Plan Review Notes
Plan Review Notes For Permit 16070193
Permit Number 16070193
Review Stop M
Sequence Number 1
Notes
Date Text
2016-08-02 12:39:501ST REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION
 CODES
 PERMIT #16070193
 8/2/16
  
 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR
 RTU'S 1, 2, 3, & 4- SECTION 403.2.1 FBC-14 ENERGY
 CONSERVATION.
  
 2) PROVIDE ENERGY CALCULATIONS- SECTIONS C101.2 &
 C401.2 FBC-14 ENERGY CONSERVATION.
  
 3) SHEET M1.1: OUTDOOR AIR AND EXHAUST VENTILATION
 CALCULATIONS ARE REQUIRED PER TABLE 403.3 HOWEVER THE
 ENGINEER IS INDICATING A DESIGN BASED ON THE
 VENTILATION RATE PROCEDURE PER FBC-14 AND ASHRAE 62.1.
 SEE SECTIONS 6.2.1- 6.2.7 ASHRAE 62.1 AND PROVIDE
 CALCULATIONS AND EQUATION 6-1 ON THE PLANS. PLEASE NOTE
 PER SECTION 6.1, EXHAUST VENTILATION MUST STILL BE
 PROVIDED WHERE REQUIRED.
  
 4) M2.1 DETAIL BAY: PROVIDE AN EXHAUST VENTILATION
 CALCULATION PER TABLE 6-4 ASHRAE 62.1 AND TABLE 403.3
 FBC-14 MECHANICAL. PLEASE NOTE PER TABLE 403.3 FOOTNOTE
 B, RECIRCULATION OF AIR FROM THE DETAIL BAY TO THE
 STORAGE AND TOILET ROOMS IS PROHIBITED- PLEASE CORRECT
 THE PLAN.
  
 5) M1.2, M2.1, & M4.1: THE EXHAUST FAN SCHEDULE
 SPECIFIES EF-3 TO BE INTERLOCKED WITH HAZARDOUS GASES
 SENSORS. SHOW THE LOCATIONS OF THE SENSORS AND PROVIDE
 A SUBMITTAL WITH APPROVAL SIGNATURE BY THE EOR.
 A) M4.1: INDICATE WHICH RTU'S AND WHICH EXHAUST FANS
 WILL BE LINKED TO THE SENSORS.
  
 6) M2.1: PROVIDE AN EXHAUST SYSTEM AND CALCULATION FOR
 THE JANITOR'S CLOSET- TABLE 6-4 ASHRAE 62.1.
  
 7) M2.1: ALTHOUGH THE VEHICLE SHOWROOM AREA HAS BEEN
 CLASSIFIED AS S-1 STORAGE UNDER A PROPOSED ALTERNATIVE
 DESIGN METHOD, THE MECHANICAL PLANS ARE NOT SHOWING A
 MEANS OF EXHAUST VENTILATION WHICH IS TYPICALLY
 REQUIRED FOR PRIVATE OR PUBLIC VEHICLE STORAGE. PLEASE
 PROVIDE A SYSTEM DESIGNED IN ACCORDANCE WITH THE RATES
 AND PROCEDURES REQUIRED UNDER SECTION 404.1 ENCLOSED
 PARKING GARAGES.
  
 8) PROVIDE A MECHANICAL ROOF PLAN SHOWING THE LOCATIONS
 OF ALL ROOFTOP EQUIPMENT AND REQUIRED CLEARANCE
 DISTANCES FROM EXHAUST OUTLETS TO AIR INTAKES- SECTION
 501.3.1
  
 9) PROVIDE WIND LOAD ENGINEERING FOR ATTACHMENT OF ALL
 ROOFTOP MECHANICAL EQUIPMENT INCLUDING THE RTU'S,
 EXHAUST FANS, AND THEIR RESPECTIVE CURBS- SECTION
 301.15.
  
 10) PROVIDE SHUTOFF DAMPER CONTROLS FOR THE OUTDOOR AIR
 INTAKES AS REQUIRED BY SECTION C403.2.4.4 FBC-14 ENERGY
 CONSERVATION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER