2016-07-26 12:03:37 | ELECTRICAL REVIEW NOTES |
| REVIEWED FOR COMPLIANCE WITH: |
| 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| |
| JOB NAME: PRIVATE GARAGE |
| JOB ADDRESS: 1503 CLARE AVE. |
| DESCRIPTION: NEW CONSTRUCTION OF PRIVATE GARAGE |
| MAST. PERMIT: 16070193 |
| REVISION: |
| |
| SHEET E2.2 |
| 1. ALL FIRE ALARM WORK TO BE DONE UNDER A SEPARATE |
| PERMIT AND SUBMITTAL. |
| 2. THE AREAS MENTIONED BELOW DO NOT SEEM TO COMPLY WITH |
| FBC-E405.2.1.2 |
| 3. YOU ARE TO PROVIDE DAYLIGHT ZONES AS INDICATED IN |
| FBC-C405.2.2.3 |
| 4. YOU SHALL PROVIDE A LIGHTING DENSITY ALLOWANCE CHART |
| TO INDICATE COMPLIANCE WITH THE FBC-E. |
| 5. AREA 11 DOES NOT APPEAR TO HAVE SUFFICIENT EMERGENCY |
| LIGHTING OR LIGHTING CONTROL. |
| 6. SHOWROOMS AND AREA 11 ARE MISSING EXIT LIGHTING. |
| 7. STORAGE AREA 2 MISSING MANDATORY LIGHTING CONTROL |
| 8. DETAIL BAY IS MISSING EMERGENCY LIGHTING AND |
| LIGHTING CONTROL |
| SHEET E2.3 |
| 1. PER NEC 422.52 ELECTRIC DRINKING FOUNTAINS SHALL BE |
| CONNECTED TO A GFCI PROTECTED CIRCUIT. |
| 2. PER NEC 406.9(B) RECEPTACLES INSTALLED IN WET OR |
| DAMP LOCATIONS IN ADDITION TO THE IN-USE TYPE COVERS, |
| SHALL BE LISTED WEATHER-RESISTANT. THIS APPLIES TO ALL |
| THE WP OUTDOOR GFI RECEPTACLES. |
| SHEET E2.4 |
| 1. RTU 4 IS BEYOND THE 25? FROM THE SERVICE OUTLET AS |
| REQUIRED BY NEC 210.63. THEREFORE, AN OUTLET IS |
| REQUIRED WITHIN THE 25? MANDATED BY CODE. CAUTION: RTU |
| 2 IS CLOSE TO BEING BEYOND AS WELL. |
| SHEET E3.1 |
| 1. PER NEC 250.94 AN INTER-SYSTEM BONDING TERMINAL |
| BLOCK SHALL BE PROVIDED. |
| SHEET E3.3 |
| 1. DETAIL 3/E3.3: PER NEC 406.9(B) RECEPTACLES |
| INSTALLED IN WET OR DAMP LOCATIONS IN ADDITION TO THE |
| IN-USE TYPE COVERS SHALL BE LISTED WEATHER-RESISTANT. |
| THIS APPLIES TO ALL THE WP OUTDOOR GFI RECEPTACLES. |
| SHEET FA1 |
| 1. ALL FIRE ALARM WORK SHALL BE CONDUCTED UNDER |
| SEPARATE SUBMITTAL. |
| |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| GREATLY APPRECIATED. |
| |