2016-07-18 16:43:25THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 THIS APPROVAL IS ONLY FOR THE FOUNDATION.
  
  
  
 1) SHEET COV - THERE IS NO REFERNECE TO ANY FIRE CODE
 COMPLIANCE.
  
 AT MINIMUM PLEASE ENSURE COMPLIANCE WITH THE BELOW
 NOTED CODES:
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
 UNDERGROUND FIRE LINE WORK SHALL COMPLY WITH NFPA 24,
 STANDARD FOR THE INSTALLATION OF PRIVATE FIRE SERVICE
 MAINS AND THEIR APPURTENANCES, 2010 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2009 EDITION.
  
  
  
 2) SHEET COV - THERE IS NO INDICATION OF A FIRE
 SPRINKLER SYSTEM. PER NFPA 1, CHAPTER 13, FIRE
 PROTECTION SYSTEMS.
 13.3.2.3 NEW BUILDINGS HOUSING EMERGENCY FIRE, RESCUE,
 OR AMBULANCE SERVICES SHALL BE PROTECTED THROUGHOUT BY
 APPROVED AUTOMATIC SPRINKLER SYSTEMS.
  
 SHOULD ANY WORK RELATED TO THE FIRE SPRINKLER SYSTEM
 INVOLVE UNDERGROUND WORK PLEASE PROVIDED THE
 APPROPRIATE REVISION OR AS-BUILT.
  
  
 3) SHEET COV - WHERE A FIRE PROTECTION ENGINEERED
 SYSTEM IS PROPOSED, PER FLORIDA ADMINISTRATIVE CODE
 SECTION 61G15-32.004, FIRE PROTECTION ENGINEERING
 DOCUMENTS SHALL INCLUDE THE POINT OF SERVICE FOR THE
 WATER SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS
 APPLICABLE TO THE PROJECT, CLASSIFICATION OF HAZARD
 OCCUPANCY FOR EACH ROOM OR AREA, SUPPRESSION SYSTEM
 TYPE, DESIGN DENSITIES, WATER SUPPLY DATA (FIRE PUMP
 DATA, HYDRANT FLOW TEST DATA) AND ANY PERFORMANCE BASED
 INFORMATION SUCH AS PRE-ENGINEERED SYSTEMS.
  
 PLEASE PROVIDE AT MINIMUM A SEALED LETTER FROM A
 QUAILIFED ENGINEER OF RECORD INDICATING THE NOTED
 INFORMATION ABOVE FOR THE PROJECT.
  
  
 4) ALL UNDERGROUND FIRE LINES SHALL BE SUBMITTED,
 CONSTURCTED AND INSPECTED PER NFPA 24.
  
 PLEASE ENSURE ALL UNDERGROUND FIRE LINES COMPLY WITH
 THE ABOVE AND INSPECTED BY FIRE AND MECHANICAL PER THE
 CODE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  
 ALL OTHER COMMENTS ARE NOTED AS INFORMATIONAL FOR THE
 BUILDING PLAN SUBMITTAL:
  
  
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2010 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2010 EDITION.
 FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 10, 2010 EDITION.
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION.
 CLEAN AGENT SYSTEMS SHALL COMPLY WITH NFPA 2001, 2012
 EDITION.
  
  
 1) SHEET 101 A - A NOTE IS INDICATED " RANGE HOOD SEE
 MECHANICAL DRAWINGS FOR DETAIL" NO MECHANICAL SHEET IS
 INCLUDED IN PLAN SUBMITTAL.
  
 PROVIDE APPLICABLE MECHANICAL SHEET.
  
 2) NO SHEETS - NO MECHANCIAL SHEETS ARE INCLUDED IN
 PLAN SUBMITTAL
  
 PROVIDE ALL MECHANICAL SHEETS.
  
 3) NO SHEET - NO REFERENCE IS INDICATED FOR FIRE
 PROTECTION OF THE HOOD SYSTEM. PER NFPA 101, CHAPTER 9
 BUILDING SERVICE AND FIRE PROTECTION EQUIPMENT
 9.2.3 COMMERCIAL COOKING EQUIPMENT. COMMERCIAL COOKING
 EQUIPMENT SHALL BE IN ACCORDANCE WITH NFPA 96, STANDARD
 FOR VENTILATION CONTROL AND FIRE PROTECTION OF
 COMMERCIAL COOKING OPERATIONS, UNLESS SUCH
 INSTALLATIONS ARE APPROVED EXISTING INSTALLATIONS,
 WHICH SHALL BE PERMITTED TO BE CONTINUED IN SERVICE.
 NFPA 96, CHAPTER 4 GENERAL REQUIREMENTS
 4.1 GENERAL.
 4.1.1 COOKING EQUIPMENT USED IN PROCESSES PRODUCING
 SMOKE OR GREASE-LADEN VAPORS SHALL BE EQUIPPED WITH AN
 EXHAUST SYSTEM THAT COMPLIES WITH ALL THE EQUIPMENT AND
 PERFORMANCE REQUIREMENTS OF THIS STANDARD.
 10.1.2* COOKING EQUIPMENT THAT PRODUCES GREASE-LADEN
 VAPORS AND THAT MIGHT BE A SOURCE OF IGNITION OF GREASE
 IN THE HOOD, GREASE REMOVAL DEVICE, OR DUCT SHALL BE
 PROTECTED BY FIRE-EXTINGUISHING EQUIPMENT.
  
 PLEASE PROVIDE AT NOTE AND MINIMUM INDICATING, ALL
 KITCHEN EQUIPMENT AND OPERATIONS SHALL COMPLY WITH NFPA
 96, STANDARD FOR VENTILATION CONTROL AND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS.
 EXTINGUISHMENT AND VENTILATION SYSTEM SHOP DRAWINGS
 SHALL BE SUBMITTED SEPARATELY FOR APPROVAL.
  
  
 4) SHEET A 410 - PER FLORIDA 69A-60.0081; NOTICE
 SIGNAGE IS REQUIRED FOR STRUCTURES WITH LIGHT-FRAME
 TRUSS-TYPE CONSTRUCTION. ANY COMMERCIAL, INDUSTRIAL, OR
 ANY MULTIUNIT RESIDENTIAL STRUCTURE OF THREE UNITS OR
 MORE WHICH USES HORIZONTAL OR VERTICAL LIGHT-FRAME
 TRUSS-TYPE CONSTRUCTION IN ANY PORTION SHALL BE MARKED
 WITH A MALTESE CROSS SIGN MEASURING 8 INCHES
 HORIZONTALLY AND 8 INCHES VERTICALLY, OF A BRIGHT RED
 REFLECTIVE COLOR. THE APPROVED SYMBOL SHALL BE PLACED
 WITHIN 24 INCHES TO THE LEFT OF THE MAIN ENTRY DOOR.
 1. STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE
 MARKED WITH THE LETTER "R".
 2. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS
 SHALL BE MARKED WITH THE LETTER "F".
 3. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF
 SYSTEMS SHALL BE MARKED WITH THE LETTERS "R/F".
  
 PLEASE PROVIDE A NOTE AT MINIMUM INDICATING THE ABOVE.
  
 5) A SHEETS - THERE IS NO DOOR SCHEDULE INCLUDED IN THE
 PLAN SUBMITTAL.
  
 PLEASE PROVIDE THE APPLICABLE DOOR SCHEDULE INCLUDING
 ALL APPLICABLE EXIT HARDWARE AND FIRE RATINGS.
  
  
 6) SHEET A 100 - A GENERATOR AND FUEL TANKS NOTE IS
 INDICATED, WHAT IS THE FUEL SOURCE OF THE GENERATOR?
 THE GENERATOR AND FUEL SOURCE TANKS SHALL BE UNDER
 SEPARATE SHOP DRAWINGS AND PERMITS.
  
 PLEASE PROVIDE A NOTE FOR COMPLIANCE WITH NFPA 110,
 STANDARD FOR EMEGENCY AND STANDBY POWER SYSTEMS AND
 NFPA 54, NATIONAL FUEL GAS CODE.
  
  
  
 7) SHEET A 411 - THERE IS NO HANDRAIL AND/OR GAURDRAIL
 DETAIL FOR THE STAIRS.
  
 PLEASE PROVIDE DETAIL IN COMPLIANCE WITH NFPA 101,
 CHAPTER 7, 7.2.2.4.4 HANDRAIL DETAILS;
 7.2.2.4.4.1 NEW HANDRAILS ON STAIRS SHALL NOT BE LESS
 THAN 34 IN. AND NOT MORE THAN 38 IN. ABOVE THE SURFACE
 OF THE TREAD, MEASURED VERTICALLY TO THE TOP OF THE
 RAIL FROM THE LEADING EDGE OF THE TREAD.
  
 7.2.2.4.5 GUARD DETAILS. SEE 7.1.8 FOR GUARD
 REQUIREMENTS.
 7.2.2.4.5.1 THE HEIGHT OF GUARDS REQUIRED IN 7.1.8
 SHALL BE MEASURED VERTICALLY TO THE TOP OF THE GUARD
 FROM THE SURFACE ADJACENT THERETO.
 7.2.2.4.5.2 GUARDS SHALL BE NOT LESS THAN 42 IN. (1065
 MM) HIGH
  
  
  
 8) SHEET A 411 - THERE IS NO HANDRAIL GAURDRAIL FOR THE
 RAMP.
  
 PLEASE PROVIDE DETAIL IN COMPLIANCE WITH NFPA 101,
 CHAPTER 7, 7.2.5.4 GUARDS AND HANDRAILS. 7.2.5.4.1
 GUARDS COMPLYING WITH 7.2.2.4 SHALL BE PROVIDED FOR
 RAMPS, UNLESS OTHERWISE PROVIDED IN 7.2.5.4.4.
 7.2.5.4.2 HANDRAILS COMPLYING WITH 7.2.2.4 SHALL BE
 PROVIDED ALONG BOTH SIDES OF A RAMP RUN WITH A RISE
 GREATER THAN 6 IN. (150 MM), UNLESS OTHERWISE PROVIDED
 IN 7.2.5.4.4.
 7.2.5.4.3 THE HEIGHT OF HANDRAILS AND GUARDS SHALL BE
 MEASURED VERTICALLY TO THE TOP OF THE GUARD OR RAIL
 FROM THE WALKING SURFACE ADJACENT THERETO.
  
  
  
 9) SHEET E 31 - THERE IS NO INDICATION OF EXIT STAIR
 LIGHTING. 7.8 ILLUMINATION OF MEANS OF EGRESS.
 7.8.1 GENERAL.
 7.8.1.1* ILLUMINATION OF MEANS OF EGRESS SHALL BE
 PROVIDED IN ACCORDANCE WITH SECTION 7.8 FOR EVERY
 BUILDING AND STRUCTURE WHERE REQUIRED IN CHAPTERS 11
 THROUGH 43. FOR THE PURPOSES OF THIS REQUIREMENT, EXIT
 ACCESS SHALL INCLUDE ONLY DESIGNATED STAIRS, AISLES,
 CORRIDORS, RAMPS, ESCALATORS, AND PASSAGEWAYS LEADING
 TO AN EXIT. FOR THE PURPOSES OF THIS REQUIREMENT, EXIT
 DISCHARGE SHALL INCLUDE ONLY DESIGNATED STAIRS, AISLES,
 CORRIDORS, RAMPS, ESCALATORS, WALKWAYS, AND EXIT
 PASSAGEWAYS LEADING TO A PUBLIC WAY.
 7.8.1.2 ILLUMINATION OF MEANS OF EGRESS SHALL BE
 CONTINUOUS DURING THE TIME THAT THE CONDITIONS OF
 OCCUPANCY REQUIRE THAT THE MEANS OF EGRESS BE AVAILABLE
 FOR USE, UNLESS OTHERWISE PROVIDED IN 7.8.1.2.2.
  
  
 10) SHEET E 31 - THERE IS NO INDICATIONS OF THE KITCHEN
 EQUIPMENT PLAN.
  
 PLEASE PROVIDE DETAILS.
  
  
 11) FA 2.1 - THERE IS NO 2ND FLOOR FA PALN.
  
 PLEASE PROVIDE.
  
  
 12) SHEET 101 A - A GWH IS INDICATED WITH NO DETAILS.
  
 LP/NG GAS PIPING AND DETAIL SHALL BE SUBMITTED UNDER
 SEPARATE SHOP DRAWINGS.
  
  
 13) IS LP/NG GAS PROPOSED FOR THE STOVE/OVEN? NO DETAIL
 IS PROVIDED.
  
 LP/NG GAS PIPING AND DETAIL SHALL BE SUBMITTED UNDER
 SEPARATE SHOP DRAWINGS.
  
  
  
 14) FIREMAN POLES ARE INDICATED; HOWEVER, THERE IS NO
 DETAIL, I.E. HOLE SIZE, SAFETY EQUIPMENT, POLE TYPE,
 ETC.
  
 PLEASE PROVIDE DETAIL.
  
  
  
 15) A KNOX BOX IS REQUIRED FOR THIS STRUCTURE LOCATED
 IN COORDINATION WITH THE AHJ.
  
 PLEASE PROVIDE A NOTE.
  
  
  
 16) HOW IS CONTROLLED GATE ACCESS PROVIDED? A KNOX KEY
 SWITCH FOR ENTRY IS RECOMMENDED BUT SHALL BE
 COORDINATED WITH THE AHJ?
  
 PLEASE PROVIDE A NOTE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL