2016-07-20 11:58:44 | ELECTRICAL REVIEW NOTES |
| REVIEWED FOR COMPLIANCE WITH: 5TH EDITION FBC 2014 & |
| NFPA 70 2011 (NEC) |
| |
| JOB NAME: WEST PALM BEACH FIRE STATION #4 |
| JOB ADDRESS: 1718 PARKER AVE. |
| DESCRIPTION: FOUNDATION ONLY |
| MAST. PERMIT: 16070084 |
| REVISION: N/A |
| |
| THE SCOPE OF THIS REVISION IS LIMITED TO THAT INDICATED |
| ABOVE AND ON THE PERMIT APPLICATION, (FOUNDATION ONLY). |
| THE SUBMITTED PLAN SET DOES NOT INCLUDE THE SITE AND OR |
| RISER DIAGRAM. YOU SHALL SUBMIT A SITE PLAN INDICATING |
| THE LOCATION OF THE UTILITY TRANSFORMER SERVICE THE |
| PREMISES AND THE LOCATION OF THE METER AND MAIN |
| DISCONNECTS. FURTHERMORE YOU SHALL INCLUDE AN |
| ELECTRICAL RISER DIAGRAM WITH LOAD CALCS FOR THE |
| PROPOSED STRUCTURE TO DETERMINE PROPER GROUNDING |
| ELECTRODE CONDUCTOR SIZING. |
| |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| GREATLY APPRECIATED. |
| |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME DIRECTLY. |
| |
| THANK YOU, |
| MIKE ALBARRAN |
| ELECTRICAL PLANS EXAMINER |
| PH: 561-805-6746 |
| EMAIL: [email protected] |
| |