Plan Review Notes
Plan Review Notes For Permit 16070085
Permit Number 16070085
Review Stop M
Sequence Number 1
Notes
Date Text
2016-07-11 16:13:261ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16070085
 7/11/16
  
 1) SHEET M-111: THE EXCEPTION THAT ALLOWED THE USE OF
 BOOSTER FANS UNDER SECTION 504.6.4.1 IN THE FBC-10
 MECHANICAL CODE WAS REMOVED FROM THE FBC-14 MECHANICAL
 CODE. PLEASE REMOVE THE FAN FROM THE PLAN AND PROVIDE
 THE TOTAL LENGTH OF THE DRYER EXHAUST DUCT RUN USING
 TABLE 504.5.1.
  
 2) M-111: REFER TO SECTION 504.6.4.2 AND SUBMIT
 MANUFACTURER'S SPECIFICATIONS FOR THE DRYER.
  
 3) M-111: REFER TO SECTION 5043.5 AND PROVIDE MAKEUP
 AIR FOR THE DRYER IF THE EXHAUST CAPACITY EXCEEDS 200
 CFMS.
  
 4) M-111: PROVIDE KEYED NOTE #3 AT THE 10X6 DUCT
 CONNECTION IN THE KITCHEN.
  
 5) M-111: PROVIDE AN EXHAUST SYSTEM FOR THE NEW
 COOKTOP- REFER TO SECTION 505.1
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  