2016-10-04 14:53:55 | 2ND ELECTRICAL REVIEW NOTES |
| REVIEWED FOR COMPLIANCE WITH: |
| 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| |
| 1. NEC 600.5 REQUIRED BRANCH CIRCUIT. EACH COMMERCIAL |
| BUILDING AND EACH COMMERCIAL OCCUPANCY ACCESSIBLE TO |
| PEDESTRIANS SHALL BE PROVIDED WITH AT LEAST ONE 20 AMP |
| DEDICATED OUTLET IN AN ACCESSIBLE LOCATION AT EACH |
| ENTRANCE TO EACH TENANT SPACE FOR SIGN OR OUTLINE |
| LIGHTING. SERVICE HALLWAYS OR CORRIDORS SHALL NOT BE |
| CONSIDERED ACCESSIBLE TO PEDESTRIANS. THIS OUTLET IS |
| MISSING AT THE REAR DOOR AND AT THE FRONT ENTRY AS |
| WELL. |
| |
| A) SPOKE WITH GREGORY BONNER, HE WILL MAKE THESE |
| CORRECTIONS. (SEE MY EMAIL TO HIM DATED 10/4/16) |
| |
| 2. FBC?EC405.2.2.3 DAYLIGHT ZONE CONTROL MEANS THAT |
| DAYLIGHT ZONES SHALL BE DESIGNED SUCH THAT LIGHTS IN |
| THE DAYLIGHT ZONE ARE CONTROLLED INDEPENDENTLY OF |
| GENERAL AREA LIGHTING AND ARE CONTROLLED IN ACCORDANCE |
| WITH EITHER SECTION C405.2.2.3.1 OR SECTION |
| C405.2.2.3.2. |
| |
| A) SATISFIED |
| |
| 3. NEC 110.26 HAS SPECIFIC SAFE WORKING CLEARANCE |
| REQUIREMENTS ABOUT ELECTRICAL EQUIPMENT. |
| |
| A) SATISFIED |
| |
| 4. NEC 110.26(B) REQUIRES THAT THE DEDICATED SPACE |
| ABOUT ELECTRICAL EQUIPMENT BE SUITABLY GUARDED. |
| THEREFORE, BECAUSE THE ELECTRICAL PANELS WILL BE IN THE |
| STORAGE AREA, MARK ON THE FLOOR THE REQUIRED CLEAR |
| SPACE ABOUT THE ELECTRICAL PANELS. |
| |
| A) SATISFIED. |
| |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE?SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| CITY RE?SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| GREATLY APPRECIATED. |
| |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME DIRECTLY. |
| |