Date |
Text |
2016-09-13 07:19:26 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 16070258 |
| ADD: 1817 S DIXIE HWY |
| CONT: TBD |
| TEL: 215-380-8580 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 2ND REVIEW |
| DATE: TUES. SEPT. 13/ 2016 |
| ACTION: DENIED |
| |
| 1) LIFE SAFETY PLAN: |
| |
| 1A) COMPLIED. MAIN FRONT ENTRY DOOR / TO SWING OUT > 50 |
| OR MORE PERSONS. 2014 FBC-B 1008.1.2.. |
| |
| 1B) COMPLIED. 2014 FBC-B 3202.2 . |
| |
| 1C)SEMI-COMPLIED. IF THE SLOPE MEETS THE DEFINITION OF |
| RAMP A TOP LANDING IS REQUIRED. FBC-B 1010.7. |
| |
| 1ST ROUND COMMENT. THE DEMO PLAN INDICATES THERE BEING |
| A 6 INCH CHANGE IN GRADE FROM THE INTERIOR FINISH FLOOR |
| THE FRONT ENTRY AND THE CITY SIDEWALK. |
| 2014 FBC-B 3202.2 ENCROACHMENTS ABOVE GRADE AND BELOW 8 |
| FEET IN HEIGHT. ENCROACHMENTS INTO THE PUBLIC |
| RIGHT-OF-WAY ABOVE GRADE AND BELOW 8 FEET (2438 MM) IN |
| HEIGHT SHALL BE PROHIBITED EXCEPT AS PROVIDED FOR IN |
| SECTIONS 3202.2.1 THROUGH 3202.2.3. |
| 2014 FBC-B 1010.1 SCOPE. THE PROVISIONS OF THIS SECTION |
| SHALL APPLY TO RAMPS USED AS A COMPONENT OF A MEANS OF |
| EGRESS. |
| 2014 FBC-ACCESS. CODE 405.1. RAMPS ON ACCESSIBLE ROUTES |
| SHALL COMPLY WITH 405. |
| |
| 1D)SEMI-COMPLIED. THE NEW COURTYARD LAYOUT INDICATES |
| THE 2ND EXIT IN AN UTILITY/ SERVICE AREA. PLEASE REVIEW |
| FBC-B 1014.2 EGRESS THROUGH INTERVENING SPACES. . (1) |
| EGRESS SHALL NOT PASS THROUGH KITCHENS, STORAGE ROOMS, |
| CLOSETS OR SPACES USED FOR SIMILAR PURPOSES. |
| |
| WITH THE NEW EGRESS OPENING IN THE S. E. CORNER OF THE |
| COURTYARD THE EXISTING GATED OPENING IN THE SOUTHWEST |
| CORNER WOULD MEET THE ? DIAGONAL DISTANCE, THE GATES |
| WOULD HAVE HAD TO BE OUTSWING. |
| |
| 1ST ROUND OF COMMENTS. THE REAR COURTYARD AREA IS |
| APPROXIMATELY 1116 SQ. FT./ 15 = 76 OCCUPANTS, THE |
| FBC-B SECTION 1015.1 AND TABLE 1015.1 WHEN THERE IS AN |
| OCCUPANT LOAD OF 50 OR MORE REQUIRES 2 MEANS OF EGRESS. |
| PLEASE ALSO NOTE SINCE THERE ARE NO FIRE SPRINKLERS THE |
| 2 EXITS WILL NEED TO BE ? THE DIAGONAL DISTANCE APART. |
| 2014 FBC-B 1015.2.1 TWO EXITS OR EXIT ACCESS DOORWAYS. |
| WHERE TWO EXITS OR EXIT ACCESS DOORWAYS ARE REQUIRED |
| FROM ANY PORTION OF THE EXIT ACCESS, THE EXIT DOORS OR |
| EXIT ACCESS DOORWAYS SHALL BE PLACED A DISTANCE APART |
| EQUAL TO NOT LESS THAN ONE-HALF OF THE LENGTH OF THE |
| MAXIMUM OVERALL DIAGONAL DIMENSION OF THE BUILDING OR |
| AREA TO BE SERVED MEASURED IN A STRAIGHT LINE BETWEEN |
| EXIT DOORS. |
| |
| 1E) SEMI- COMPLIED, SEE COMMENT ABOVE. THE 2 EXIT |
| DOORWAYS/ GATES WITHIN THE COURTYARD WILL NEED TO |
| COMPLY WITH: FBC-B 1015.2.1 TWO EXITS OR EXIT ACCESS |
| DOORWAYS. WHERE TWO EXITS OR EXIT ACCESS DOORWAYS ARE |
| REQUIRED FROM ANY PORTION OF THE EXIT ACCESS, THE EXIT |
| DOORS OR EXIT ACCESS DOORWAYS SHALL BE PLACED A |
| DISTANCE APART EQUAL TO NOT LESS THAN ONE-HALF OF THE |
| LENGTH OF THE MAXIMUM OVERALL DIAGONAL DIMENSION OF THE |
| BUILDING OR AREA TO BE SERVED MEASURED IN A STRAIGHT |
| LINE BETWEEN EXIT DOORS OR EXIT ACCESS DOORWAYS. |
| |
| 1F) COMPLIED. . EXIT SIGNAGE SHALL COMPLY WITH FBC-B |
| 1011.4 & 1011.6.1. |
| |
| 2) COMPLIED. |
| |
| 3)BUILDING PROVISO: SHOP DRAWINGS TO BE A DEFERRED |
| SUBMITTAL. STRUCTURAL SHEETS NOR THE MECHANICAL SHEETS |
| SHOW ROOF FRAMING DETAILS FOR THE NEW ROOF TOP |
| PENETRATIONS WILL BE FRAMED FOR THE HOOD INTAKE AND |
| EXHAUST FANS, FRAMING DETAILS FOR THE ROOF TOP UNITS |
| NOR DETAILS FOR ROOF TOP CURBS TO THE MWFRS (MAIN WIND |
| FORCE RESISTING SYSTEM). DETAILS ARE LACKING ALSO HOW |
| THE ROOFTOP FANS WILL BE ANCHORED TO THE CURBS NOR THE |
| RTU UNITS TO THE ROOF TOP CURBS. |
| FOR ALL ROOF TOP EQUIPMENT, CURBS OR A/C STANDS, |
| DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL |
| AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE. |
| 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL |
| MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY |
| METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT |
| EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY |
| AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES. |
| EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE |
| OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES |
| SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND |
| LOADS? |
| |
| 2014 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL |
| EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO |
| WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND |
| PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA |
| BUILDING CODE, BUILDING |
| |
| 4-5) COMPLIED. |
| |
| 6) SEMI-COMPLIED. SOPERMA ROOFING PROVIDE PRODUCT |
| APPROVAL FOR THIS PRODUCT. 1609.6.4.4.1 COMPONENTS & |
| CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE |
| 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR |
| CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| APPROVALS: |
| (31)(D) ROOFING PRODUCTS AND ASSEMBLIES |
| |
| 7) COMPLIED. THE PRODUCT APPROVAL NANA WALL NOA |
| 15-0226.05. |
| |
| 8) IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. |
| THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT |
| OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE |
| PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION |
| DEVELOPMENT SERVICES DEPARTMENT |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |