Plan Review Notes
Plan Review Notes For Permit 16070258
Permit Number 16070258
Review Stop E
Sequence Number 1
Notes
Date Text
2016-07-12 09:07:327/12/16 I SPOKE WITH THE ENGINEER TO DISCUSS THE ITEMS
 MENTIONED BELOW. HE UNDERSTANDS AND CONCURS WITH THE
 COMMENTS. WITH REGARDS TO THE SIGN OUTLET, THE REAR
 DOORS ARE NOT ENTRY BUT LEAD IN TO A CLOSED PATIO AREA.
 HE WILL INDICATE THAT ON THE DRAWINGS. IF THAT IS THE
 CASE THE SIGN REQUIREMENT WILL NOT APPLY AS THEY ARE
 NOT ENTRY DOORS.
  
 1ST ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 1. NEC 600.5 REQUIRED BRANCH CIRCUIT. EACH COMMERCIAL
 BUILDING AND EACH COMMERCIAL OCCUPANCY ACCESSIBLE TO
 PEDESTRIANS SHALL BE PROVIDED WITH AT LEAST ONE 20 AMP
 DEDICATED OUTLET IN AN ACCESSIBLE LOCATION AT EACH
 ENTRANCE TO EACH TENANT SPACE FOR SIGN OR OUTLINE
 LIGHTING. SERVICE HALLWAYS OR CORRIDORS SHALL NOT BE
 CONSIDERED ACCESSIBLE TO PEDESTRIANS. THIS OUTLET IS
 MISSING AT THE REAR DOORS.
 2. FBC-EC405.2.2.3 DAYLIGHT ZONE CONTROL MEANS THAT
 DAYLIGHT ZONES SHALL BE DESIGNED SUCH THAT LIGHTS IN
 THE DAYLIGHT ZONE ARE CONTROLLED INDEPENDENTLY OF
 GENERAL AREA LIGHTING AND ARE CONTROLLED IN ACCORDANCE
 WITH EITHER SECTION C405.2.2.3.1 OR SECTION
 C405.2.2.3.2.
 3. NEC 110.26 HAS SPECIFIC SAFE WORKING CLEARANCE
 REQUIREMENTS ABOUT ELECTRICAL EQUIPMENT.
 4. NEC 110.26(B) REQUIRES THAT THE DEDICATED SPACE
 ABOUT ELECTRICAL EQUIPMENT BE SUITABLY GUARDED.
 THEREFORE, BECAUSE THE ELECTRICAL PANELS WILL BE IN THE
 STORAGE AREA, MARK ON THE FLOOR THE REQUIRED CLEAR
 SPACE ABOUT THE ELECTRICAL PANELS.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  