Plan Review Notes
Plan Review Notes For Permit 16070258
Permit Number 16070258
Review Stop M
Sequence Number 1
Notes
Date Text
2016-07-19 09:20:101ST REVIEW MECHANICAL
 PERMIT #16070258
 7/19/16
  
 1) ADVISORY: SEPARATE PERMITS ARE REQUIRED FOR THE
 KITCHEN EXHAUST HOOD, FIRE SUPPRESSION, AND WALK-IN
 COOLER. PLEASE PLACE ADVISORY NOTES IN BOLD LETTERS ON
 THE PLANS.
  
 2) ADVISORY: ALTHOUGH THE KITCHEN EXHAUST HOOD WILL BE
 PERMITTED SEPARATELY, SOME INFORMATION MUST BE PLACED
 ON THE MAIN PLAN TO HELP EXPEDITE THE PROJECT. PLEASE
 PROVIDE EQUIPEMENT SCHEDULES FOR THE KITCHEN HOOD, AND
 THE EXHAUST AND MAKEUP AIR FANS.
  
 3) PROVIDE A MECHANICAL ROOF PLAN SHOWING ALL EQUIPMENT
 LOCATIONS INCLUDING THE AC CONDENSERS, THE O/A INTAKES,
 THE HOOD EXHAUST FAN TERMINATION, AND HOOD MAKEUP AIR
 INTLET. SHOW ON THE PLAN ALL REQUIRED CLEARANCE
 DISTANCE MEASUREMENTS INCLUDING: A) O/A INTAKES TO
 EXHAUST AND VENT OUTLETS. B) EQUIPMENT TO ROOF EDGES.
 C) SERVICE CLEARANCES AROUND EQUIPMENT.
  
 4) IN ACCORDANCE WITH TABLE 403.3, AN EXHAUST RATE OF
 0.70 CFMS PER SQ. FT. IS REQUIRED FOR KITCHENS, AND ALL
 AIR SUPPLIED TO THE AREA SHALL BE EXHAUSTED AND
 RECIRCULATION IS PROHIBITED PER FOOTNOTE B AND SECTION
 403.2.1(3). CURRENTLY NO EXHAUST SYSTEM IS SHOWN ON THE
 PLAN- PLEASE REVISE THE PLAN TO SHOW COMPLIANCE.
  
 5) PROVIDE AIR BALANCE CALCULATIONS.
  
 6) PROVIDE COMBUSTION AIR CALCULATIONS FOR THE
 GAS-FIRED COOKING APPLIANCES- SEE SECTION 304 FBC-14
 FUEL GAS.
  
 7) REMOVE THE AC DROPS FROM AHU #4 TO THE RESTROOMS IN
 COMPLIANCE WITH TABLE 403.3 FOOTNOTE B, AND SECTION
 403.2.1(3).
  
 8) DUCT SMOKE DETECTORS ARE REQUIRED IN THE RETURN AIR
 SYSTEMS OF AHU- 1 & 4 PER SECTION 606.2.1, UNLESS THE
 EOR SUBMITS MANUFACTURER'S SPECIFICATIONS THAT SHOW THE
 SYSTEMS DO NOT HAVE THE CAPACITIES TO EXCEED 2000 CFMS.
  
 9) PROVIDE FLEX DUCT SIZES.
  
 10) INDICATE HOW ACCESS WILL BE PROVIDED FOR
 MAINTENANCE AND REPLACEMENT OF AHU-1 AND ANY OTHER
 AHU'S LOCATED ABOVE DRYWALL CEILINGS.
  
 11) PROVIDE WIND LOAD ENGINEERING FOR ATTACHEMENT AND
 TIE DOWN OF ALL ROOF TOP MECHANICAL EQUIPMENT TO THE
 ROOF STRUCTURE INCLUDING THE CONDENSERS AND CONDENSER
 STANDS, THE FANS AND FAN CURBS, AND THE O/A INTAKES-
 SEE SECTION 301.15, AND SECTION 1609 FBC-14 BUILDING
 FOR WIND LOAD DESIGN CRITERIA- INDICATE THE WIND SPEED,
 EXPOSURE CATEGORY, IMPORTANCE FACTOR AND DESIGN
 PRESSURES.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER