2016-09-20 07:56:57 | 2ND REVIEW FBC-2014 MECHANICAL | | PERMIT #16070258 | | 9/20/16 | | | | 1) THE TRANE AIR HANDLER SUBMITTAL INDICATES THE 5-TON | | UNIT CAN PRODUCE OVER 2000 CFMS OF COOLING AT 0.1 AND | | 0.3 STATIC PRESSURE, AND FOR ALL HEATING AIRFLOWS | | (PLEASE SEE THE NOTE INDICATING AUTO SETTINGS). PROVIDE | | THE DUCT SMOKE DETECTORS AS PREVIOUSLY REQUESTED. | | | | 2) THE 24X12 RETURN AIR GRILLS FOR AHU-1 ARE UNDERSIZED | | FOR 1800 CFMS OF SUPPLY AIR. TYPICAL SIZING IS 2 CFMS | | PER SQ. IN. | | | | 3) PROVIDE EITHER MOTORIZED OR GRAVITY DAMPERS FOR THE | | O/A DUCTS TO AHU'S #2, 3, & 4- SECTION C403.2.4.4 | | FBC-14 ENERGY CONSERVATION. | | | | 4) REQUESTED WIND LOAD ENGINEERING INCLUDING A FL. | | PRODUCT APPROVAL AND/OR A MIAMI-DADE NOA FOR THE ROOF | | STANDS NOT PROVIDED. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|