Plan Review Notes
Plan Review Notes For Permit 16070193
Permit Number 16070193
Review Stop E
Sequence Number 1
Notes
Date Text
2016-07-26 12:03:37ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 JOB NAME: PRIVATE GARAGE
 JOB ADDRESS: 1503 CLARE AVE.
 DESCRIPTION: NEW CONSTRUCTION OF PRIVATE GARAGE
 MAST. PERMIT: 16070193
 REVISION:
  
 SHEET E2.2
 1. ALL FIRE ALARM WORK TO BE DONE UNDER A SEPARATE
 PERMIT AND SUBMITTAL.
 2. THE AREAS MENTIONED BELOW DO NOT SEEM TO COMPLY WITH
 FBC-E405.2.1.2
 3. YOU ARE TO PROVIDE DAYLIGHT ZONES AS INDICATED IN
 FBC-C405.2.2.3
 4. YOU SHALL PROVIDE A LIGHTING DENSITY ALLOWANCE CHART
 TO INDICATE COMPLIANCE WITH THE FBC-E.
 5. AREA 11 DOES NOT APPEAR TO HAVE SUFFICIENT EMERGENCY
 LIGHTING OR LIGHTING CONTROL.
 6. SHOWROOMS AND AREA 11 ARE MISSING EXIT LIGHTING.
 7. STORAGE AREA 2 MISSING MANDATORY LIGHTING CONTROL
 8. DETAIL BAY IS MISSING EMERGENCY LIGHTING AND
 LIGHTING CONTROL
 SHEET E2.3
 1. PER NEC 422.52 ELECTRIC DRINKING FOUNTAINS SHALL BE
 CONNECTED TO A GFCI PROTECTED CIRCUIT.
 2. PER NEC 406.9(B) RECEPTACLES INSTALLED IN WET OR
 DAMP LOCATIONS IN ADDITION TO THE IN-USE TYPE COVERS,
 SHALL BE LISTED WEATHER-RESISTANT. THIS APPLIES TO ALL
 THE WP OUTDOOR GFI RECEPTACLES.
 SHEET E2.4
 1. RTU 4 IS BEYOND THE 25? FROM THE SERVICE OUTLET AS
 REQUIRED BY NEC 210.63. THEREFORE, AN OUTLET IS
 REQUIRED WITHIN THE 25? MANDATED BY CODE. CAUTION: RTU
 2 IS CLOSE TO BEING BEYOND AS WELL.
 SHEET E3.1
 1. PER NEC 250.94 AN INTER-SYSTEM BONDING TERMINAL
 BLOCK SHALL BE PROVIDED.
 SHEET E3.3
 1. DETAIL 3/E3.3: PER NEC 406.9(B) RECEPTACLES
 INSTALLED IN WET OR DAMP LOCATIONS IN ADDITION TO THE
 IN-USE TYPE COVERS SHALL BE LISTED WEATHER-RESISTANT.
 THIS APPLIES TO ALL THE WP OUTDOOR GFI RECEPTACLES.
 SHEET FA1
 1. ALL FIRE ALARM WORK SHALL BE CONDUCTED UNDER
 SEPARATE SUBMITTAL.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  