Plan Review Notes
Plan Review Notes For Permit 16070241
Permit Number 16070241
Review Stop P
Sequence Number 1
Notes
Date Text
2016-07-08 16:23:141ST REVIEW
  
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
  
 PLUMBING COMMENTS:
  
 1. THE ZURN MODEL 975XL IS NOT LEAD FREE A WEIGHTED
 AVERAGE OF NOT MORE THAN 0.25% IN THE WETTED
 SURFACE MATERIAL. PER NSF/ANSI 61-372
  
 2. PLEASE INDICATE WHAT SIZE BACK FLOW YOU ARE
 INSTALLING. PER WPB AMEND TO FBC 107.2.1