2016-07-21 15:15:11 | BUILDING PLAN REVIEW |
| W. P. B. FOUNDATION PERMIT: 16070084 |
| W. P. B. PERMIT: 16071078 BUILDING |
| ADD: 1718 PARKER AVENUE/ FIRE STATION # 4 |
| CONT: HEDRICK BROTHERS |
| TEL: 561-662-8049 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2ND REVIEW |
| DATE: WED. SEEPT. 21/ 2016 |
| ACTION: ON HOLD WAITING FOR SIGNED & SEALED SOILS |
| REPORT. |
| |
| REVIEWED ONLY FOR FOUNDATION!!!!!!! |
| |
| 1A) MISSING SOILS REPORT: 2014 FBC-B 1803.5.2 |
| QUESTIONABLE SOIL. WHERE THE CLASSIFICATION, STRENGTH |
| OR COMPRESSIBILITY OF THE SOIL IS IN DOUBT OR WHERE A |
| LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS |
| CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL BE |
| PERMITTED TO REQUIRE THAT A GEOTECHNICAL INVESTIGATION |
| BE CONDUCTED. |
| |
| 1B) TO BE SUBMITTED UNDER THE MAIN PERMIT: CORRECT!!!! |
| STRUCTURAL CALCULATIONS BY DAVID CHARLAND HAS NOT |
| SIGNED AND SEALED THE INDEX PAGE. 61G15-23.002(2) FL. |
| ADMIN. CODE. A COVER SHEET OR INDEX SHEET FOR |
| ENGINEERING SPECIFICATIONS MAY BE USED AND THAT SHEET |
| MUST BE SIGNED IN RESPONSIBLE CHARGE OF THE PRODUCTION |
| & PREPARATION OF EACH SECTION OF THE ENGINEERING |
| SPECIFICATION WITH SUFFICIENT INFORMATION ON THE COVER |
| SHEET OR INDEX LISTING HOW MANY PAGES ARE COVERED UNDER |
| THE COVER SHEET OR INDEX SHEET. . |
| |
| |
| |