2016-08-05 10:01:244850 LORING DRIVE
 PERMIT #16070228
 MASTER #14120909
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO*****
  
 REPEAT COMMENT: INDICATE THE FLOORS TO BE TESTED IN
 EXCESS OF THE 200 PSI HYDROSTATIC TEST PRESSURE.
 INDICATE THE TEST PRESSURE (ABOVE 200 PSI) NEEDED AT
 THESE FLOORS.
  
 SHEET 2 OF 11:
 1) PLAN INDICATES A HYDROSTATIC TEST PRESSURE OF 200
 PSI. SYSTEMS SHALL BE TESTED AT 50 PSI ABOVE WORKING
 PRESSURE; THEREFORE, THE 1ST FLOOR SHOULD BE TESTED AT
 254 PSI (PUMP CHURN 148 PSI, PLUS CITY SUPPLY 56 PSI,
 PLUS 50 PSI ABOVE WORKING). THE 254 PSI HYDRO TEST
 PRESSURE WILL APPLY TO THE SYSTEM FEED MAINS AND
 STANDPIPES. THE SPRINKLER SYSTEMS WILL BE PROTECTED BY
 A PRESSURE REDUCING VALVE SET TO A MAXIMUM PRESSURE OF
 165 PSI; THEREFORE, THE CROSS MAINS, BRANCHLINES AND
 SPRINKLERS SHALL BE PRESSURE TESTED TO AT LEAST 215
 PSI.
  
 2) ORDINARY HAZARD ROOM MECHANICAL CHILLER #182 HAS
 SEVERAL SPRINKLERS WITH COVERAGES EXCEEDING 130 SQUARE
 FEET.
  
 3) THE CENTER NORTH SPRINKLER IN MULTIPURPOSE #125 IS
 LOCATED IN THE 10'-8" CEILING. THE ADJACENT 9'-8"
 SOFFIT TO THE NORTH OBSTRUCTS THE SPRAY OF THIS
 SPRINKLER PER NFPA 13 TABLE 8.6.5.1.2.
  
 4) TREATMENT #140 HAS A SPRINKLER LOCATED IN THE UPPER
 9'-0" CEILING; HOWEVER, THE ADJACENT 8'-0" SOFFITS
 OBSTRUCT THE SPRAY OF THE SPRINKLER ON THREE SIDES PER
 NFPA 13 TABLE 8.6.5.1.2.
  
 GENERAL OBSERVATION:
 1) RESIDENTIAL SIDEWALL SPRINKLERS ARE TYPICALLY
 INSTALLED 1"- 6" BELOW THE CEILING. THE RESIDENTIAL
 SIDEWALL SPRINKLERS THAT WERE SUBMITTED ALLOW THE
 SIDEWALL SPRINKLERS TO BE INSTALLED UP TO 12" BELOW THE
 CEILING. THIS SHOULD BE NOTED ON ALL PLANS FOR THE
 INSTALLER, OTHERWISE SPRINKLERS INSTALLED 1" - 6" BELOW
 THE CEILING WILL BE OBSTRUCTED BY SOFFITS IN SEVERAL
 DWELLING UNITS SUCH AS UNIT #107 (UNIT TYPE B1A), UNIT
 #106 (UNIT TYPE C3), UNIT #220 (UNIT TYPE C3).
  
 SHEET 5 OF 11:
 1) ARCHITECTURAL AND SPRINKLER PLANS DO NOT INDICATE A
 CEILING HEIGHT IN UNIT #216 (UNIT TYPE E2) AND UNIT
 #218 (UNIT TYPE D2). THESE UNITS FEATURE BEDROOM
 SOFFITS THAT MAY OBSTRUCT THE SIDEWALL SPRINKLER SPRAY
 NFPA 13 TABLE 8.10.7.1.3. THIS SEEMS TO BE NEAR TYPICAL
 CONDITIONS ON EACH FLOOR ABOVE.
  
 SHEET 8 OF 11:
 1) UNIT 1018 (UNIT TYPE D) THE MASTER BEDROOM HAS A
 CEILING HEIGHT OF 10'-0" AND A SOFFIT HEIGHT OF 8'-0".
 THE SOFFIT CREATES A SIDEWALL SPRAY OBSTRUCTION PER
 NFPA 13 TABLE 8.10.7.1.3.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE