2016-07-19 09:20:10 | 1ST REVIEW MECHANICAL |
| PERMIT #16070258 |
| 7/19/16 |
| |
| 1) ADVISORY: SEPARATE PERMITS ARE REQUIRED FOR THE |
| KITCHEN EXHAUST HOOD, FIRE SUPPRESSION, AND WALK-IN |
| COOLER. PLEASE PLACE ADVISORY NOTES IN BOLD LETTERS ON |
| THE PLANS. |
| |
| 2) ADVISORY: ALTHOUGH THE KITCHEN EXHAUST HOOD WILL BE |
| PERMITTED SEPARATELY, SOME INFORMATION MUST BE PLACED |
| ON THE MAIN PLAN TO HELP EXPEDITE THE PROJECT. PLEASE |
| PROVIDE EQUIPEMENT SCHEDULES FOR THE KITCHEN HOOD, AND |
| THE EXHAUST AND MAKEUP AIR FANS. |
| |
| 3) PROVIDE A MECHANICAL ROOF PLAN SHOWING ALL EQUIPMENT |
| LOCATIONS INCLUDING THE AC CONDENSERS, THE O/A INTAKES, |
| THE HOOD EXHAUST FAN TERMINATION, AND HOOD MAKEUP AIR |
| INTLET. SHOW ON THE PLAN ALL REQUIRED CLEARANCE |
| DISTANCE MEASUREMENTS INCLUDING: A) O/A INTAKES TO |
| EXHAUST AND VENT OUTLETS. B) EQUIPMENT TO ROOF EDGES. |
| C) SERVICE CLEARANCES AROUND EQUIPMENT. |
| |
| 4) IN ACCORDANCE WITH TABLE 403.3, AN EXHAUST RATE OF |
| 0.70 CFMS PER SQ. FT. IS REQUIRED FOR KITCHENS, AND ALL |
| AIR SUPPLIED TO THE AREA SHALL BE EXHAUSTED AND |
| RECIRCULATION IS PROHIBITED PER FOOTNOTE B AND SECTION |
| 403.2.1(3). CURRENTLY NO EXHAUST SYSTEM IS SHOWN ON THE |
| PLAN- PLEASE REVISE THE PLAN TO SHOW COMPLIANCE. |
| |
| 5) PROVIDE AIR BALANCE CALCULATIONS. |
| |
| 6) PROVIDE COMBUSTION AIR CALCULATIONS FOR THE |
| GAS-FIRED COOKING APPLIANCES- SEE SECTION 304 FBC-14 |
| FUEL GAS. |
| |
| 7) REMOVE THE AC DROPS FROM AHU #4 TO THE RESTROOMS IN |
| COMPLIANCE WITH TABLE 403.3 FOOTNOTE B, AND SECTION |
| 403.2.1(3). |
| |
| 8) DUCT SMOKE DETECTORS ARE REQUIRED IN THE RETURN AIR |
| SYSTEMS OF AHU- 1 & 4 PER SECTION 606.2.1, UNLESS THE |
| EOR SUBMITS MANUFACTURER'S SPECIFICATIONS THAT SHOW THE |
| SYSTEMS DO NOT HAVE THE CAPACITIES TO EXCEED 2000 CFMS. |
| |
| 9) PROVIDE FLEX DUCT SIZES. |
| |
| 10) INDICATE HOW ACCESS WILL BE PROVIDED FOR |
| MAINTENANCE AND REPLACEMENT OF AHU-1 AND ANY OTHER |
| AHU'S LOCATED ABOVE DRYWALL CEILINGS. |
| |
| 11) PROVIDE WIND LOAD ENGINEERING FOR ATTACHEMENT AND |
| TIE DOWN OF ALL ROOF TOP MECHANICAL EQUIPMENT TO THE |
| ROOF STRUCTURE INCLUDING THE CONDENSERS AND CONDENSER |
| STANDS, THE FANS AND FAN CURBS, AND THE O/A INTAKES- |
| SEE SECTION 301.15, AND SECTION 1609 FBC-14 BUILDING |
| FOR WIND LOAD DESIGN CRITERIA- INDICATE THE WIND SPEED, |
| EXPOSURE CATEGORY, IMPORTANCE FACTOR AND DESIGN |
| PRESSURES. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL PLANS EXAMINER |
| 561-805-6719 |