITS TO THE ROOF TOP CURBS. |
| FOR ALL ROOF TOP EQUIPMENT, CURBS OR A/C STANDS, |
| DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL |
| AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE. |
| 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL |
| MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY |
| METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT |
| EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY |
| AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES. |
| EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE |
| OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES |
| SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND |
| LOADS? |
| |
| 2014 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL |
| EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO |
| WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND |
| PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA |
| BUILDING CODE, BUILDING |
| |