2016-07-25 17:05:20 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| 1) INFOMATIONAL ONLY : |
| |
| SHEET 008 C 7 - A FDC IS LOCATED INSIDE A GATE AND A |
| FIRE HYDRANT ON THE OTHER SIDE. ACCESS THROUGH AN OPEN |
| GATE IS REQUIRED. |
| |
| IT IS STRONGLY RECCOMMENDED THAT KNOX KEY SWITCHES BE |
| PROVIDED AT EACH GATE AND THAT ACTIVATION OF |
| ONE(EITHER) GATE OPENS AND CLOSES BOTH. |
| |
| |
| |
| 2) INFORMATIONAL ONLY : |
| |
| SHEET 014 ASP - # 9 NOTE INDICATES A KNOX BOX LOCATION |
| AS REQUIRED BY WP FIRE DEPT. |
| |
| KNOX KEY SWITCHES AT BOTH GATES FOR 24 HR EMERGENCY |
| ACCESS TO THE PROPERTY AND A KNOX BOX WITH DOOR KEYS |
| PROVIDED BY OWNER LOCATED ON THE WALL NEXT TO THE MAN |
| DOOR ON THE NORTH SIDE OF THE BUILDING. |
| |
| |
| 3) NO SHEET - I WAS UNABLE TO LOCATED A DOOR SCHEDULE |
| TO VERIFY FIRE RATINGS AND EXIT HARDWARE. EXIT DOORS |
| AND EXIT HARDWARE SHALL COMPLY WITH NFPA 1, CHAPTER 12 |
| FEATURES OF FIRE PROTECTION AND NFPA 101, CHAPTER 7, |
| MEAND OF EGRESS. |
| |
| 12.4 FIRE DOORS AND OTHER OPERATING PROTECTIVES. |
| 12.4.1* THE INSTALLATION AND MAINTENANCE OF ASSEMBLIES |
| AND DEVICES USED TO PROTECT OPENINGS IN WALLS, FLOORS, |
| AND CEILINGS AGAINST THE SPREAD OF FIRE AND SMOKE |
| WITHIN, INTO, OR OUT OFBUILDINGS SHALL COMPLY WITH |
| SECTION 12.4 AND NFPA 80, STANDARD FOR FIRE DOORS AND |
| OTHER OPENING PROTECTIVES. [80:1.1] |
| |
| 12.7.3 FIRE DOORS AND WINDOWS. |
| 12.7.3.1 OPENINGS REQUIRED TO HAVE A FIRE PROTECTION |
| RATING BY TABLE 12.7.4.2 SHALL BE PROTECTED BY |
| APPROVED, LISTED, LABELED FIRE DOOR ASSEMBLIES AND FIRE |
| WINDOW ASSEMBLIES AND THEIR ACCOMPANYING HARDWARE, |
| INCLUDING ALL FRAMES, CLOSING DEVICES, ANCHORAGE, AND |
| SILLS IN ACCORDANCE WITH THE REQUIREMENTS OF SECTION |
| 12.4, EXCEPT AS OTHERWISE SPECIFIED IN THIS CODE. |
| [101:8.3.3.1] |
| |
| PLEASE PROVIDE A DOOR SCHEDULE LISTING THE APPLICABLE |
| FIRE RATINGS AND EXIT HARDWARE. |
| |
| |
| 4) NO SHEET - I WAS UNABLE TO LOCATE THE STAIR RAIL |
| DETAIL. HANDRAILS SHALL COMPLY WITH NFPA 101, CHAPTER |
| 7, MEANS OF EGRESS. 7.2.2.4 GUARDS AND HANDRAILS. |
| 7.2.2.4.1 HANDRAILS. |
| 7.2.2.4.1.1 STAIRS AND RAMPS SHALL HAVE HANDRAILS ON |
| BOTH SIDES, UNLESS OTHERWISE PERMITTED IN 7.2.2.4.1.5 |
| OR 7.2.2.4.1.6. |
| |
| 7.2.2.4.4* HANDRAIL DETAILS. |
| 7.2.2.4.4.1 NEW HANDRAILS ON STAIRS SHALL BE NOT LESS |
| THAN 34 IN. (865 MM), AND NOT MORE THAN 38 IN. (965 |
| MM), ABOVE THE SURFACE OF THE TREAD, MEASURED |
| VERTICALLY TO THE TOP OF THE RAIL FROM THE LEADING EDGE |
| OF THE TREAD. |
| |
| 7.2.2.4.5 GUARD DETAILS. SEE 7.1.8 FOR GUARD |
| REQUIREMENTS. |
| 7.2.2.4.5.1 THE HEIGHT OF GUARDS REQUIRED IN 7.1.8 |
| SHALL BE MEASURED VERTICALLY TO THE TOP OF THE GUARD |
| FROM THE SURFACE ADJACENT THERETO. |
| 7.2.2.4.5.2 GUARDS SHALL BE NOT LESS THAN 42 IN. (1065 |
| MM) HIGH, EXCEPT AS PERMITTED BY ONE OF THE FOLLOWING: |
| (1) EXISTING GUARDS WITHIN DWELLING UNITS SHALL BE |
| PERMITTED TO BE NOT LESS THAN 36 IN. (915 MM) HIGH. |
| (2) THE REQUIREMENT OF 7.2.2.4.5.2 SHALL NOT APPLY IN |
| ASSEMBLY OCCUPANCIES WHERE OTHERWISE PROVIDED IN |
| CHAPTERS 12 AND 13. |
| |
| PLEASE PROVIDE A SHEET DETAIL COMPLIANCE WITH THE ABOVE |
| |
| |
| 5) NO SHEET - I WAS UNABLE TO LOCATE THE WIDTH |
| DIMENSION OF THE PROPOSED INTERIOR STAIR. |
| |
| 7.2.2.2.1 STANDARD STAIRS. |
| 7.2.2.2.1.1 STAIRS SHALL MEET THE FOLLOWING CRITERIA: |
| (1) NEW STAIRS SHALL BE IN ACCORDANCE WITH TABLE |
| 7.2.2.2.1.1(A) AND 7.2.2.2.1.2. |
| |
| 7.2.2.2.1.2 MINIMUM NEW STAIR WIDTH. |
| (A) WHERE THE TOTAL OCCUPANT LOAD OF ALL STORIES SERVED |
| BY THE STAIR IS FEWER THAN 50, THE MINIMUM WIDTH CLEAR |
| OF ALL OBSTRUCTIONS, EXCEPT PROJECTIONS NOT MORE THAN |
| 4? IN. (114 MM) AT OR BELOW HANDRAIL HEIGHT ON EACH |
| SIDE, SHALL BE 36 IN. (915 MM). |
| |
| PLEASE PROVIDE A SHEET DETAIL COMPLIANCE WITH THE ABOVE |
| |
| |
| |
| 6) SHEET 022 A 2.2 - BASED ON THE INDICATED ROOF TRUSS |
| DESIGN A LIGHWEIGHT ROOF TRUSS SIGN IS REQUIRED. PER |
| FLORIDA 69A-60.0081; NOTICE SIGNAGE IS REQUIRED FOR |
| STRUCTURES WITH LIGHT-FRAME TRUSS-TYPE CONSTRUCTION. |
| ANY COMMERCIAL, INDUSTRIAL, OR ANY MULTIUNIT |
| RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE WHICH USES |
| HORIZONTAL OR VERTICAL LIGHT-FRAME TRUSS-TYPE |
| CONSTRUCTION IN ANY PORTION SHALL BE MARKED WITH A |
| MALTESE CROSS SIGN MEASURING 8 INCHES HORIZONTALLY AND |
| 8 INCHES VERTICALLY, OF A BRIGHT RED REFLECTIVE COLOR. |
| THE APPROVED SYMBOL SHALL BE PLACED WITHIN 24 INCHES TO |
| THE LEFT OF THE MAIN ENTRY DOOR. |
| 1. STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE |
| MARKED WITH THE LETTER "R". |
| 2. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS |
| SHALL BE MARKED WITH THE LETTER "F". |
| 3. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF |
| SYSTEMS SHALL BE MARKED WITH THE LETTERS "R/F". |
| |
| |
| PLEASE PROVIDE A NOTE INDICATING COMPLIANCE ON SHEET |
| 035 A 2.0. |
| |
| |
| 7) SHEET 050 E 2.1 - CLARIFICATION IS NEEDED REGARDING |
| NOTE # 2 AND NOTE # 4 - A NG GENERATOR AT THE NORTH |
| EAST CORNER AND A FUEL TANK PUMP IS INDICATED ON THE |
| SOUTH EAST CORNER. |
| |
| A. PLEASE PROVIDE A CONFIRMATION/VERIFICATION NOTE |
| INDICATING IF THIS GENERATOR WILL BE PROVIDING |
| EMERGENCY POWER FOR THE LIFE SAFETY SYSTEMS. |
| |
| THE GENERATOR SHALL COMPLY WITH NFPA 110, STANDARD FOR |
| EMERGENCY AND STANDBY POWER SYSTEMS, 2013 EDITION. |
| |
| PROVIDE A NOTE INDICATING UNDER SEPARATE PERMIT. |
| |
| B. WHAT TYPE OF FUEL TANK IS PROPOSED? |
| |
| MOTOR FUEL DISPENSING FACILITIES AND REPAIR GARAGES |
| SHALL COMPLY WITH NFPA 30 A, 2012 EDITION |
| |
| PROVIDE A NOTE INDICATING UNDER SEPARATE PERMIT. |
| |
| |
| |
| 8) SHEET 051 E 2.2 - IT IS UNCLEAR IF THE EXIT LIGHT |
| OVER THE NORTH MAN DOOR CAN/WILL BE SEEN FROM THE |
| WAREHOUSE AREA. |
| |
| PLEASE REVIEW AND VERIFY. IT IT CAN'T BE SEEN AND |
| ADDITIONAL EXIT SIGN WILL BE NEEDED TO LEAD/DIRECT TO |
| THAT AREA. |
| |
| |
| |
| 9) SHEET 051 E 2.2 - NO EXIT SIGN IS INDICATED OVER THE |
| SOUTH GARAGE DOOR THAT IS PROPOSED TO BE THE 2ND EXIT. |
| |
| PLEASE PROVIDE AN EXIT SIGN AT THIS LOCATION. |
| |
| |
| 10) SHEET 015 A 1.1 - THE SOUTH GARAGE DOOR IS |
| INDICATED AS BEING USED AS A REQUIRED EXIT DOOR. |
| ADDITIONAL CLARIFICATION IS NEEDED. |
| |
| HOW IS IT PROPOSED THAT THIS DOOR GARAGE DOOR CAN BE |
| OPENED IN THE EVENT OF AN EMERGENCY FOR EXITING |
| PURPOSES. PROVIDE DETAILS. |
| |
| PER NFPA 101, CHAPTER 42 STORAGE OCCUPANCIES , |
| 42.2.2.2.5 WHERE HORIZONTAL OR VERTICAL SECURITY |
| GRILLES OR DOORS ARE USED AS A PART OF THE REQUIRED |
| MEANS OF EGRESS FROM A TENANT SPACE, SUCH GRILLES OR |
| DOORS SHALL COMPLY WITH 7.2.1.4.1. |
| |
| 7.2.1.4 SWING AND FORCE TO OPEN. |
| 7.2.1.4.1* SWINGING-TYPE DOOR ASSEMBLY REQUIREMENT. ANY |
| DOOR ASSEMBLY IN A MEANS OF EGRESS SHALL BE OF THE |
| SIDE-HINGED OR PIVOTED- SWINGING TYPE, AND SHALL BE |
| INSTALLED TO BE CAPABLE OF SWINGING FROM ANY POSITION |
| TO THE FULL REQUIRED WIDTH OF THE OPENING IN WHICH IT |
| IS INSTALLED, UNLESS OTHERWISE SPECIFIED AS FOLLOWS: |
| (1) DOOR ASSEMBLIES IN DWELLING UNITS, AS PROVIDED IN |
| CHAPTER 24, SHALL BE PERMITTED. |
| (2) DOOR ASSEMBLIES IN RESIDENTIAL BOARD AND CARE |
| OCCUPANCIES, AS PROVIDED IN CHAPTERS 32 AND 33, SHALL |
| BE PERMITTED. |
| (3) WHERE PERMITTED IN CHAPTERS 11 THROUGH 43, |
| HORIZONTAL-SLIDING OR VERTICAL-ROLLING SECURITY GRILLES |
| OR DOOR ASSEMBLIES THAT ARE PART OF THE REQUIRED MEANS |
| OF EGRESS SHALL BE PERMITTED, PROVIDED THAT ALL OF THE |
| FOLLOWING CRITERIA ARE MET: |
| (A) SUCH GRILLES OR DOOR ASSEMBLIES SHALL REMAIN |
| SECURED IN THE FULLY OPEN POSITION DURING THE PERIOD OF |
| OCCUPANCY BY THE GENERAL PUBLIC. |
| (B) ON OR ADJACENT TO THE GRILLE OR DOOR OPENING, THERE |
| SHALL BE A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT |
| LESS THAN 1 IN. (25 MM) HIGH ON A CONTRASTING |
| BACKGROUND THAT READS AS FOLLOWS: THIS DOOR TO REMAIN |
| OPEN WHEN THE |
| BUILDING IS OCCUPIED. |
| (C) DOOR LEAVES OR GRILLES SHALL NOT BE BROUGHT TO THE |
| CLOSED POSITION WHEN THE SPACE IS OCCUPIED. |
| (D) DOOR LEAVES OR GRILLES SHALL BE OPERABLE FROM |
| WITHIN THE SPACE WITHOUT THE USE OF ANY SPECIAL |
| KNOWLEDGE OR EFFORT. |
| (E) WHERE TWO OR MORE MEANS OF EGRESS ARE REQUIRED, NOT |
| MORE THAN HALF OF THE MEANS OF EGRESS SHALL BE EQUIPPED |
| WITH HORIZONTAL-SLIDING OR VERTICAL-ROLLING GRILLES OR |
| DOOR ASSEMBLIES. |
| (4) HORIZONTAL-SLIDING DOOR ASSEMBLIES SHALL BE |
| PERMITTED UNDER ANY OF THE FOLLOWING CONDITIONS: |
| (A) HORIZONTAL-SLIDING DOOR ASSEMBLIES IN DETENTION AND |
| CORRECTIONAL OCCUPANCIES, AS PROVIDED IN CHAPTERS 22 |
| AND 23, SHALL BE PERMITTED. |
| (B) HORIZONTAL-SLIDING DOOR ASSEMBLIES COMPLYING WITH |
| 7.2.1.14 SHALL BE PERMITTED. |
| (C) UNLESS PROHIBITED BY CHAPTERS 11 THROUGH 43, |
| HORIZONTALSLIDING DOOR ASSEMBLIES SERVING A ROOM OR |
| AREA WITH AN OCCUPANT LOAD OF FEWER THAN 10 SHALL BE |
| PERMITTED, PROVIDED THAT ALL OF THE FOLLOWING CRITERIA |
| ARE MET: |
| I. THE AREA SERVED BY THE DOOR ASSEMBLY HAS NO HIGH |
| HAZARD CONTENTS. |
| II. THE DOOR ASSEMBLY IS READILY OPERABLE FROM EITHER |
| SIDE WITHOUT SPECIAL KNOWLEDGE OR EFFORT. |
| III. THE FORCE REQUIRED TO OPERATE THE DOOR ASSEMBLY IN |
| THE DIRECTION OF DOOR LEAF TRAVEL IS NOT MORE THAN 30 |
| LBF (133 N) TO SET THE DOOR LEAF IN MOTION AND IS NOT |
| MORE THAN 15 LBF (67 N) TO CLOSE THE DOOR ASSEMBLY OR |
| OPEN IT TO THE MINIMUM REQUIRED WIDTH. |
| IV. THE DOOR ASSEMBLY COMPLIES WITH ANY REQUIRED FIRE |
| PROTECTION RATING, AND, WHERE RATED, IS SELF-CLOSING OR |
| AUTOMATIC-CLOSING BY MEANS OF SMOKE DETECTION IN |
| ACCORDANCE WITH 7.2.1.8 AND IS INSTALLED IN ACCORDANCE |
| WITH NFPA 80, STANDARD FOR FIRE DOORS AND OTHER OPENING |
| PROTECTIVES. |
| V. CORRIDOR DOOR ASSEMBLIES REQUIRED TO BE |
| SELF-LATCHING HAVE A LATCH OR OTHER MECHANISM THAT |
| ENSURES THAT THE DOOR LEAF WILL NOT REBOUND INTO A |
| PARTIALLY OPEN POSITION IF FORCEFULLY CLOSED. |
| (D) WHERE PRIVATE GARAGES, BUSINESS AREAS, INDUSTRIAL |
| AREAS, AND STORAGE AREAS WITH AN OCCUPANT LOAD NOT |
| EXCEEDING 10 CONTAIN ONLY LOW OR ORDINARY HAZARD |
| CONTENTS, DOOR OPENINGS TO SUCH AREAS AND PRIVATE |
| GARAGES SHALL BE PERMITTED TO BE HORIZONTAL-SLIDING |
| DOOR ASSEMBLIES. |
| (5) WHERE PRIVATE GARAGES, BUSINESS AREAS, INDUSTRIAL |
| AREAS, AND STORAGE AREAS WITH AN OCCUPANT LOAD NOT |
| EXCEEDING 10 CONTAIN ONLY LOW OR ORDINARY HAZARD |
| CONTENTS, DOOR OPENINGS TO SUCH AREAS AND PRIVATE |
| GARAGES SHALL BE PERMITTED TO BE VERTICAL-ROLLING DOOR |
| ASSEMBLIES. |
| (6) REVOLVING DOOR ASSEMBLIES COMPLYING WITH 7.2.1.10 |
| SHALL BE PERMITTED. |
| (7) EXISTING FUSIBLE LINK?OPERATED HORIZONTAL-SLIDING |
| OR VERTICALROLLING FIRE DOOR ASSEMBLIES SHALL BE |
| PERMITTED TO BE USED AS PROVIDED IN CHAPTERS 39, 40, |
| AND 42. |
| |
| PLEASE PROVIDE A NOTE OF NARRATIVE INDICATING |
| COMPLAINCE, WITH DETAIL, WITH ANY OF THE ABOVE. |
| |
| |
| 11) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |
| [email protected] |
| |
| |
| |
| |
| |