Plan Review Notes
Plan Review Notes For Permit 16070258
Permit Number 16070258
Review Stop P
Sequence Number 1
Notes
Date Text
2016-07-30 10:18:201) THE PLANS REQUIRE REVIEW AND APPROVAL FROM THE DEPT.
 OF BUSINESS AND PROFESSIONAL REGULATION, DIVISION OF
 HOTELS AND RESTAURANTS.WPB AMEND. TO FBC SEC.102.1.2.
 2) SHT. A-300 - THE INSTALLATION OF GRAB BARS SHALL BE
 MEASURED FROM THE FINISH FLOOR TO THE TOP OF THE
 GRIPPING SURFACE PER 2014 FBC-ACCESSIBILITY SEC. 609.4.
 3) SHT.P-1 - THE PLAN SHOWS THE DISCHARGE FROM THE ICE
 MAKERS, GLASS RACK, ICE BIN & BAR SINK DISCHARGING INTO
 THE GREASY WASTE SYSTEM. THIS IS NOT PERMITTED PER THE
 2014 FPC SEC.1003.2.WASTES THAT DO NOT REQUIRE
 TREATMENT OR SEPARATION SHALL NOT BE DISCHARGED INTO
 ANT INTERCEPTOR OR SEPARATOR.
 4) SHT.P-1 - THE SANITARY RISER APPEARS TO SHOW THE
 FRYERS DISCHARGING INDIRECTLY INTO THE FLOOR SINK FOR
 THE GREASY WASTE SYSTEM. CLARIFY.
 5) A SEPARATE PERMIT IS REQUIRED FOR THE BACKFLOW
 PREVENTER.WPB AMEND. TO FBC SEC. 105.1.
 6) SUBMIT A DETAIL FOR THE HOT WATER RETURN PIPING. IT
 IS DIFFICULT TO SEE HOW/WHERE THE RETURN LINE IS
 CONNECTED. IT APPEARS LIKE THE FLOW ARROW AT THE CHECK
 VALVE IS REVERSED. CLARIFY.
 7) BACKFLOW PREVENTION DEVICES ARE REQUIRED ON THE
 ICEMAKERS. 2014 FPC SEC.608.3.
 8) THE GREASE INTERCEPTOR SHALL BE SIZED BASED ON THE
 NUMBER OF SEATS IN THE DINING AREA WHICH INCLUDES THE
 EXTERIOR SEATING AREA . HAVE THE SEATS IN WHAT APPEARS
 TO BE BOOTHS BEEN INCLUDED IN THE COUNT? CLARIFY.
 9) SHT. P-3 - REFERENCE IS MADE TO TABLE 709.1 OF THE
 PLUMBING CODE FOR GREASE SIZING CALCULATIONS. TABLE
 709.1 IS FOR DRAINAGE FIXTURE UNITS, NOT FOR GREASE
 SIZING CALCULATIONS. CLARIFY. THERE IS ALSO A REFERENCE
 TO TABLE 1003.5.1 FOR THE SIZING FORMULA FOR GREASE
 INTERCEPTORS. THERE IS NO SUCH TABLE IN THE PLUMBING
 CODE. CLARIFY.
 10) SHT.A-102 - SCUPPERS SHALL BE SIZED IN ACCORDANCE
 WITH TABLE 1106.7 OF THE 2014 FPC.THE SIZING SHALL BE
 BASED ON A 5 INCH PER HOUR RATE OF RAINFALL. INDICATE
 THE HEAD IN INCHES FOR THE OVERFLOW SCUPPERS AND SHOW
 THE SQUARE FOOT AREA BEING DRAINED BY EACH SCUPPER.
 11) THE SAMPLING PORT SHOWN ON THE PLANS IS NOT AN
 ACCEPTABLE DESIGN PER THE CWPB UTILITIES DEPT. A
 PRE-MANUFACTURED SAMPLING PORT OR A DIFFERENT DESIGN
 MAY BE ACCEPTABLE. YOU MAY CONTACT KELLY CRANFORD IN
 THE ENGINEERING DIVISION FOR ASSISTANCE. 561-835-7423.
 12) THE GAS SHALL BE PERMITTED UNDER A SEPARATE
 PERMIT.WPB AMEND. TO FBC SEC. 105.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692