2016-09-27 15:58:062ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16070193
 9/27/16
  
 1) THE REQUIRED AC AND ENERGY CALCULATIONS REQUESTED IN
 THE 1ST REVIEW WERE NOT SUBMITTED- PLEASE COMPLY.
  
 2) COMMENT #3 FROM THE 1ST REVIEW STILL PARTIALLY
 EXISTS- EXHAUST VENTILATION CALCULATIONS FOR EF-2 NOT
 PROVIDED.
  
 3) SHEET M2.1: COMMENT #4 FROM THE 1ST REVIEW STILL
 PARTIALLY EXISTS- RECIRCULATION OF AIR FROM THE DETAIL
 BAY TO ADJOINING AREAS IS PROHIBITED.
  
 4) M2.1: COMMENT #5 FROM THE 1ST REVIEW STILL EXISTS-
 LOCATIONS OF HAZARDOUS GAS SENSORS NOT SHOWN AND
 APPROVED PRODUCTS NOT SUBMITTED. A) ADDITIONAL
 INFORMATION IS REQUIRED TO DETERMINE IF THE EXHAUST
 VENTILATION SYSTEM IS ADEQUATELY SIZED AND WILL
 FUNCTION ACCORDING TO CODE. HYDROGEN IS INCLUDED IN THE
 TOXIC GAS LIST ON THE NEW M4.1 SHEET. PLEASE REFER TO
  
 SECTION 502.4 AND CLARIFY IF HYDOGEN BATTERIES WILL BE
 STORED IN THE DETAIL BAY OR STORAGE ROOM. PLEASE NOTE
 CONTINOUS EXHAUST VENTILATION MAY BE REQUIRED.
  
 5) M2.1: COMMENT #7 FROM THE 1ST REVIEW STILL EXISTS.
 NO CORECTIONS HAVE BEEN MADE TO THE PLANS TO SHOW
 REQUIRED EXHAUST VENTILATION FOR THE VEHICLE STORAGE
 AREA.
  
 6) M2.1: PLEASE SHOW THE LOCATION OF KEYED NOTE #3 ON
 THE PLANS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER