2016-08-03 14:25:34BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16070193
 ADD: 1503 CLARE AVE.
 CONT: HEDRICK BROTHERS
 TEL: 561-578-2875/ DOUG GORDON
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. AUGUST 03/ 2016
 ACTION: DENIED
  
 1) SHEET 015A1.1 BUILDING CODE ANALYSIS INDICATES THIS
 TO BE A S1 (PRIVATE WAREHOUSE). THE PLANS INDICATE THE
 SQUARE FOOTAGE OF THE BUILDING (VB) TO BE 11,296/500 =
 23 OCCUPANTS. THERE IS ALSO A NOTE ON THE RIGHT SIDE OF
 THE PLAN OPPOSITE END OF THE BUILDING WHERE THE MAN
 DOOR (EGRESS DOOR) IS LOCATED.
 THIS NOTE INDICATES THE 2ND MEANS OF EGRESS IS THE
 OVERHEAD DOOR AS AGREED ON 05/03/16 PRELIMINARY REVIEW
 MEETING WITH CITY BUILDING OFFICIALS.
 THERE WAS DISCUSSION AS TO HANDLE A SECOND MEANS OF
 EGRESS. ONE METHOD WAS LIMITING THE OCCUPANT LOAD TO 10
 OR LESS OCCUPANTS. THE 2014 FBC-B SECTION 1008.1.2
 EXCEPTION # 1 ALLOWS IN PRIVATE GARAGES, OFFICE AREAS,
 FACTORY AND STORAGE AREAS WITH AN OCCUPANT LOAD OF 10
 OR LESS THE EGRESS DOORS DO NOT NEED TO BE PIVOTED OR
 SIDE-HINGED SWINGING TYPE.
 IF THE OWNER DOES NOT WANT TO REDUCE THE OCCUPANT LOAD
 TO COMPLY WITH SECTION 1008.1.2 OF THE 2014 FBC-B THEN
 THE DESIGNER OF RECORD WOULD NEED TO SUBMIT A LETTER TO
 THE BUILDING OFFICIAL ROBERT BROWN TO REVIEW THE PLANS
 UNDER SECTION 104.11 ALTERNATIVE MATERIALS, DESIGN AND
 METHODS OF CONSTRUCTION AND EQUIPMENT, 2014 FLORIDA
 BUILDING CODE W 2014 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION.
 IN THE MEETING THERE ARE SEVERAL CODE ARTICLE THAT WE
 HAD AGREED ON THAT COULD BE COVERED UNDER THIS SAME
 LETTER, HANDICAPPED RESTROOMS, HAND RAILS, VERTICAL
 ACCESSIBILITY RAMPS / LIFTS, AND ACCESSIBLE AREA OF THE
 BAR.
 THE DESIGNER OF RECORD WILL ALSO NEED TO INCLUDE
 REQUIREMENTS THAT WOULD BE REQUIRED BY OTHER TRADES AS
 WELL. UNLESS WE RECEIVE THIS REQUEST WE ARE OBLIGED TO
 REVIEW THE PLANS TO THE 2014 FBC FAMILY OF CODES.
  
 2) THE LOCATION OF THIS SITE LAYS IN AN A-9 FLOOD ZONE.
 NONE OF THE ARCHITECTURAL SHEETS OR STRUCTURAL SHEETS
 INDICATE WHAT THE HEIGHT OF FINISH FLOOR IS IN NGVD.
 FBC BUILDING 1612 AND CITY OF WPB CODE OF ORDINANCES
 SECTION 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD
 ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED.
 PLEASE REVIEW CITY ORDINANCE FOR THE CITY REQUIREMENTS
 REQUIRE AN ADDITIONAL 6 INCHES OF FREEBOARD ELEVATION.
 THE MINIMUM FINISH FLOOR ELEVATION CURRENTLY WOULD BE
 13.5 FT. NGVD.
  
 DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE
 REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES
 REQUIRED:
 (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE
 PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR
 HEIGHT.
 (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND
 ELEVATION CERTIFICATE IS REQUIRED.
 (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE
 CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR
 ATTENDANTS A/C PADS OR OTHER SLABS FOR GENERATORS.
 FEMA NEW FORM AVAILABLE JUNE 13/2016.
 OMB NO. 1660-0008
 EXPIRATION DATE: NOV. 30/2018
 HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM
 ADDITIONAL INFORMATION ON THE DIFFERENCES, THE NEW
 FORM, AND INSTRUCTIONS ARE AVAILABLE AT:
 HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM
  
 3) THIS REVIEW CYCLE THERE WAS NO SOILS REPORT
 SUBMITTED. 2014 FBC-B 1803.5.2 QUESTIONABLE SOIL.
 WHERE THE CLASSIFICATION, STRENGTH OR COMPRESSIBILITY
 OF THE SOIL IS IN DOUBT OR WHERE A LOAD-BEARING VALUE
 SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE
 BUILDING OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A
 GEOTECHNICAL INVESTIGATION BE CONDUCTED.
  
 4) THIS REVIEW CYCLE THERE WERE NO ENERGY DOCUMENTS
 SUBMITTED FOR NEW CONSTRUCTION. 2014 FBC-ENERGY CODE
 C401.2 APPLICATION.
 COMMERCIAL BUILDINGS SHALL COMPLY WITH ONE OF THE
 FOLLOWING:
  
 1. THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1.
  
 2. THE REQUIREMENTS OF SECTIONS C402, C403, C404 AND
 C405. IN ADDITION, COMMERCIAL BUILDINGS SHALL COMPLY
 WITH EITHER SECTION C406.2, C406.3 OR C406.4.
  
 3. THE REQUIREMENTS OF SECTION C407, C402.4, C403.2,
 C404, C405.2, C405.3, C405.4, C405.6 AND C405.7. THE
 BUILDING ENERGY COST SHALL BE EQUAL TO OR LESS THAN 85
 PERCENT OF THE STANDARD REFERENCE DESIGN BUILDING.
  
 5) THIS REVIEW THERE WERE NO PRODUCT APPROVALS
 SUBMITTED COMPLYING WITH; 2014 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE
 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (C) WALL LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, CURBS AND ROOF TOP
 FANS
 (G) PRE-ENGINEERED A/C STANDS
  
 6) ADMINISTRATION 107.3.4 DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL BE RESPONSIBLE
 FOR REVIEWING AND COORDINATING SUBMITTAL DOCUMENTS
 PREPARED BY OTHERS, INCLUDING PHASED AND DEFERRED
 SUBMITTAL ITEMS, FOR COMPATIBILITY WITH THE DESIGN OF
 THE BUILDING. THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 7) SHEET 018 _A1.4. THE ROOF PLAN SHOWS BOTH ROOF TOP
 DOWN UNITS AND THE USE OF ROOF TOP INTAKE AND EXHAUST
 FANS. SHEET 035_S2.0 SHOWS 2 DETAILS FOR THE ROOFTOP
 RTU UNITS ON SHEET 037_S4.0 DETAILS 1 & 2. BOTH OF
 THESE DETAILS ARE FOR THE RTU UNITS. THERE ARE NO
 DETAILS FOR THE INTAKE & EXHAUST FANS FOR THE BASE/
 CURB NOR FOR THE ATTACHMENT OF THE FAN HOUSING TO THE
 ROOF TOP CURB. PLEASE SUPPLY ADDITIONAL DETAILS AS WELL
 AS PRODUCT APPROVALS FOR ROOF TOP FANS AND CURBS.
 1609.6.4.4.1 COMPONENTS & CLADDING.
 FOR ALL ROOF TOP EQUIPMENT, CURBS OR A/C STANDS,
 DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL
 AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE.
 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS?
  
 8) SHEET 021_A2.1 SHOWS A ROOF TOP LADDER TO GAIN
 ACCESS TO THE ROOF TOP MECHANICAL EQUIPMENT. PLEASE
 PROVIDE COMPLIANCE WITH: ? 1509.6.4 EQUIPMENT AND
 APPLIANCES ON ROOFS OR ELEVATED STRUCTURES.
 WHERE EQUIPMENT AND APPLIANCES REQUIRING ACCESS ARE
 INSTALLED ON ROOFS OR ELEVATED STRUCTURES AT A HEIGHT
 EXCEEDING 16 FEET (4877 MM), SUCH ACCESS SHALL BE
 PROVIDED BY A PERMANENT APPROVED MEANS OF ACCESS, THE
 EXTENT OF WHICH SHALL BE FROM GRADE OR FLOOR LEVEL TO
 THE EQUIPMENT AND APPLIANCES? LEVEL SERVICE SPACE. SUCH
 ACCESS SHALL NOT REQUIRE CLIMBING OVER OBSTRUCTIONS
 GREATER THAN 30 INCHES (762 MM) HIGH OR WALKING ON
 ROOFS HAVING A SLOPE GREATER THAN 4 UNITS VERTICAL IN
 12 UNITS HORIZONTAL (33-PERCENT SLOPE).
 PERMANENT LADDERS INSTALLED TO PROVIDE THE REQUIRED
 ACCESS SHALL COMPLY WITH THE FOLLOWING MINIMUM DESIGN
 CRITERIA:
 1. THE SIDE RAILING SHALL EXTEND ABOVE THE PARAPET OR
 ROOF EDGE NOT LESS THAN 30 INCHES (762 MM).
 2. LADDERS SHALL HAVE RUNG SPACING NOT TO EXCEED 14
 INCHES (356 MM) ON CENTER.
 3. LADDERS SHALL HAVE A TOE SPACING NOT LESS THAN
 6-INCHES (152 MM) DEEP.
 4. THERE SHALL BE A MINIMUM OF 18 INCHES (457 MM)
 BETWEEN RAILS.
 5. RUNGS SHALL HAVE A MINIMUM 0.75-INCH (19 MM)
 DIAMETER AND BE CAPABLE OF WITHSTANDING A 300-POUND
 (136.1 KG) LOAD.
 6. LADDERS OVER 30 FEET (9144 MM) IN HEIGHT SHALL BE
 PROVIDED WITH OFFSET SECTIONS AND LANDINGS CAPABLE OF
 WITHSTANDING 100 POUNDS PER SQUARE FOOT (488.2 KG/M2).
 7. LADDERS SHALL BE PROTECTED AGAINST CORROSION BY
 APPROVED MEANS. CATWALKS INSTALLED TO PROVIDE THE
 REQUIRED ACCESS SHALL BE NOT LESS THAN 24-INCHES (610
 MM) WIDE AND SHALL HAVE RAILINGS AS REQUIRED FOR
 SERVICE PLATFORMS.
  
 9) SHEET 030_A4.3 SHOWS THE RESTROOMS WITH VANITY
 MILLWORK. AGAIN PLEASE INCORPORATE IN THE LETTER THESE
 UNITS ARE TO BE ADAPTABLE AS TO A PRIVATE OFFICE FOR
 LAVATORY, GRAB BARS ETC?
 2014 FBC-ACCESS. CODE 606.2 EXCEP. 2.
  
 10) SHEET 023_A3.1 NOTE 25 INDICATES FOR THE
 INTERSTITIAL SPACE ACCESS CATWALK 4 FOOT WIDE/ ? INCH
 PLYWOOD & SUSPENDED FROM STEEL STRUCTURE (REF
 STRUCTURAL PLANS). SHEET 035_S2.0 SHOWS THE SUSPENDED
 FRAME. SEE ARCHITECTURAL SHEETS FOR DIMENSIONS AND
 ELEVATIONS. THE DIMENSIONS ARE NOT GIVEN. 107.2.1.3.
 ADDITIONAL INFORMATION IS REQUIRED.
  
 11) SHEET 027_A3.5 INDICATES THE DETAILS FOR THE RAISED
 FLOOR AREA TO BE FOUND ON 036_S3.0 DETAILS 3 & 4.
 THE USE OF STRUCTURAL FOAM IS TO BE USED AS A FILLER.
 PLEASE PROVIDE DETAILS OF THE FOAM BEING TOTALLY
 ENCASED TO COMPLY WITH 2016 FBC-B 2603.4.1.1.
  
 12) SHEET 027_ A3.5 AND 036_S3.0 SHOW THE STAIRS TO BE
 CONCRETE WITH REBAR BUT WHERE IS THE RUN AND RISE FOUND
 FOR THE STAIR? 2014 FBC-B 1009.7 STAIR TREADS AND
 RISERS. STAIR TREADS AND RISERS SHALL COMPLY WITH
 SECTIONS 1009.7.1 THROUGH 1009.7.5.3.
  
 13) PLEASE PROVIDE WHERE EXTERIOR WALL DETAILS FOR WALL
 INSULATION AND FOR THE ROOF TOP INSULATION CAN BE FOUND
 IN COMPLIANCE WITH THE ENERGY CODE. 2014 ENERGY CODE
 C401.2.
  
 14) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 15) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  