| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| RELIABLE SPRINKLER MODEL G5 WAS SUBMITTED BUT CANNOT BE |
| LOCATED ON ANY OF THE PLANS. |
| |
| SITE PLAN INDICATES THE FIRE PUMP IS "NOT IN CONTRACT" |
| HOWEVER, FIRE PUMP ISOMETRIC AND PUMP BILL OF MATERIALS |
| HAVE BEEN PROVIDED. |
| |
| SUBMIT PRODUCT DATA FOR FIRE PUMP, JOCKEY PUMP, |
| CONTROLLERS, PRESSURE REDUCING VALVES, PIPE, FITTINGS, |
| ETC. |
| |
| 1ST FLOOR PLANS ARE NOT SCALABLE; HOWEVER, PLANS |
| INDICATE A SCALE OF 3/32"=1'-0". PLANS ARE REQUIRED TO |
| A MINIMUM OF 1/8"=1'-0". |
| |
| PROVIDE LOCKING KNOX CAPS ON FIRE DEPARTMENT |
| CONNECTION. |
| |
| FOR THE AREAS EXPOSED TO STRUCTURE (NO CEILING) |
| INDICATE IF THE SPACE IS OBSTRUCTED CONSTRUCTION OR |
| UNOBSTRUCTED CONSTRUCTION AND INDICATE THE MAXIMUM |
| SPRINKLER DISTANCE LOCATED BELOW THE STRUCTURE OR ROOF |
| DECK (IF OBSTRUCTED CONSTRUCTION). |
| |
| PROVIDE A FLEXIBLE DROP DETAIL INDICATING THE MAXIMUM |
| NUMBER OF BENDS PERMITTED AND THE MINIMUM BEND RADIUS |
| PERMITTED IN THE LISTING DATA. |
| |
| INDICATE THE FLOORS TO BE TESTED IN EXCESS OF THE 200 |
| PSI HYDROSTATIC TEST PRESSURE. INDICATE THE TEST |
| PRESSURE (ABOVE 200 PSI) NEEDED AT THESE FLOORS. |
| |
| RELIABLE MODEL RESIDENTIAL SPRINKLERS ARE LOCATED IN |
| SEVERAL ROOMS THAT ARE NOT DWELLING UNITS. PER NFPA 13 |
| SECTION 8.4.5.1 RESIDENTIAL SPRINKLERS SHALL BE |
| PERMITTED IN DWELLING UNITS AND THEIR ADJOINING |
| CORRIDORS. |
| |
| SPRINKLER FLOOR CONTROL VALVES (SEVERAL SHEETS): PER |
| NFPA 13 SECTION 8.16.1.2.2 PRESSURE GAUGES SHALL BE |
| INSTALLED ON THE INLET AND OUTLET SIDES OF EACH |
| PRESSURE-REDUCING VALVE. A RELIEF VALVE OF NOT LESS |
| THAN 1/2-INCH IN SIZE SHALL BE PROVIDED ON THE |
| DISCHARGE SIDE OF THE PRESSURE-REDUCING VALVE SET TO |
| OPERATE AT A PRESSURE NOT EXCEEDING 175 PSI. |
| |
| 2ND FLOOR: SPRINKLERS LOCATED IN THE HIGH CEILING OF |
| LIVING/LIBRARY ROOM #121 NEED TO BE SUPPLIED FROM THE |
| 1ST FLOOR SPRINKLER SYSTEM SEEING THAT THE SPRINKLERS |
| ARE PROTECTING THE FLOOR AREA OF THE 1ST FLOOR, |
| OTHERWISE FIREFIGHTERS MAY INCORRECTLY ASSUME THE FIRE |
| IS LOCATED ON THE 2ND FLOOR WHEN THE FLOW SWITCH |
| OPERATES. |
| |
| 10TH FLOOR: THE HYDRAULIC CALCULATION NODES DO NOT |
| MATCH THE HYDRAULIC NODES ON THE PLANS. FOR EXAMPLE, |
| HYDRAULIC CALCULATIONS INDICATE FLOWING NODES #1001 - |
| #1005; HOWEVER, THE PLANS SHOW NODES IN THE 300'S AND |
| 3000'S. |
| |
| 10TH FLOOR: NO HYDRAULIC CALCULATIONS SUBMITTED FOR |
| AREAS OUTSIDE THE DWELLING UNITS SUCH AS TRASH ROOMS, |
| STORAGE ROOMS, COMMUNITY ROOMS ETC. |
| |
| 10TH FLOOR: PROVIDE HYDRAULIC CALCULATION FOR 4 |
| SIDEWALL SPRINKLERS IN UNIT #1019. |
| |
| 10TH FLOOR: RESIDENTIAL TYPE SPRINKLERS SHOWN IN |
| ACTIVITY ROOM #1017 AND COMMUNITY ROOM #937 (TYPICAL |
| SEVERAL FLOORS). PER NFPA 13 SECTION 8.4.5.1 |
| RESIDENTIAL SPRINKLERS SHALL BE PERMITTED IN DWELLING |
| UNITS AND THEIR ADJOINING CORRIDORS. |
| |
| STANDPIPE RISERS: PROVIDE PRESSURE GAUGES AT THE TOP OF |
| THE STANDPIPES PER NFPA 14 SECTION 5.5. |
| |
| FIRE PUMP ISOMETRIC: PER NFPA 20 (2010 EDITION) SECTION |
| 4.14.6.3.2, THE DISTANCE OF THE FIRE PUMP SUCTION |
| FLANGE AND ANY ADJACENT SUCTION PIPE ELBOW/TEE FLANGE |
| SHALL BE SEPARATED BY AT LEAST 10 PIPE DIAMETERS WHEN |
| THE ELBOW/TEE HAS A CENTERLINE PLANE PARALLEL TO A |
| HORIZONTAL SPLIT-CASE PUMP SHAFT. NOTE: THE CODE |
| REQUIREMENTS HAVE NOT CHANGED IN THE LATEST EDITION OF |
| THE STANDARD; HOWEVER, DIAGRAMS OF CORRECT/INCORRECT |
| SUCTION PIPE INSTALLATIONS HAVE BEEN UPDATED IN FIGURE |
| A4.14.6 OF NFPA 20 - 2013 EDITION. |
| |
| A COMPLETE PLAN REVIEW CANNOT BE COMPLETED AT THIS TIME |
| DUE TO SCALING AND TECHNICAL ERRORS SUBMITTED ON THE |
| PLANS. ADDITIONAL PLAN REVIEW COMMENTS MAY BE GENERATED |
| DURING PLAN RESUBMISSION. |
| |