2016-07-12 09:07:32 | 7/12/16 I SPOKE WITH THE ENGINEER TO DISCUSS THE ITEMS |
| MENTIONED BELOW. HE UNDERSTANDS AND CONCURS WITH THE |
| COMMENTS. WITH REGARDS TO THE SIGN OUTLET, THE REAR |
| DOORS ARE NOT ENTRY BUT LEAD IN TO A CLOSED PATIO AREA. |
| HE WILL INDICATE THAT ON THE DRAWINGS. IF THAT IS THE |
| CASE THE SIGN REQUIREMENT WILL NOT APPLY AS THEY ARE |
| NOT ENTRY DOORS. |
| |
| 1ST ELECTRICAL REVIEW NOTES |
| REVIEWED FOR COMPLIANCE WITH: |
| 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| |
| 1. NEC 600.5 REQUIRED BRANCH CIRCUIT. EACH COMMERCIAL |
| BUILDING AND EACH COMMERCIAL OCCUPANCY ACCESSIBLE TO |
| PEDESTRIANS SHALL BE PROVIDED WITH AT LEAST ONE 20 AMP |
| DEDICATED OUTLET IN AN ACCESSIBLE LOCATION AT EACH |
| ENTRANCE TO EACH TENANT SPACE FOR SIGN OR OUTLINE |
| LIGHTING. SERVICE HALLWAYS OR CORRIDORS SHALL NOT BE |
| CONSIDERED ACCESSIBLE TO PEDESTRIANS. THIS OUTLET IS |
| MISSING AT THE REAR DOORS. |
| 2. FBC-EC405.2.2.3 DAYLIGHT ZONE CONTROL MEANS THAT |
| DAYLIGHT ZONES SHALL BE DESIGNED SUCH THAT LIGHTS IN |
| THE DAYLIGHT ZONE ARE CONTROLLED INDEPENDENTLY OF |
| GENERAL AREA LIGHTING AND ARE CONTROLLED IN ACCORDANCE |
| WITH EITHER SECTION C405.2.2.3.1 OR SECTION |
| C405.2.2.3.2. |
| 3. NEC 110.26 HAS SPECIFIC SAFE WORKING CLEARANCE |
| REQUIREMENTS ABOUT ELECTRICAL EQUIPMENT. |
| 4. NEC 110.26(B) REQUIRES THAT THE DEDICATED SPACE |
| ABOUT ELECTRICAL EQUIPMENT BE SUITABLY GUARDED. |
| THEREFORE, BECAUSE THE ELECTRICAL PANELS WILL BE IN THE |
| STORAGE AREA, MARK ON THE FLOOR THE REQUIRED CLEAR |
| SPACE ABOUT THE ELECTRICAL PANELS. |
| |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| GREATLY APPRECIATED. |
| |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME DIRECTLY. |
| |