Notes |
Date |
Text |
2016-07-11 16:13:26 | 1ST REVIEW: FBC 2014 MECHANICAL | | PERMIT #16070085 | | 7/11/16 | | | | 1) SHEET M-111: THE EXCEPTION THAT ALLOWED THE USE OF | | BOOSTER FANS UNDER SECTION 504.6.4.1 IN THE FBC-10 | | MECHANICAL CODE WAS REMOVED FROM THE FBC-14 MECHANICAL | | CODE. PLEASE REMOVE THE FAN FROM THE PLAN AND PROVIDE | | THE TOTAL LENGTH OF THE DRYER EXHAUST DUCT RUN USING | | TABLE 504.5.1. | | | | 2) M-111: REFER TO SECTION 504.6.4.2 AND SUBMIT | | MANUFACTURER'S SPECIFICATIONS FOR THE DRYER. | | | | 3) M-111: REFER TO SECTION 5043.5 AND PROVIDE MAKEUP | | AIR FOR THE DRYER IF THE EXHAUST CAPACITY EXCEEDS 200 | | CFMS. | | | | 4) M-111: PROVIDE KEYED NOTE #3 AT THE 10X6 DUCT | | CONNECTION IN THE KITCHEN. | | | | 5) M-111: PROVIDE AN EXHAUST SYSTEM FOR THE NEW | | COOKTOP- REFER TO SECTION 505.1 | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|