Plan Review Notes
Plan Review Notes For Permit 16070082
Permit Number 16070082
Review Stop G
Sequence Number 1
Notes
Date Text
2016-07-07 06:56:26THE SUBMITTED PLANS ARE SEVERELY DEFICIENT WITH THE
 REQUIRED INFORMATION IN ORDER TO PERFORM A THOROUGH AND
 COMPREHENSIVE REVIEW, COMPLY WITH ALL OF THE FOLLOWING
 REQUIREMENTS.
  
 1.) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING
  
 (IF APPLICABLE) FOR EACH PIPE SIZE. WPB AMENDMENTS TO
 FBC SEC.107.2.1.
  
 2.) TYPE OF GAS (LP OR NATURAL).
  
 3.) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2014 FBC-FUEL GAS SEC.402.2 OR FBC RES.
 SEC. G2413.2. .
  
 4.) SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE
 AND TERMINATION OF THE GAS VENTS PER 2014 FBC-FUEL GAS
 SECS. 502 THRU 505 OR 2014 FBC-RES. SEC.G2426.
  
 5.) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1.
  
 6) SUBMIT A PLAN SHOWING THE LOCATION OF THE TANKLESS
 WATER HEATER AND THE GENERATOR. WPB AMEND. TO FBC SEC.
 107.2.1.
  
 7) THE GENERATOR INSTALLATION SHALL COMPLY WITH NFPA 37
 AND SHALL MEET THE REQUIREMENTS OF UL2200 PER 2014 FGC
 SEC.616.1.
  
 8) SHOW THE DISTANCE OF THE GENERATOR FROM THE EXTERIOR
 WALL OF THE STRUCTURE. THE GENERATOR SHALL BE A MINIMUM
 OF 5 FT. FROM AN EXTERIOR WALL UNLESS THE WALL IS ONE
 HOUR FIRE RATED CONSTRUCTION PER NFPA 37.
  
 9) SHOW THE LOCATION OF ALL DOORS AND WINDOWS ON THE
 PLAN AND THE DISTANCE FROM THE GENERATOR EXHAUST. THE
 GENERATOR EXHAUST SHALL BE A MINIMUM OF 10 FEET FROM
 DOORS AND WINDOWS. FGC SEC.
  
  